5. Trouble Shooting
1. Self-diagnosis Function
1.1 Error Indicator (Indoor)
• The function is to self-diagnosis air conditioner and express the troubles if there is any trouble.
• Error mark is displayed on display window of indoor units and wired-remote controller, and LED of outdoor unit control
board.
• If more than two troubles occur simultaneously, lower number of error code is first displayed.
• After error occurs, if error is released, error LED is also released simultaneously.
1 Time
1 Time
1 Time
2 Times
2 Times
2 Times
10 digit
LED
1 digit
LED
1 Sec.
2 Sec.
2 Sec.
1 Sec.
1 Sec.
1 digit
10 digit
Ex) Error 21 (DC Peak)
1.2 Indoor Error
Error code
Description
INV TPS
LED 1
(Red)
LED 2
(Green)
Indoor
Status
00
No Error
ON
01
Indoor Room themistor error
1time
OFF
02
Indoor in-piping sensor error
2times
OFF
03
Remote controller error
3times
OFF
04
Drain Pump error
4times
OFF
05
Communcation error between in and out
5times
OFF
06
Indoor Out-Piping sensor error
6times
OFF
07
Differnt mode operation
7times
OFF
09
Checksum error
9times
OFF
10
BLDC motor fan lock (indoor)
10times
OFF