9
25' maximum
8' minimum
16.4' maximum
OIL TRAP
INDOOR UNIT
OUTDOOR UNIT
***Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement:
For systems with maximum elevation of 25 ft. (see chart above and Figure A), refrigerant lines
must be oil trapped between 8 ft. and 16.4 ft. of elevation.
For systems with elevation of greater than 25 ft. (see chart above), refrigerant lines must be oil
trapped at least every 16.4 ft. of elevation.
Figure A.
Example: 25 ft. maximum elevation.
ART COOL MINI-SPLIT
SINGLE ZONE
ELECTRICAL & REFRIGERATION
•
QUICK REFERENCE
NOTE: Please see local electrical codes for proper wire specifications.
All equipment single phase.
*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
Wire Size
Minimum AWG
14-3
Indoor/Outdoor Connecting Cable Minimum AWG
18-4
Electrical Specifications
Type
Model
BTUs
Voltage
Rated Amps
MCA*
MOP**
Art Cool
Indoor
Outdoor
Single Zone
A/C
LA091CNP
9,000
36V DC
115
7.2
15
15
A/C
LA121CNP
12,000
36V DC
115
9.3
15
20
A/C
LA121CNM
11,500
36V DC
115
10.5
15
20
A/C
LA181CNW
18,000
36V DC
230/208
9.8
15
20
H/P
LA091HNP
9,000
36V DC
115
7.2
15
20
H/P
LA121HNP
12,000
36V DC
115
9.3
15
20
H/P
LA121HNM
11,500
36V DC
115
10.5
15
20
Refrigerant Line & Formula Specifications*
Type
Model
BTUs
Pipe Size
Additional
Max. Pipe
Max.
Art Cool
Liquid
Suction
Refrigerant
Length
Elevation
Single Zone
A/C
LA091CNP
9,000
1/4"
1/2"
0.21 oz./ft.
50'
25'
A/C
LA121CNP
12,000
1/4"
1/2"
0.21 oz./ft.
50'
25'
A/C
LA121CNM
11,500
1/4"
1/2"
0.21 oz./ft.
50'
25'
A/C
LA181CNW
18,000
1/4"
1/2"
0.21 oz./ft.
100'
50'
H/P
LA091HNP
9,000
1/4"
1/2"
0.21 oz./ft.
50'
25'
H/P
LA121HNP
12,000
1/4"
1/2 "
0.21 oz./ft.
50'
25'
H/P
LA121HNM
11,500
1/4"
1/2 "
0.21 oz./ft.
50'
25'
Electrical Specifications
Refrigerant Line Specifications***