12 | FLOOR STANDING
MUL
TI V Floor
, Suspended, Convertible Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
FLOOR STANDING
Electrical Data
Table 3: Floor Standing (CEA, CFA [Cased]; CEU, CFU [Uncased]) Indoor Unit Electrical Data.
Model
Voltage Range
MCA
MOP
Rated Amps (A)
Power Supply
Power Input (W)
Hz
Volts
Phase
Cooling
Heating
CEA / CFA (Cased) Units
ARNU073CEA4
208-230
1.0
15
0.76
60
208-230
1
85
85
ARNU093CEA4
1.0
0.76
85
85
ARNU123CEA4
1.0
0.76
85
85
ARNU153CEA4
1.0
0.76
85
85
ARNU183CFA4
1.2
15
0.97
115
115
ARNU243CFA4
1.2
0.97
115
115
CEU / CFU (Uncased) Units
ARNU073CEU4
208-230
1.0
15
0.76
60
208-230
1
85
85
ARNU093CEU4
1.0
0.76
85
85
ARNU123CEU4
1.0
0.76
85
85
ARNU153CEU4
1.0
0.76
85
85
ARNU183CFU4
1.2
15
0.97
115
115
ARNU243CFU4
1.2
0.97
115
115
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.