background image

Indoor unit

R32 Heat Pump (50 / 60Hz)

0CTI5-02A (Replaces 0CTI5-01C)

P/No. : MFL67502513

Summary of Contents for AM07BP NSJ

Page 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 02A Replaces 0CTI5 01C P No MFL67502513 ...

Page 2: ... General information Product data Wall Mounted Unit Wall Mounted Unit 2 ART COOL Mirror Ceiling Mounted cassette 4 way Ceiling concealed duct Middle static pressure Ceiling concealed duct Low static pressure Ceiling Suspended Unit ...

Page 3: ...General information MULTI SINGLE Indoor unit 1 Model Line Up 2 External Appearance 3 Nomenclature ...

Page 4: ...orinated greenhouse gases Category Chassis Name Capacity Index kW kBtu h 1 5 5 2 1 7 2 5 9 3 5 12 4 2 15 5 0 18 7 1 24 10 0 36 12 0 42 14 0 48 15 0 60 Wall Mounted Unit R410A R32 Common Deluxe SJ SK Standard plus SJ SK Standard SJ SK Wall Mounted Unit 2 R32 only Deluxe SJ SK Standard plus SJ SK Standard SJ SK ART COOL Mirror SJ SK Ceiling Mounted Cassette 4 Way TR TQ TP TM Ceiling Concealed Duct M...

Page 5: ...NM12JA3BA SC12EQ NSJ S3NM18KL3BA SC18EQ NSK ART COOL Mirror AMNW07GSJR0 AM07BP NSJ USNW09GJRZ0 AM09BP NSJ USNW12GJRZ0 AM12BP NSJ USNW18GKRZ0 AM18BP NSK AMNW24GSKR0 AM24BP NSK Ceiling Suspended Unit Ceiling Mounted Cassette 4 way ZVNW18GM1A0 UV18R N10 ZVNW24GM1A0 UV24R N10 ZVNW36GM2A0 UV36R N20 ZVNW42GM2A0 UV42R N20 ZVNW48GM2A0 UV48R N20 ZVNW60GM2A0 UV60R N20 ZMNW05GTRA0 MT06R NR0 ZMNW07GTRA0 MT08R...

Page 6: ...ss 07 18 000 Btu h Class 18 4 Electrical rating G 1Ø 220 240V 50 Hz 1Ø 220V 60 Hz 5 Indoor unit type for Z N ASN USN series models Chassis name Indoor unit type for AMN series models S Wall Mounted Unit ART COOL Mirror T Ceiling Mounted Cassette 6 Indoor unit type for Z N ASN USN series models L Basic 1 Deluxe type 2 Standard plus type 3 Standard type R ARTCOOL Mirror type Indoor unit type for AMN...

Page 7: ...M Common Indoor unit for Multi and Residential system 5 Nominal Capacity Ex 7 000 Btu h Class 07 18 000 Btu h Class 18 6 Indoor unit Chassis name J SJ K SK 7 Outdoor unit Chassis name for Residential system L UL2 2 U24A 4 U4 8 Look Color SJ SK Chassis R ART COOL Mirror Black 1 R Look White Panel Transparent 2 Semi R Look White Panel Silver Deco 3 E Look White Pane 9 Function B Non Ionizer 4way F N...

Page 8: ...ndoor units only for Multi systems U Indoor units only for Single CAC systems C Common Indoor Unit for Multi and Single CAC 2 Product type T Ceiling Mounted Cassette B L Ceiling Concealed Duct V Ceiling Suspended Unit 3 Nominal Capacity Ex 7 000 Btu h Class 07 18 000 Btu h Class 18 4 Detailed product type R Indoor Units using R32 5 Indoor Unit Outdoor Units N Indoor Unit U Outdoor Unit 6 Chassis n...

