18
Single Zone
Art Cool Premier W
all Mounted Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL INSTALLATION GUIDELINES
Mounting of Indoor Unit Installation Plate
Follow this procedure and best practices when mounting the indoor
unit’s plate to a wall.
Note:
Select location carefully. Unit should be anchored to a strong wall to
prevent unnecessary vibration.
WARNING
• When choosing a location for the wall mount plate, be sure to take
into consideration routing of wiring for power outlets within the wall.
Touching wiring can cause serious bodily injury, or death.
• Use caution when drilling holes through the walls for the purposes
of piping connections. Touching power wiring with tools or bare skin
can cause serious bodily injury, or death.
Procedure
1. Locate the installation plate and five Type A screws (Figure 8).
2. Position the installation plate horizontally on the wall. Align the
centerline, and use a leveling tool to ensure the plate is level.
3. Secure plate to the wall with the five Type A screws (Figure 10).
If mounting on a concrete wall, use field-supplied anchor bolts.
4. Observe the left and right rear piping clearance when drilling into
the wall.
Mounting Installation Plate to Wall
Figure 7: Drilling Piping Hole
Figure 8: Provided Installation Parts
Drilling Piping Hole in the Wall
Follow the left or right piping clearance recommendations as shown
in Figure 9.
1. Using a 2 5/8 (
ø
65mm) inch hole core drill bit, drill a hole at
either the right or left side of the wall mounting (Figure 10).
• The slant of the hole should be 3/16” to 5/16” from level with the
slant being upward on the indoor unit side and downward
on the outdoor unit side (Figure 7).
2. Finish off the hole as shown with bushing and sleeve
covering. The sleeve and bushing prevents damage to
the tubing/bundling of the piping.
(3/16"~5/16")
Indoor
WALL
Outdoor
Bushing
Core Drill
Sleeve
Figure 9: LAN090HYV1 / LAN120HYV1 Installation Plate Dimensions
See
Refrigerant Piping Connections for Indoor Unit on
to proceed with piping.
Installation plate
Type "A" screw
Type "B" screw
Type "C" screw
Type "D" screw
Bracket
Wireless controller
holder
Figure 10: Installation Plate
Type A Screws
Installation
Plate
Chassis
Hook
Type "A"
Screws (5)
Ø2-9/16
4-13/16
6-11/16
Right
rear
piping
Left
rear
piping
Installation Plate
Place a level on raised tab
Indoor Unit Outline
8-17/32
6-29/32
Unit: inch
17
17-5/16
Ø2-9/16
Figure 11: LAN180HYV1 / LAN240HYV1 Installation Plate Dimensions
Left
rear
piping
Unit Outline
6
1/
5
-1
2
6
1/
1
1
-1
2
Unit : Inch
2-3/8
1-7/16
1-5/16
13
Ø2-9/16
3-15/16
7-3/16
Ø2-9/16
2-3/4
7-11/16
Installation Plate
Right
rear
piping
Place a level on raised tab