108
Outdoor Unit
Test Run
Display
Title
Cause of Error
1
8
2
1
Master outdoor unit Main Board Main-
Sub Micom communication error
Master Outdoor Unit Main Board Main-Sub Micom
communication failed
2
Slave1 outdoor unit Main Board Main-
Sub Micom communication error
Slave1 Outdoor Unit Main Board Main-Sub Micom
communication failed
3
Slave2 outdoor unit Main Board Main-
Sub Micom communication error
Slave2 Outdoor Unit Main Board Main-Sub Micom
communication failed
4
Slave3 outdoor unit Main Board Main-
Sub Micom communication error
Slave3 Outdoor Unit Main Board Main-Sub Micom
communication failed
1
8
4
1
Master Inv. oil equalizing pipe
Temperature Sensor error
Master Outdoor Unit oil equalizing temperature Sensor
open or short
2
Slave1 Inv. oil equalizing pipe
Temperature Sensor error
Slave1 Outdoor Unit oil equalizing temperature Sensor
open or short
3
Slave2 Inv. oil equalizing pipe
Temperature Sensor error
Slave2 Outdoor Unit oil equalizing temperature Sensor
open or short
4
Slave3 Inv. oil equalizing pipe
Temperature Sensor error
Slave3 Outdoor Unit oil equalizing temperature Sensor
open or short
1
8
5
1
Master const.1 oil equalizing pipe
Temperature Sensor error
Master Outdoor Unit oil equalizing temperature Sensor
open or short
2
Slave1 const.1 oil equalizing pipe
Temperature Sensor error
Slave1 Outdoor Unit oil equalizing temperature Sensor
open or short
3
Slave2 const.1 oil equalizing pipe
Temperature Sensor error
Slave2 Outdoor Unit oil equalizing temperature Sensor
open or short
4
Slave3 const.1 oil equalizing pipe
Temperature Sensor error
Slave3 Outdoor Unit oil equalizing temperature Sensor
open or short
1
8
6
1
Master const.2 oil equalizing pipe
Temperature Sensor error
Master Outdoor Unit oil equalizing temperature Sensor
open or short
2
Slave1 const.2 oil equalizing pipe
Temperature Sensor error
Slave1 Outdoor Unit oil equalizing temperature Sensor
open or short
3
Slave2 const.2 oil equalizing pipe
Temperature Sensor error
Slave2 Outdoor Unit oil equalizing temperature Sensor
open or short
4
Slave3 const.2 oil equalizing pipe
Temperature Sensor error
Slave3 Outdoor Unit oil equalizing temperature Sensor
open or short
1
9
3
1
Excessive increase of Master Outdoor
Unit Fan PCB Heat Sink Temperature
Master Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
2
Excessive increase of Slave1 Outdoor
Unit Fan PCB Heat Sink Temperature
Slave1 Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
3
Excessive increase of Slave2 Outdoor
Unit Fan PCB Heat Sink Temperature
Slave2 Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
4
Excessive increase of Slave3 Outdoor
Unit Fan PCB Heat Sink Temperature
Slave3 Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
1
9
4
1
Master Outdoor Unit Fan PCB Heat Sink
Temperature Sensor Error
Master Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
2
Slave1 Outdoor Unit Fan PCB Heat Sink
Temperature Sensor Error
Slave1 Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
3
Slave2 Outdoor Unit Fan PCB Heat Sink
Temperature Sensor Error
Slave2 Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
4
Slave3 Outdoor Unit Fan PCB Heat Sink
Temperature Sensor Error
Slave3 Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
Outdoor unit related error