Page 9: ...Product type D Deluxe P Standard or Standard plus A ARTCOOL Mirror 2 Connectable Outdoor unit type M Common Indoor unit for Multi and Residential system 3 Nominal Capacity Ex 7 000 Btu h Class 07 18 000 Btu h Class 18 4 Product Look R R Look E E Look S Semi R Look B Mirror Look 5 Serial 6 Indoor Unit Outdoor Units N Indoor Unit U Outdoor Unit 7 Chassis name ...

Page 10: ...cation 1 Product type D Deluxe P Standard plus S Standard A ARTCOOL Mirror 2 Connectable Outdoor unit type C Multi Compatible 3 Nominal Capacity Ex 7 000 Btu h Class 07 18 000 Btu h Class 18 4 Product Look R R Look S Semi R Look E E Look B Black Mirror Look 5 Serial 6 Indoor Unit Outdoor Units N Indoor Unit U Outdoor Unit 7 Chassis name ...

Page 11: ... SINGLE Indoor unit FDF Wall Mounted Unit Wall Mounted Unit 2 ARTCOOL Mirror Ceiling Mounted cassette 4 way Ceiling concealed duct Middle static pressure Ceiling concealed duct Low static pressure Ceiling Suspended Unit ...

Page 12: ...Wall Mounted Unit MULTI SINGLE Indoor unit 1 List of Functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring diagrams 6 Air flow and temperature distribution 7 Sound levels 8 Installation ...

Page 13: ...uto cleaning O Auto operation artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O 7hr Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Humidity Control X Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP O Note 1 O Applied X Not applied Accessory m...

Page 14: ...ntact For Setback O PDRYCB300 O PDRYCB500 Dry Contact For Modbus X Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 X Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m X 2 ...

Page 15: ...nience Auto changeover X Auto cleaning O Auto operation artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O 7hr Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Humidity Control X Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP O Note 1 O Applied...

Page 16: ...RYCB400 2 Points Dry Contact For Setback O PDRYCB300 O PDRYCB500 Dry Contact For Modbus X Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 X Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control w...

Page 17: ...uto cleaning O Auto operation artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O 7hr Timer on off O Timer weekly X Two thermistor control X Auto Elevation Grille X Special Functions Wi Fi X Humidity Control X Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP X Note 1 O Applied X Not applied Accessory m...

Page 18: ...ntact For Setback X PDRYCB300 X PDRYCB500 Dry Contact For Modbus X Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 X Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m X 2 ...

Page 19: ...27 Sound Power Level Max dB A 56 56 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may be ...

Page 20: ...8 34 29 44 38 34 Sound Power Level Max dB A 56 60 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 12 7 1 2 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some specific...

Page 21: ...nch Ø 12 7 1 2 Drain O D I D mm Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter ...

Page 22: ...31 27 35 32 27 Sound Power Level Max dB A 57 57 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some specificat...

Page 23: ...0 35 27 Sound Power Level Max dB A 57 57 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications ma...

Page 24: ...A 41 36 29 44 38 35 Sound Power Level Max dB A 57 59 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 12 7 1 2 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some speci...

Page 25: ...h Ø 12 7 1 2 Drain O D I D mm Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter sh...

Page 26: ...6 33 27 Sound Power Level Max dB A 57 57 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Connections Method Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some speci...

Page 27: ...B A 40 35 27 44 38 35 Sound Power Level Max dB A 57 59 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 12 7 1 2 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some spe...

Page 28: ... 1 2 Drain O D I D mm Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be ...

Page 29: ...18 MULTI SINGLE Indoor unit Wall Mounted Unit 3 Dimensions Deluxe SJ Chassis AMNW07GSJL0 DM07RP NSJ ASNW09GJ1Z0 DM09RP NSJ ASNW12GJ1Z0 DM12RP NSJ ...

Page 30: ... 19 Wall Mounted Unit Standard Plus Standard SJ Chassis AMNW05GSJB0 PM05SP NSJ AMNW07GSJB0 PM07SP NSJ USNW09GJ2F0 PM09SP NSJ USNW12GJ2F0 PM12SP NSJ AMNW15GSJB0 PM15SP NSJ AMNW07GSJA0 PM07EP NSJ USNW09GJ3A0 PM09EP NSJ USNW12GJ3A0 PM12EP NSJ ...

