The cause of malfunction
Indoor TH. is short or open.
Temp. of Heat sink is over 95°C.
Comunication error (serial
comunication).
DC peak error.
Running current is
overloaded.
D-PIPE TH is short or open.
The LED01M will be blinking
twice.
The LED01M will be blinking 4
times.
The LED01M will be blinking 5
times.
The LED01M will be blinking 6
times.
The LED01M will be blinking 7
times.
The LED01M will be blinking 10
times.
Keep operating state.
Restart comp. on in the OLP short
state.
The operation is off(enable to restart
by remote controller).
Compressor will be turned off
immediately.
Compressor will be turned off
immediately.
Compressor will be turned off
immediately.
Malfunction indicator
The operating state
Error
Code
-51-
1. The malfunction indicator of indoor (see the operating LED of the INDOOR)
Self-diagnosis function
The cause of malfunction
Error
Code
1
Indoor TH. is short or open.
Outdoor TH. is short or open.
Temp. of Heat sink is over
95°C.
Comunication error (serial
comunication).
DC peak error.
Running current is
overloaded.
D-PIPE TH is short or open.
The operating LED will be
blinking once.
The operating LED will be
blinking twice.
The operating LED will be
blinking 4 times.
The operating LED will be
blinking 5 times.
The operating LED will be
blinking 6 times.
The operating LED will be
blinking 7 times.
The LED01M will be blinking 10
times.
Keep operating state.
Keep operating state.
Restart compressor when OLP TH
Temp is 85°C below.
The operation is off(enable to restart
by remote controller).
Compressor will be turned off
immediately.
Compressor will be turned off
immediately.
Compressor will be turned off
immediately.
Malfunction indicator
The operating state
2. The malfunction indicator of outdoor (see the LED01M on the outdoor PCB ass’y)
❈
Error code
➅
,
➆
can’t be operated unless the power cord is removed.
2
4
5
6
7
2
4
5
6
7
10
10
Summary of Contents for LS-J0762YL
Page 66: ...Schematic Diagram 66 Indoor _YL _UL Series ...
Page 67: ... 67 Indoor _NM _NN Series ...
Page 68: ... 68 Outdoor 7K AC Series ...
Page 69: ... 69 Outdoor 12K AC Series ...
Page 70: ... 70 Outdoor 9K DC Series ...
Page 71: ... 71 Outdoor 12K DC Series ...
Page 78: ...Memo 78 ...
Page 79: ...P No 3828A20177G December 2004 Printed in Korea ...