The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the
main drain
pipe to
the exterior
an
d le
av
e it
pr
ov
is
io
na
lly
un
til
th
e t
es
t
comes to an end.
• F
ee
d w
ate
r to
th
e fl
ex
ib
le
dra
in
ho
se
an
d
check the piping for leakage.
• Be sure
to check
the drain
pump for
normal
operating and
noise when
electrical wiring
is complete.
• W
he
n t
he
te
st
is
co
mp
le
te
, c
on
ne
ct
th
e
flexible drain
hose to
the drain
port on
the
indoor unit.
Drain test
Feed water
Drain Pump
Drain pan
Flexible drain hose
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip
• Drain piping
must have
down-slope (1/50
to 1/100):
be sure
not to
provide up-and-down slope to prevent reversal flow.
• During
drain piping
connection, be
careful not
to exert
extra force
on the drain port on the indoor unit.
• The
outside diameter
of the
drain connection
on the
indoor unit
is
32mm.
• Be sure to install heat insulation on the drain piping.
Pip
in
g m
ate
ria
l:
Po
ly
vin
yl
ch
lo
rid
e p
ip
e V
P-2
5 a
nd
pipe fittings
Heat insulation
material: Polyethylene
foam with
thick-
ness more than 8 mm.
Upward
routing
not allowed
Pipe clamp
Maintenance
drain port
Indoor unit
D). Drain Piping
7
CA UTION:
After the confirmation of the above conditions, prepare the wiring as follows:
1) Ne
ver fail to have an individual po
wer specialized f
or the air conditioner. As f
or the method of
wiring, be guided b
y the circuit dia
gram posted on the inside of control bo
x cover
.
2) Pro
vide a circuit breaker s
witch between po
wer source and the unit.
3) The scre
ws which fasten the wiring in the casing of electrical fittings are liab
le to come loose
from vibrations to whic
h the unit is subjected during the course of transpor
tation. Chec
k them
and make sure that they are all tightl
y fastened. (If the
y are loose, it could give rise to b
urn-out
of the wires.)
4) Specification of power sour
ce
5) Confirm that electrical capacity is sufficient.
6) Be sure that the star
ting volta
ge is maintained at more than 90 per
cent of the rated volta
ge
1/50~1/100 slope
Hanger
distance
Hanger Brac
ket
Max 700mm
Flexib
le drain hose
Insulation
Metal
clamp
Max 300mm
1~15m
CA UTION :
The supplied fle
xible drain
hose should not be curved,
neither
screwed.
The cur
ved or screwed hose
may cause a leaka
ge of water
.
marked on the name plate.
7) Confirm that the cab
le thickness is as specified in the po
wer sources specification.
(Par
ticularly note the relation between cab
le length and thickness.)
8) Never fail to equip a leaka
ge breaker where it is wet or moist.
9) The f
ollowing tr
oubles w
ould be caused by v
oltag
e drop-do
wn.
• Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the nor-
mal function of an overload protection device.
• Proper starting power is not given to the compressor.
Summary of Contents for JB-Q18GB2A0
Page 5: ...Wide LCD Wired Remote Controller Optional 5 ...
Page 9: ...Installer Setting How to enter installer setting mode 9 ...
Page 10: ...Installer Setting Installer Setting Code Table 10 ...
Page 11: ...Installer Setting Setting Address of Central Control 11 ...
Page 12: ...Cooling Mode 12 ...
Page 13: ...Auto Operation Mode 13 ...
Page 14: ...Dehumidification Mode 14 ...
Page 15: ...Fan Mode 15 ...
Page 16: ...Temperature Setting Room Temperature Checking 16 ...
Page 23: ......
Page 24: ...27 Installer Setting Setting Address of Central Control ...
Page 25: ...26 Installer Setting Installer Setting Code Table ...
Page 26: ...Installer Setting How to enter installer setting mode 25 ...