Page 31: ...LTI SINGLE Indoor unit Wall Mounted Unit Deluxe Standard Plus Standard SK Chassis ASNW18GK1Z0 DM18RP NSK ASNW24GK1Z0 DM24RP NSK USNW18GK2F0 PM18SP NSK USNW24GK2F0 PM24SP NSK USNW18GK3A0 PM18EP NSK AMNW24GSKA0 PM24EP NSK ...

Page 32: ... outlet temperature CN TH2 Model Gas Liquid AMNW07GSJL0 DM07RP NSJ ASNW09GJ1Z0 DM09RP NSJ ASNW12GJ1Z0 DM12RP NSJ AMNW05GSJB0 PM05SP NSJ AMNW07GSJB0 PM07SP NSJ USNW09GJ2F0 PM09SP NSJ USNW12GJ2F0 PM12SP NSJ AMNW15GSJB0 PM15SP NSJ AMNW07GSJA0 PM07EP NSJ USNW09GJ3A0 PM09EP NSJ USNW12GJ3A0 PM12EP NSJ Ø9 52 3 8 Ø6 35 1 4 ASNW18GK1Z0 DM18RP NSK ASNW24GK1Z0 DM24RP NSK USNW18GK2F0 PM18SP NSK USNW24GK2F0 PM...

Page 33: ...22 MULTI SINGLE Indoor unit Wall Mounted Unit 5 Wiring Diagrams Deluxe Model AMNW07GSJL0 DM07RP NSJ ...

Page 34: ...MULTI SINGLE Indoor unit 5 Wiring Diagrams 23 Wall Mounted Unit Models ASNW09GJ1Z0 DM09RP NSJ ASNW12GJ1Z0 DM12RP NSJ ASNW18GK1Z0 DM18RP NSK ASNW24GK1Z0 DM24RP NSK ...

Page 35: ...ULTI SINGLE Indoor unit Wall Mounted Unit Standard plus Models AMNW05GSJB0 PM05SP NSJ AMNW07GSJB0 PM07SP NSJ USNW09GJ2F0 PM09SP NSJ USNW12GJ2F0 PM12SP NSJ AMNW15GSJB0 PM15SP NSJ USNW18GK2F0 PM18SP NSK USNW24GK2F0 PM24SP NSK ...

Page 36: ...MULTI SINGLE Indoor unit 5 Wiring Diagrams 25 Wall Mounted Unit Standard Models AMNW07GSJA0 PM07EP NSJ USNW09GJ3A0 PM09EP NSJ USNW12GJ3A0 PM12EP NSJ USNW18GK3A0 PM18EP NSK AMNW24GSKA0 PM24EP NSK ...

Page 37: ...tical Vane 0ȋ Fan speed Power Air speed 0 3m s Range 11 0m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power Side View Air velocity m s Temperature C Discharge angle 35 28 1 0 2 0 1 5 26 24 22 20 m 2 1 0 2 1 0 10 8 6 4 2 0 10 8 6 4 2 0 0 5 0 3 2 7 m m 2 7 m Air Velocity m s 0 5 1 0 2 0 0 3 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 2 0...

Page 38: ...eed 0 3m s Range 13 2m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 1 5 2 0 1 0 2 1 0 10 8 6 4 2 0 m 0 3 0 5 2 7 m 2 1 0 10 8 6 4 2 0 2 7 m m 26 28 30 32 24 Side View Air velocity m s Temperature C Discharge angle 55 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 3 0 5 1 0 1 0 2 0 0 5 0 5 0 3 0 3 Air Velocity m s Air Velocity m s Top View Discha...

