6.7 Troubleshooting Outdoor Error
CH 35 (Discharge pipe overheating error of Inverter)
h
IPM (Intelligent Power Module) : The part to control the inverter compressor
Items
Contents
Purpose
Possible damage of compressor due to excessive low pressure
Condition for Generation The low pressure of outdoor unit is decreased excessively.
Expected
Causes
Installation
Lack and leakage of refrigerant
Service valve clogged in case of deformation or shielding by refrig-
eration pipe damage (outdoor unit shielding during heating / indoor
filter clogging during cooling)
PCB
Assembly
Outdoor unit PCB defect
Sensor
Low pressure sensor defect
Indoor pipe temperature sensor defect
Others
Indoor unit or outdoor unit fan failure
EEV defect