–33–
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
8-1. No cooling operation performed
1) Both the blower and the compressor do not work
NAME PLATE RATING
MINIMUM
MAXIMUM
220V
198V
242V
2) Only blowers do not work
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Other parts than the unit
Magnetic switch for
compressor & fan motor
Operating switch
Protection devices
Electric supply interrupted
Defective power wiring Cut
of power fuse
Too low voltage
Control point is on
condition of "OFF" due to
trouble.
Troubled or defective
contactor
Opened the contact point
with trouble
Measure it with a tester in
case that the same power
source is supplied to other
equipment than the unit,
what and where trouble
can be discovered by
checking the operation of
other equipment.
Measure it with a tester.
Make short-circuit, then
measure it with a tester.
Check it with the eyes or
tester.
Check it with the eyes or
tester.
Repair a switch box and
is relative instrument.
Replacement of fuse
Request a power
supplier to repair.
Check the power source.
Use a thick cable if
necessary.
Replace it if necessary.
Repair or replace it.
Discover the trouble
cause and push the rest
button.
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Air volume change over
switch
Capacitor
Troubled or defective
contact point
Defected
Check it with the eyes or a
tester
Check it with a tester.
Repair or replace it.
Replace it.
Summary of Contents for LP-8091PC
Page 1: ...Package Air Conditioner SERVICE MANUAL MODEL LP 8091PC Библиотека СОК ...
Page 42: ...9 Electronic Control Device 42 9 1 MAIN P C B ASSY ...
Page 44: ...10 Schematic Diagram 44 Circuit and Troubleshooting ...
Page 46: ... 46 14 17 10 19 29 1 13 11 8 1 15 12 8 9 20 22 5 6 7 2 4 3 2 1 16 ...
Page 49: ... 49 Outdoor Unit 4 1 4 2 4 4 4 3 12 8 ...
Page 52: ...P No 3828A30074W April 2000 Printed in Korea ...