Installation Manual 27
ENGLISH
Charging
■
Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a
7.5m(25ft) line set for each indoor line.
Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone)
line set length the refrigerant charge has to be adjusted.
■
Whether the line set is made shorter or longer you must adjust the charge based on how many ft
of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot).
Example:
A 80ft line set is used for tri - zone 5 additional ft X 0.22 ounces per foot= add 1.1
ounces of R-410A
Important:
If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using
the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor
unit.
Charging
24k
30m(100ft)
15m(50ft)
3m(10ft)
7.5m(25ft)
7.5m(25ft)
20g/m(0.22oz/ft)
36k
45m(150ft)
15m(50ft)
3m(10ft)
7.5m(25ft)
7.5m(25ft)
20g/m(0.22oz/ft)
Capacity
(Btu/h)
Max total
length of all
pipes (A+B+C)
Max length of
each pipe
(A/B/C)
Min length of
each pipe
(A/B/C)
Max Elevation
between each
indoor unit and
outdoor unit (h1)
Max elevation
between
indoor units
(h2)
Additional
Refrigerant
Summary of Contents for FLEX MULTI SPLIT
Page 32: ...32 Room Air Conditioner Memo ...