– 42 –
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
8.1 No cooling and heating operation performed
1) Both the blower and the compressor do not work
NAME PLATE RATING
MINIMUM
MAXIMUM
220 V
198 V
242 V
380 V
342 V
418 V
2) Only blowers do not work
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Other parts than the unit
Magnetic switch for com-
pressor & fan motor
Operating switch
Protection devices
Electric supply interrupted
Defective power wiring
Cut of power fuse
Too low voltage
Control point is on condi-
tion of "OFF" due to trou-
ble.
Troubled or defective
contactor
Opened the contact point
with trouble
Measure it with a tester in
case that the same
power source is supplied
to other equipment than
the unit, what and where
trouble can be discov-
ered by checking the
operation of other equip-
ment.
Measure it with a tester.
Make short-circuit, then
measure it with a tester.
Check it with the eyes or
tester.
Check it with the eyes or
tester.
Repair a switch box and
is relative instrument.
Replacement of fuse
Request a power
supplier to repair.
Check the power source.
Use a thick cable if nec-
essary.
Replace it if necessary.
Repair or replace it.
Discover the trouble
cause and push the rest
button.
WHAT TROUBLED
COMPLAINTS
HOW TO CHECK
REMEDY
Air volume change over
switch
Capacitor
Troubled or defective
contact point
Defected
Check it with the eyes or a
tester
Check it with a tester.
Repair or replace it.
Replace it.
Summary of Contents for LP-10091CL/XL
Page 1: ...Package Air Conditioner SERVICE MANUAL MODEL LP 10091CL XL LP 15091CL XL LP 20091CL XL ...
Page 7: ...2 1 LP 10091CL XL 2 2 LP 15091CL XL 2 3 LP 20091CL XL 7 2 DIMENSIONS ...
Page 53: ... 53 9 ELECTRONIC CONTROL DEVICE 9 1 MAIN P C B ASSY ...
Page 55: ... 55 10 SCHEMATIC DIAGRAM LP 10091CL XL LP 15091CL XL ...
Page 57: ... 57 22 19 10 4 5 1 12 21 20 15 13 16 2 9 8 7 18 17 6 3 11 14 ...
Page 62: ... 62 3 13 12 9 11 10 2 8 1 6 5 7 4 16 17 24 25 22 20 14 15 23 21 26 19 ...
Page 67: ... 67 3 13 12 9 11 10 2 8 1 6 5 7 4 16 17 24 25 22 20 14 15 23 21 26 19 ...
Page 76: ...11 6 Outdoor Unit LP 20091CL 20091XL 1 Exploded View 76 ...