BACnet / Modbus Points List
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
%$&1(702'%8632,176/,67
Variable
Description
Active
Text
Inactive
Text
BACnet
Modbus
Access
COV
Incre. Index
Register
Type Size
x 0.1
Req.
,QSXW5HJLVWHU
I073_SAFanOperationRate
Supply Fan Motor Speed (%)
ReadCOV_NoWrite
1
30074 Input
2
I074_EAFanOperationRate
Exhaust Fan Motor Speed (%)
ReadCOV_NoWrite
1
30075 Input
2
I075_ERWOperationRate
Energy Recovery Wheel Motor
Speed (%) by Cycle Period
ReadCOV_NoWrite
1
30076 Input
2
I076_MainCoilOperationRate
Target Pressure Adjustment
Value (%) by Cycle Period
ReadCOV_NoWrite
1
30077 Input
2
I077_ReheatCoilOperationRate
Reheat Coil EEV Adjustment
Value (%) by Cycle Period
ReadCOV_NoWrite
1
30078 Input
2
I078_PreheatCoilOperationRate
Electric Heater
Read_NoWrite
30079 Input
2
I079_RecoveryCoilOperationRate
Recovery Coil EEV Adjustment
Value (%) by Cycle Period
ReadCOV_NoWrite
1
30080 Input
2
I080_TargetHighPressure
Target High Pressure of
Outdoor Unit
Read_NoWrite
30081 Input
2
I081_TargetLowPressure
Target Low Pressure of
Outdoor Unit
Read_NoWrite
30082 Input
2
I084_ReheatCoilEEVPulse
Reheat Coil EEV Pulse Value
Read_NoWrite
30085 Input
2
I086_SAFanFlowVolume
Supply Air Flow Rate
ReadCOV_NoWrite
2
30087 Input
2
I087_EAFanFlowVolume
Exhaust Air Flow Rate (if
Differential Pressure Sensor is
equipped)
ReadCOV_NoWrite
2
30088 Input
2
I9004_ODU1_HighPressureTrace
ODU Main High Pressure
Read_NoWrite
39005 Input
2
I9005_ODU1_LowPressureTrace
ODU Main Low Pressure
Read_NoWrite
39006 Input
2
I9012_ODU1_Inv1Trace
ODU Main Inverter #1
Compressor Hz
Read_NoWrite
39013 Input
2
I9014_ODU1_Inv2Trace
ODU Main Inverter #2
Compressor Hz
Read_NoWrite
39015 Input
2
I9015_ODU1_Fan1Trace
ODU Main Fan #1 RPM
Read_NoWrite
39016 Input
2
I9016_ODU1_Fan2Trace
ODU Main Fan #1 RPM
Read_NoWrite
39017 Input
2
I9023_ODU1_AirTemp
ODU Main Ambient
Temperature
Read_NoWrite
39024 Input
2
ż
I9024_ODU1_SuctionTemp
ODU Main Suction Pipe
Refrigerant Temperature
Read_NoWrite
39025 Input
2
ż
I9025_ODU1_CondeseTemp
ODU Main Condenser
Refrigerant Temperature
Read_NoWrite
39026 Input
2
ż
I9026_ODU1_EvaporateTemp
ODU Master Evaporator
Refrigerant Temperature
Read_NoWrite
39027 Input
2
ż
I9036_ODU1_Inv1IPMTemp
ODU Main Inverter #1
Heat-Sink Temperature
Read_NoWrite
39037 Input
2
I9037_ODU1_Inv2IPMTemp
ODU Main Inverter #2
Heat-Sink Temperature
Read_NoWrite
39038 Input
2
I9038_ODU1_Inv1InputCT
ODU Main Inverter #1 Input
Current (CT)
Read_NoWrite
39039 Input
2
ż
I9039_ODU1_Inv2InputCT
ODU Main Inverter #2 Input
Current (CT)
Read_NoWrite
39040 Input
2
I9040_ODU1_Inv1InputVT
ODU Main Inverter #1 Input
Voltage
Read_NoWrite
39041 Input
2
I9041_ODU1_Inv2InputVT
ODU Main Inverter #2 Input
Voltage
Read_NoWrite
39042 Input
2
I9042_ODU1_Inv1PhaseCT
ODU Main Inverter #1 Phase
Current
Read_NoWrite
39043 Input
2
I9043_ODU1_Inv2PhaseCT
ODU Main Inverter #2 Phase
Current
Read_NoWrite
39044 Input
2
Table 27: BACnet / Modbus Points List for DOAS Units Table, continued.