Installation Manual
35
Pipe connections between indoor and outdoor unit
u
Combination of Y branch/header method
1 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
L 150m(200m : Conditional application)
40m(90m : Conditional application)
L 110m
Branch pipe can not be used after header
Branch pipe can not be used after header
2 Outdoor Units
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe
between Outdoor units:
ARCNN21
Ⓕ
: Header
Ⓖ
: Sealed piping
10m or
less
H 110m
Master
Slave
Master
Slave
Master
Slave
L 150m(200m : Conditional application)
40m(90m : Conditional application)
ODU Capacity
Master
≥
Slave