Installation of Ceiling Cassette Type(4 way) Indoor Unit
42
Installation of Ceiling Cassette Type(4 way) Indoor Unit
Air conditioner
unit
Ceiling
board
Decorative panel
Decorative
panel
Fit the insulator (this part) and
be careful for cool air leakage
Good example
Air
Cool air leakage
(no good)
Bad example
Ceiling
board
Air conditioner unit
Feed water
Drain Pump
D i
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX 700mm
CAUTION
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior
and leave it provisionally until the test
comes to an end.
• Feed water to the flexible drain hose and
check the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring
is complete.
• When the test is complete, connect the
flexible drain hose to the drain port on the
indoor unit.
5. Indoor Unit Drain Piping
• Drain piping must have down-slope (1/50 to 1/100): be
sure not to provide up-and-down slope to prevent
reversal flow.
• During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the
indoor unit is 32mm.
• Be sure to install heat insulation on the drain piping.
Drain test
Install certainly the decorative panel.
Cool air leakage causes sweating.
Water drops fall.
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
Heat insulation material: Polyethylene foam with
thickness more than 8 mm.
Summary of Contents for CRNN Series
Page 1: ...Multi V Air Conditioner INSTALLATION MANUAL INDOOR UNIT Model No CRNN_Series ...
Page 4: ...InstallationofWallMountedTypeIndoorUnit 4 Installation of Wall Mounted Type Indoor Unit ...
Page 14: ...InstallationofWallMountedTypeIndoorUnit 14 Memo ...
Page 15: ...InstallationofArtCoolTypeIndoorUnit 15 Installation of Art Cool Type Indoor Unit ...
Page 24: ...InstallationofArtCoolTypeIndoorUnit 24 Memo ...
Page 34: ...InstallationofCeilingCassetteType 1way IndoorUnit 34 Memo ...
Page 44: ...InstallationofCeilingCassetteType 4way IndoorUnit 44 Memo ...
Page 45: ...InstallationofConvertibleTypeIndoorUnit 45 Installation of Convertible Type Indoor Unit ...
Page 60: ...InstallationofConvertibleTypeIndoorUnit 60 Memo ...
Page 70: ...InstallationofCeilingConcealedDuctTypeIndoorUnit 70 Memo ...
Page 71: ...CommonInstallationProcess 71 Common Installation Process ...
Page 86: ...P No 3828A20280A October 2002 Printed in Korea ...