Table-2
- 4 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Nominal ton
(Ton)
15
20
Models
LK-1580CH/AH, LK-1580AHS1
LK-2080CH/AH
Electrical Data
ARI Net Cooling Capacity
(BTU/hr)
159,000
224,000
(W)
46,598
65,648
(Kcal/h )
40,071
56,452
Voltage
(V,PH)
380/415V, 3PH
M.C.A(with standard motor)
Cooling
(Amps)
41.9
53.8
Power Input
Cooling
(Watt)
17,200
24,800
Performance
Air Circulation
Nominal CFM
CFM
5,300
8,000
EER
Cooling
(BTU/hr.W)
9.2
9
Sound Rating
Cooling
bell
9.2
9.2
Features
Wired Remote Controller
O(Accessory)
O(Accessory)
Time Delay Safety Function
O
O
Cooling Operation Mode
O
O
Heating Operation Mode(with E/Heater)
O
O
Soft Dry Operation
O
O
Timer Setting (24-Hour on/off)
O
O
Auto rastart mode
O
O
Humidifier function
O
O
Test function
O
O
Self-Diagnosis Function
O
O
Filter type
washable & Anti-fungus
washable & Anti-fungus
Compressor
Type
Reciprocating
Reciprocating
Quantity
2
2
Outdoor Coil
Type
High efficiency
High efficiency
Tube size(O.D)
(inch)
0.375
0.375
(mm)
9.52
9.52
Row/FPI
2R/16FPI
2R/16FPI
Lengh
(inch)
85
78.7
(mm)
2,160
2,000
Face area
(sq.ft)
25.98
32.81
(mm
3
)
2.41
3.05
Indoor Coil
Type
High efficiency
High efficiency
Tube size(O.D)
(inch)
0.375
0.375
(mm)
9.52
9.52
Row/FPI
2R/16FPI
2R/16FPI
Lengh
(inch)
55.1
55.9
(mm)
1,400
1,420
Face area
(sq.ft)
16.08
23.29
(mm
3
)
1.49
2.16
Outdoor Fan
Type
Propeller
Propeller
No. Used/Diameter(in.)
2EA/24"
2EA/26"
Drive Type
Direct
Direct
CFM
9,000
12,500
No. Motor/Motor output(Hp)
2/0.5
2/1.3
Motor RPM
950
950
Indoor Fan
Type
Centrifugal Blower Fan
No. Used
1EA
1EA
Diameter/Width(in.)
15"/15"
18"/18"
Drive Type/Motor Step
Belt/1
Belt/1
No.motors
1EA
1EA
Motor output(standard/oversized)
4.0Hp/5.0Hp
5Hp/7.5Hp
Motor rpm(Standard/oversized)
1440/2980
2980/2980
Drain Connection Size(in.)
1"
1"
Dimensions
Indoor unit (WxHxD)
(mm)
2,438*1,230*1,766
2,774*1,660*1,880
Weight
net
(kg)
530
820
(lbs)
1168
1808
1) Test Condition of ARI Rated Cooling Capacity :
Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB
2) ARI standard
210/240 or 360 for EER
270 for Sound
3) The supply of filters is standard.
COOLING ONLY
Summary of Contents for LK-0580AC
Page 66: ...P NO 3828A30027F AUGUST 2009 ...