- 70 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
5. Trouble Shooting
6.8 Check code Trouble shooting CH04
Check the wire
connection (Open,
Soldered poorly)
❊
Drain pump check
Check drain tube
installation
Is it normal ?
Check the level of
water (Float moves top
position)
Is it normal ?
Check the wire
connection (Open,
Soldered poorly)
Is the float
switch clean ?
Yes
Yes
No
Check Drain Pump
Yes
No
Correct connection
Or re-soldering PCB
Is the resistance of
Drain Pump? Normal
( about 400
Ω
) ?
Yes
No
Change the Drain Pump
Is the drain
pump clean ?
Yes
No
Clean drain pump
No
Clean float switch
Is the resistance of f
loat switch normal
(short) ?
Yes
No
Change the float switch
Is it normal ?
No
Correct connection
Or re-soldering PCB
Check Flow Chart
CN-Float
CN-Float
04
Drain pump
/ Float switch
• Float switch open.
(Normal : short)
• Water over flow
• The connection of wire (Drain pump/ Float switch)
• Drain pump power input. (220V)
• Drain tube installation.
• Indoor unit installation. (Inclination)
Display
code
Title
Cause of error
Check point & Normal condition
Summary of Contents for APNH2433LAD