Electrical Wiring
n
Using Cool/Heat Selector Installation and Connection
• Connect wires as below figure at the hole of backside of Outdoor Unit Dry Contact.
• Insert the wire in the connection hole pushing the "Push" button.
• Maximum communication line length for Cool/Heat Selector : 200m.
• Setting Main PCB Dip S/W of Master Outdoor Unit.
Mode Change
Fan
Cooling
Back
Heating
Outdoor Unit
GND
GND
GND
Cool/Heat Selector Installation and Connection
n
Without Cool/Heat Selector Installation and Connection
In case, try to set mode without Cool/Heat Selector and try to use other switch except from LG Outdoor
Cool/Heat Selector in field.
Connect signal terminal block as below figure and description.
- How to set mode without Cool/Heat Selector
• Cooling Mode Setting
¿ ‘
GND Connection
¡ ‘
Off (Open)
• Heating Mode Setting
¿ ‘
GND Connection
¡ ‘
GND Connection
• Fan Mode Setting
¿ ‘
Off (Open)
¡ ‘
GND Connection