Installation Manual  9

Installation of Unit

Installation Method

No.

Installation works

Descriptions

1

Preparation of tools and installation parts

Preparation of installation

2

Flaring the pipes

To insert the flare nuts, mounted on the 
connection parts of both indoor and 
outdoor unit, onto the copper pipes.

3

Pipe bending

To reduce the flow resistance of refrigerant.

4

Connection of installation parts

Connection of long piping

(elbows, socket etc)

5

Tighten the flare nut (outdoor) 

Connecting the pipings of the outdoor unit.

6

Blowing the pipings

To remove dust and scale in working.

7

Tighten the flare nut (indoor)

Connecting the pipings of the indoor unit.

8

Check a gas-leakage of the connecting 
part of the pipings.

9

Vacuum drying of the piping and indoor unit

The air which contains moisture and which
remains in the refrigeration cycle may cause a 
malfunction on the compressor

10

Open the 3-way (liquid side) and 
3-way (gas side) valves.

11

Form the pipings

To prevent heat loss and sweat

12

Checking the drainage (indoor unit) 

To ensure if water flow drain hose of indoor unit.

13

Connecting the cable between outdoor 

Preparation of the operating

and indoor unit 

14

Connecting the main cable to outdoor unit

15

Supply the power to the crankcase heater

To prevent the liquid back to the compressor.

(Before the operating the unit)

(Heat pump only)

16

Cooling operation
(Use the remote control or display of the
indoor unit)

Summary of Contents for LPUC808FA0

Page 1: ...al completely before installing the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly TYPE FLOOR STANDING P NO 3828A21022A ...

Page 2: ...nstallation method procedure 9 6 Preparation of installation parts and tools 10 7 Preparation of piping 11 8 Connection of piping 12 9 Precautions in bending 12 10 Connecting the cable to the indoor unit 13 11 Connecting the piping to the outdoor unit 14 12 Connecting the cable to the outdoor unit 14 13 Power supply and wiring 15 14 Vacuum drying of the connecting pipes and the indoor unit 17 15 C...

Page 3: ...low the instruction Safety Precautions Installation Install the panel and the cover of control box securely There is risk of fire or electric shock Always install a dedicated circuit and breaker Improper wiring or installation may cause fire or electric shock Use the correctly rated breaker or fuse There is risk of fire or electric shock Do not use a defective or underrated circuit breaker Use thi...

Page 4: ... damage to the product Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property damage product failure and personal injury Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open Moisture may condense and wet or damage furniture Do not store or use flammabl...

Page 5: ...t To avoid vibration or water leakage Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods It may cause a problem for your neighbors Use two or more people to lift and transport the product Avoid personal injury Do not install the product where it will be exposed to sea wind salt spray directly It may cause corrosion on the product Corrosion pa...

Page 6: ...icated by arrows from the wall ceiling or other obstacles The indoor unit must keep the maintenance space 2 Outdoor unit If an awning is built over the unit to prevent direct sunlight or rain exposure be careful that heat radiation from the condenser is not restricted There should not be any animals or plants which could be affected by hot air discharged Ensure the spaces indicated by arrows from ...

Page 7: ...wance length is on the basis of reliability Oil trap should be installed every 5 7 meters 20K 5 8 1 4 25 15 28K 30K 40K 5 8 3 8 30 20 44K 50K 3 4 3 8 40 25 80K 1 5 8 50 30 80K 1 1 2 50 30 Saudi Model 100K 1 1 8 1 2 50 30 Saudi Model PIPE SIZE MODEL GAS SIDE LIQUID SIDE Max Length A m Max Elevation B m Remarks A B Indoor unit Outdoor unit ...

Page 8: ...unit on the concrete or any solid base securely and horizontally by securing it with bolts Ø12mm and nuts 2 If there is any vibration transmitted to the building mount the rubber underneath the outdoor unit Refrigerant amount Before shipment this air conditioner is filled with the rated amount of refrigerant including additional amount required for air purging subject to 7 5m piping length The rat...

