ELECTRICAL SYSTEM
LG Control Board Layout
Figure 20: Main Module.
Drawing
Reference Terminal
Unit Connection
Type
Position Indicates
Range
2
CH1
CAREL J4 Field Bus Connector (For Communication with CAREL)
RS-485
CH2
RS-485 communication with other Module’s CH1
RS-485
CH3
CEN_Bus A&B (To Outdoor Unit)
RS-485
CH4
BMS_Bus A&B (To Outdoor Unit)
RS-485
3
UI1
Unassigned
0 – 10Vdc
UI2
Outdoor Air Humidity
0 – 10Vdc
0~100%
UI3
Supply Air Temperature (Field Option)
0 – 10Vdc
-130-210°F
UI4
Supply Air Relative Humidity (Field Option)
0 – 10Vdc
0~100%
UI5
Differential Pressure Sensor (For SA flow rate monitoring and
CFM Modulation)
0 – 10Vdc
0-30”wc
UI6
Unassigned
0 – 10Vdc
UI7
Unassigned
UI8
Space CO
2
Sensor (Field Option)
0 – 10Vdc
0-3,000ppm
4
DI1
Forced Stop
NC (Open = Unit Stop)
DI2
Unit On / Off
NO (Closed = Unit On)
DI3
Float Switch
NC (Open = Unit Stop)
5
AO1
Unassigned
0 – 10Vdc
AO2
Unassigned
0 – 10Vdc
AO3
Unassigned
0 – 10Vdc
AO4
Unassigned
0 – 10Vdc
AO5
Heater_1 (Filed Option) * Only for Split Compact DOAS
0 – 10Vdc
AO6
Heater_2 (Filed Option) * Only for Split Compact DOAS
0 – 10Vdc
6
DO1
DO1-COM Error status
C type
NO (Closed = Alarm)
(C) - COM
NC (Open = Alarm)
DO2
On / Off Status
NO (Closed= Unit On
1
)
DO3
Unassigned
DO4
Unassigned
DO5
Unassigned
DO6
Solenoid Valve (Reheat Coil)
NO (Closed= Valve open) Open/Close
Table 15: Main Module Component Details.
1
If the fan is operating, it indicates as unit on.
Terminal Connections for Electrical Components
Main Module