Table-3
Supply Fan Performance LK-0880AH/0880BH/0880BHS1/0880CH/0880HH (SI)
External Static Pressure(inches of water)
L/s
2.5
5.1
7.6
10.2
12.7
15.2
17.8
20.3
22.9
25.4
31.8
38.1
RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW RPM BkW
982
1104
1227
1350
1472
645
676
711
749
792
0.19
0.31
0.45
0.62
0.81
668
699
734
773
815
0.24
0.36
0.5
0.66
0.85
691
722
757
796
838
0.28
0.4
0.55
0.71
0.9
714
746
781
819
861
0.33
0.45
0.59
0.76
0.94
738
769
804
842
885
0.38
0.5
0.64
0.8
0.99
761
792
827
866
908
0.42
0.54
0.68
0.85
1.04
784
815
850
889
931
0.47
0.59
0.73
0.89
1.08
807
838
873
912
954
0.51
0.63
0.77
0.94
1.13
830
862
897
935
977
0.56
0.68
0.82
0.98
1.17
854
885
920
958
1001
0.6
0.72
0.87
1.03
1.22
912
943
978
1016
1059
0.72
0.84
0.98
1.14
1.33
970
1001
1036
1074
1117
0.83
0.95
1.09
1.26
1.45
1.5 STANDARD MOTOR & DRIVE
3Hp OVERSIZE MOTOR & DRIVE
Table-4
Supply Fan Performance LK-0880AH/0880BH/0880BHS1/0880CH/0880HH (English)
External Static Pressure(inches of water)
CFM
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.25
1.5
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2080
2340
2600
2860
3120
645
676
711
749
792
0.26
0.42
0.61
0.83
1.08
668
699
734
773
815
0.32
0.48
0.67
0.89
1.14
691
722
757
796
838
0.38
0.54
0.73
0.95
1.2
714
746
781
819
861
0.44
0.6
0.79
1.01
1.27
738
769
804
842
885
0.5
0.66
0.85
1.07
1.33
761
792
827
866
908
0.56
0.73
0.92
1.14
1.39
784
815
850
889
931
0.63
0.79
0.98
1.2
1.45
807
838
873
912
954
0.69
0.85
1.04
1.26
1.51
830
862
897
935
977
0.75
0.91
1.1
1.32
1.57
854
885
920
958
1001
0.81
0.97
1.16
1.38
1.63
912
943
978
1016
1059
0.96
1.12
1.31
1.53
1.79
970
1001
1036
1074
1117
1.12
1.28
1.47
1.69
1.94
1.5 STANDARD MOTOR & DRIVE
3Hp OVERSIZE MOTOR & DRIVE
Table-5
Fan speed Data LK-0880AH/0880BH/0880BHS1/0880CH/0880HH
Standard Motor & Drive
Fan Speed
Over size Motor & Drive
Fan Speed
6 Turn Open
644
694
745
795
845
896
946
751
810
869
928
986
1045
1104
5 Turn Open 4 Turn Open 3 Turn Open 2 Turn Open 1 Turn Open
Closed
• Factory set at 3 turns open.
• Fan motor heat(MBH)= 1.28 x Fan BkW
• Test Condition:
➊
Voltage : 380V
❷
Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.
• Fan motor heat(kW)= 3.26 x Fan Bhp
• Test Condition:
➊
Voltage : 380V
❷
Operating Mode: Fan operation mode with clean filter, dry coil, without electric heater.