Installation of Ceiling Concealed Duct Type Indoor Unit
64
Installation of Ceiling Concealed Duct Type Indoor Unit
2. Ceiling dimension and hanging
bolt location
■
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
• A place where the unit will be leveled and that can
support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Drainage hole
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
A
B
C
1-3 mm
D
(G)
H
I
E
F
A
B
C
D
E
F
(G)
H
I
5.3/18
942 880 466
54 575
30
87
750 186
7.0/24
942 880 466
54 575
30
87
750 186
10.6/36
1242 1180 492
54 600
30
87
830 186
Dimension
Capacity
(kW/kBtu)
NOTE:
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
Summary of Contents for CRNN Series
Page 1: ...Multi V Air Conditioner INSTALLATION MANUAL INDOOR UNIT Model No CRNN_Series ...
Page 4: ...InstallationofWallMountedTypeIndoorUnit 4 Installation of Wall Mounted Type Indoor Unit ...
Page 14: ...InstallationofWallMountedTypeIndoorUnit 14 Memo ...
Page 15: ...InstallationofArtCoolTypeIndoorUnit 15 Installation of Art Cool Type Indoor Unit ...
Page 24: ...InstallationofArtCoolTypeIndoorUnit 24 Memo ...
Page 34: ...InstallationofCeilingCassetteType 1way IndoorUnit 34 Memo ...
Page 44: ...InstallationofCeilingCassetteType 4way IndoorUnit 44 Memo ...
Page 45: ...InstallationofConvertibleTypeIndoorUnit 45 Installation of Convertible Type Indoor Unit ...
Page 60: ...InstallationofConvertibleTypeIndoorUnit 60 Memo ...
Page 70: ...InstallationofCeilingConcealedDuctTypeIndoorUnit 70 Memo ...
Page 71: ...CommonInstallationProcess 71 Common Installation Process ...
Page 86: ...P No 3828A20280A October 2002 Printed in Korea ...