Page 9: ...door Connecting the pipings of the indoor unit 8 Check a gas leakage of the connecting part of the pipings 9 Vacuum drying of the piping and indoor unit The air which contains moisture and which remains in the refrigeration cycle may cause a malfunction on the compressor 10 Open the 3 way liquid side and 3 way gas side valves 11 Form the pipings To prevent heat loss and sweat 12 Checking the drain...

Page 10: ... refrigerant amount 11 Bombe Freon 22 Gas charge Cleaning the pipe 12 Spanner To tighten the connecting parts of the pipings 13 Monkey spanner 14 Driver 15 Benchi 150mm Cutting the wires 16 Tapeline To measure the length 17 Core drill To make holes through the concrete wall and blocks 18 Voltmeter Amperemeter Clampmeter To measure the current and voltage 19 Insulation resistance tester To measure ...

Page 11: ... flare nuts attached to indoor and outdoor units than put them on pipe tube having completed burr removal Not possible to put them on after flaring work 4 Flaring work Carry out flaring work using dedicated flaring tool for R 22 as shown below Firmly hold copper tube in a bar or die as indicated dimension in the table above 5 Check Compare the flared work with figure below If flare is noted to be ...

Page 12: ...2 Do not repeat the bending process to prevent the tubing from cracking or crushing 3 Keep in mind that the bending part should not be cracked and make the radius R as long as possible Refer to Fig 2 PIPE SIZE TORQUE 1 4 1 8 Kg m 3 8 4 2 Kg m 1 2 5 5 Kg m 5 8 5 5 Kg m 3 4 6 5 Kg m 1 Move the indoor tubing and drain hose to the hole Remove tubing holder and pull the tubing out of the chassis 2 Repl...

Page 13: ...NTACT T N OF OUTDOOR TERMINAL BLOCK MAGNETIC SWITCH 1 2 3 4 5 6 Terminals on the outdoor unit Housing ASM Connect to Outdoor BR BR BL BL GN YL POWER INPUT 3P4W 380 415V Heater Power POWER INPUT 3P4W 380 415V 1 L 2 N 3 4 1 2 3 R S T N 6 5 4 5 6 Main Terminal on the outdoor unit R S T N Terminals on the indoor unit CONNECT TO CONTACT T N OF OUTDOOR TERMINAL BLOCK 1 2 3 4 5 6 Terminals on the outdoor...

Page 14: ...rench 1 Open the control board cover from the outdoor unit by removing the screws 2 Connect wires to the terminals on the control board individually and secure the cables onto the control board with clamp 3 Secure the control board cover to the original position with the screws CAUTION Perform grounding This product should be grounded Defective grounding could cause an electric shock Gas side pipi...

Page 15: ...y disconnect all supply lines must be fitted for service operations The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could give rise to burn out of the wires See to it that the starting vo...

Page 16: ...ector 3 Remove the service port nut and connect the gauge manifold and the vacuum pump to the service port by the charge hose 4 Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 76cmHg 5 Remove the valve stem nuts and fully open the stems of the 2 way and 3 way valves with a hexagon wrench 6 Tighten the valve stem nuts of the 2 way valve and 3 way valve 7 D...

Page 17: ...Checking the Drainage 1 Remove the inlet grille with your hands as shown right and left and pull in the direction indicated by the arrow 2 Check the drainage Pour a glass of water into the drain pan Ensure if water flows drain hose of indoor unit ...

Page 18: ...ing gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent 1 Tape the piping and connecting cable from down to up 2 In order to prevent water from entering the room form a trap and tape the piping 3 Fix the piping onto the wall with saddle or bracket In case of the outdoor unit is installed below position of the indoor unit In case of the outdoor unit is instal...

Page 19: ... main switch ON Running test should be accomplished as follows Set operation switch at FAN and the fan will start Check to ensure that the fan sounds normal Next set it at COOL and the compressor will start Check to ensure that the compressor sounds normal Check discharge and suction pressure on the compound gauges Check working voltage phase balance and running current Check to ensure that the th...

Page 20: ......

Reviews: