Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Figure43: EEV Module
Drawing
Reference
Label
Unit Connection
Type
Position Indicates
Range
2
CH1 CH1 port of Other module for communication
RS485
CH2 IDU_Bus_A&B (To Outdoor Unit)
RS485
3
RI1
Main Coil #1 Refrigerant temperature (Pipe In)
NTC 5k
-130-210F
RI2
Main Coil #1 Refrigerant temperature (Pipe out)
NTC 5k
-130-210F
4
EEV1 Unassigned
EEV2 Main Coil #1 EEV
Step Control
0 - 1350
#2(Reheat Coil)
Drawing
Reference
Label
Unit Connection
Type
Position Indicates
Range
2
CH1 CH1 port of Other module for communication
RS485
CH2 IDU_Bus_A&B
RS485
3
RI1
Reheat Coil Refrigerant temperature (Pipe In)
NTC 5k
-130-210F
RI2
Reheat Coil Refrigerant temperature (Pipe out)
NTC 5k
-130-210F
4
EEV1 Unassigned
EEV2 Reheat Coil EEV
Step Control
0 - 1350
#1(Main Coil
48