26
Ceiling Concealed Duct Air Conditioner
External Static Pressure & air Flow
External Static Pressure & air Flow
External Static
60
90
110
130
150
180
200
Pressure (Pa)
Capacity(Btu/h) step(HI/Med/Low)
Setting Remote Cotroller's Switch2
Setting RPM
Hi (48 CMM)
120
42 k
Med (42 CMM)
Low E.S.P Mode
High E.S.P Mode
114
Low (36 CMM)
108
48 k
Hi (60 CMM)
127
55 k
Med (50 CMM)
Low E.S.P Mode
High E.S.P Mode
120
Low (40 CMM)
113
60
Ø1/230 V
High
7.5 m
27/19
35/24
20/15
7/6
Static
Pressure
(Pa)
Voltage
(Phase/Volt)
Temperaure(°C DB/°C WB)
Cooling
Heating
Air
Flow
Step
Piping
Length
Indoor
Outdoor
Indoor
Outdoor
Capacities are tested in the following conditions.
NOTICE
Remote Controller
For Low E.S.P Mode
For High E.S.P Mode
S/W 2
1
1. Low/Low E.S.P
2. Standard/high E.S.P
3. High/high E.S.P
3
2
ZONE 1
ZONE 2
ZONE 3
ZONE 4
AUTO
INDOOR
REMO
ZONE 1
ZONE 2
ZONE 3
ZONE 4
2TH
REMO
AUTO INDOOR
100 unit 10 unit
1
Press the
button.
2
Press the
button.
3
Set the volume of each air flow (
Lo
→
Med
→
Hi
) by using the
button. Press the
button to select the air flow.
(The value of E.S.P could be adjusted from 1 to 255.)
(The figure on the left shows when the strong wind’s ESP value
has been set to 127. 127 means 1270 RPM).
4
If you press the
button one more time, the
E.S.P value will be set and the setting mode will
be unset.
• How to set Remote Controller's switch 2
• How to set RPM