YES
YES
YES
NO
YES
Is the heating mode?
Is the output
voltage of IC02D on the MAIN
PCB DC5V?
1. Press heating operation key.
2. After reenergizing power supply,
press power "ON/OFF" button.
YES
NO
Is the unit operating?
1. Press power ON/OFF button.
Is the output
voltage of IC02M's 16/15(4WAY B)
on the MAIN PCB DC0V?
1. Check 4WAY A and B.
NO
1. Set following.
'Set Temp. > Room Temp.'
NO
NO
1. Check or exchange IC01D,
IC02D on the MAIN PCB.
YES
Is the voltage
between 4WAY A/B of CN-BYPASS and
NEUTRAL 220V?
NO
1. Check or exchange IC02M.
1. Check or exchange RY8/9(4WAY B).
Set Temp. > Room Temp.?
Possible trouble 10
: No heating operation performed.