Installation
64
Due to our policy of continuous product innovation, some specifications may change without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
External Shutdown Switch Operation
The External Shutdown Switch option must be enabled on the HMI screen in order to use it. Please
ensure that this function is operating normally after the installation.
If it is enabled, the external shutdown switch will make the system operate as stated in the following
table.
Shutdown Switch
Home 8 Operation
Plunger Type
(Mushroom)
Rotary Type
Pressed
OFF position
All Home 8 operations will be shut down (The Home 8 will
be in standby mode with no AC voltage output.).
This operation is the same regardless of AC grid presence.
Released
ON Position
[AC grid present]
The system operation will resume normally soon.
[AC Grid not present (Off-grid or AC grid is down)]
Home 8 operation will only resume when the utility grid is
recovered or when woken by “Black Start” on the Home 8.
y
When Black Start operation is required, follow the guidelines for "Black Start".