GENERAL INSTALLATION GUIDELINES
Mounting of Indoor Unit
Drilling Piping Hole in the Wall
Follow the left or right piping clearance recommendations as shown in Figure 11 and
12.
1. Using a 2-5/8 (ø65mm) inch hole core drill bit, drill a hole at either the right or left
side of the wall mounting (Figure 13).
• The slant of the hole should be 3/16” to 5/16” from level with the slant being upward
on the indoor unit side and downward on the outdoor unit side.
2. Finish off the newly drilled hole as shown with bushing and sleeve covering.
• Sleeve and bushing prevents damage to the tubing/bundling of the piping.
(3/16"~5/16")
Indoor
WALL
Outdoor
Bushing
Core Drill
Sleeve
Figure 13: Drilling Piping Hole
Mounting the Indoor Unit to the Installation Plate
Installation plate
Indoor unit
3”
Spacer
1
2
Preparing for Piping/Electrical Connection
1. To prepare indoor unit for piping, disengage bottom on indoor unit from installation
plate by reversing step 3 from previous procedure.
• This step will separate the indoor unit’s bottom side from the wall mount in order
to route drain hose correctly. See Figure 17 for a reference of the rear view of the
indoor unit.
2. Swing drain hose holder (L-bracket) out and anchor as shown in Figure 15,
against installation plate.
3. Optionally, go to
Refrigerant Piping Connections
section of this manual to
continue with piping connections to the indoor unit.
4. Optionally, go to
Electrical Connections
section of this manual to continue
with conduit/electrical wiring to the indoor unit.
Figure 14: Mounting Unit on Installation Plate
Figure 15: Mounting Unit on Installation Plate
Figure 16: Mounting Bottom of Unit to Installation Plate
Figure 17: Rear View of IDU
side of the indoor unit from the wall .
Installation Plate
Drain Hose
Holder
L-bracket
Type 'C' Screws
Bottom of
Indoor Unit
Indoor Unit
Piping
Through
Wall
Installation Plate
Drain Hose
Drain Hose Holder
1. Hook the indoor unit onto the upper portion of the installation plate (Figure 14).
2. Engage the hooks at the top of the indoor unit with the upper edge of the installation
plate.
• Ensure that the hooks are properly seated on the installation plate by moving it left
and right.
3. Move the bottom of indoor unit towards the installation plate to anchor to wall (Figure
15).
• It helps to press the lower left and right sides of the unit against the installation plate
until the hooks engage into their slots.
• You will hear a clicking sound as the bottom attaches to the installation plate
successfully.
4. Finish by inserting and tightening two type “C” screws into the bottom of the installa-
tion plate (Figure 16).
• Pay attention to the positioning of the piping through any wall as shown in the figure,
as you insert the screws to the indoor unit.