Installation Manual
13
Installation
ENGLISH
- The appliance shall be installed, operated and stored in a room with a floor area larger than the
minimum area.
- Use the graph of table to determine the minimum area.
- m : Total refrigerant amount in the system
- Total refrigerant amount : factory refrigerant additional refrigerant amount
- Amin : minimum area for installation
Minimum floor area
0
100
200
300
400
500
600
Amin (m
2
)
m (kg)
0
1.224
2
3
4
5
6
7
8
Floor standing
Wall mounted
Ceiling mounted
Floor location
m (kg)
Amin (m
2
)
< 1.224
-
1.224
12.9
1.4
16.82
1.6
21.97
1.8
27.80
2
34.32
2.2
41.53
2.4
49.42
2.6
58.00
2.8
67.27
3
77.22
3.2
87.86
3.4
99.19
3.6
111.20
3.8
123.90
4
137.29
4.2
151.36
4.4
166.12
Floor location
m (kg)
Amin (m
2
)
4.6
181.56
4.8
197.70
5
214.51
5.2
232.02
5.4
250.21
5.6
269.09
5.8
288.65
6
308.90
6.2
329.84
6.4
351.46
6.6
373.77
6.8
396.76
7
420.45
7.2
444.81
7.4
469.87
7.6
495.61
7.8
522.04
Wall mounted
m (kg)
Amin (m
2
)
< 1.224
-
1.224
1.43
1.4
1.87
1.6
2.44
1.8
3.09
2
3.81
2.2
4.61
2.4
5.49
2.6
6.44
2.8
7.47
3
8.58
3.2
9.76
3.4
11.02
3.6
12.36
3.8
13.77
4
15.25
4.2
16.82
4.4
18.46
Wall mounted
m (kg)
Amin (m
2
)
4.6
20.17
4.8
21.97
5
23.83
5.2
25.78
5.4
27.80
5.6
29.90
5.8
32.07
6
34.32
6.2
36.65
6.4
39.05
6.6
41.53
6.8
44.08
7
46.72
7.2
49.42
7.4
52.21
7.6
55.07
7.8
58.00
Ceiling Mounted
m (kg)
Amin (m
2
)
< 1.224
-
1.224
0.956
1.4
1.25
1.6
1.63
1.8
2.07
2
2.55
2.2
3.09
2.4
3.68
2.6
4.31
2.8
5.00
3
5.74
3.2
6.54
3.4
7.38
3.6
8.27
3.8
9.22
4
10.21
4.2
11.26
4.4
12.36
Ceiling Mounted
m (kg)
Amin (m
2
)
4.6
13.50
4.8
14.70
5
15.96
5.2
17.26
5.4
18.61
5.6
20.01
5.8
21.47
6
22.98
6.2
24.53
6.4
26.14
6.6
27.80
6.8
29.51
7
31.27
7.2
33.09
7.4
34.95
7.6
36.86
7.8
38.83
(for R32)