Page 39: ...l Louver Center Fan speed Power Vertical Louver Center Vertical Vane 0ȋ Fan speed Power Air speed 0 3m s Range 11 5m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7m m 0 5 1 0 2 0 1 5 0 3 2 1 0 10 8 6 4 2 0 2 7 m m 26 24 22 28 20 Side View Air velocity m s Temperature C Discharge angle 35 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 2 0 1 0 1 0 0 3 0 3 0 5 0 5 Air V...

Page 40: ...ed 0 3m s Range 13 5m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 Y_ ZW Y Y ZY Side View Air velocity m s Temperature C Discharge angle 55 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 5 0 3 2 0 2 0 1 0 1 0 0 5 0 3 0 5 0 3 Air Velocity m s Air Velocity m s Top View Disch...

Page 41: ...ical Vane 0ȋ Fan speed Power Air speed 0 3m s Range 12 9m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 2 1 0 10 8 6 4 2 0 2 7 m m 26 24 22 28 Side View Air velocity m s Temperature C Discharge angle 25 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 3 0 5 2 0 2 0 1 0 1 0 0 3 0 3 0 5 0 5 0 3 Air Vel...

Page 42: ...ed 0 3m s Range 20 0m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 2 0 1 5 0 3 0 5 1 0 28 30 32 26 Side View Air velocity m s Temperature C Discharge angle 45 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 0 3 0 5 1 0 2 0 2 0 1 0 1 0 0 5 0 3 0 5 0 3 Air Velocity m s Air Velocity m s Top View Disc...

Page 43: ...rtical Vane 0ȋ Fan speed Power Air speed 0 3m s Range 15 0m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 26 24 22 28 Side View Air velocity m s Temperature C Discharge angle 25 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 3 0 5 2 0 2 0 1 0 1 0 0 5 0 5 0 3 0 3 Air Veloc...

Page 44: ...eed 0 3m s Range 20 0m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 2 0 0 3 0 5 1 0 1 5 ZW ZY Y_ Y Side View Air velocity m s Temperature C Discharge angle 45 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 0 3 0 5 1 0 2 0 2 0 1 0 1 0 0 5 0 5 0 3 0 3 Air Velocity m s Air Velocity m s Top View Discha...

Page 45: ... construction acoustic absorption coefficient of particular room in which the equipment in installed Model 50Hz 220 240V Sound pressure Levels dB A H M L AMNW07GSJL0 DM07RP NSJ 35 31 26 ASNW09GJ1Z0 DM09RP NSJ 36 32 27 ASNW12GJ1Z0 DM12RP NSJ 38 34 29 ASNW18GK1Z0 DM18RP NSK 44 38 34 ASNW24GK1Z0 DM24RP NSK 47 41 36 Model 50Hz 220 240V Sound pressure Levels dB A H M L AMNW05GSJB0 PM05SP NSJ 34 31 27 A...

Page 46: ...requency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low High Midd...

Page 47: ...NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure L...

Page 48: ... of particular room in which the equipment in installed Reference acoustic intensity 0dB 10E 6μW m2 Model Sound power Levels dB A H AMNW07GSJL0 DM07RP NSJ 56 ASNW09GJ1Z0 DM09RP NSJ 56 ASNW12GJ1Z0 DM12RP NSJ 56 ASNW18GK1Z0 DM18RP NSK 60 ASNW24GK1Z0 DM24RP NSK 64 Model Sound power Levels dB A H AMNW05GSJB0 PM05SP NSJ 57 AMNW07GSJB0 PM07SP NSJ 57 USNW09GJ2F0 PM09SP NSJ 57 USNW12GJ2F0 PM12SP NSJ 57 AM...

Page 49: ...er Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low High Middle Ǹ Low 10 ...

Page 50: ...R 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 1...

Page 51: ...should be solid enough to protect it from the vibration The place where the unit is not affected by an electrical noise The place where noise prevention is taken into consideration The place where the maintenance space for product is sufficient There should not be any heat source or steam near the unit Please read the instruction sheets completely before installing the product When the power cord ...

Page 52: ...must be done safely According to product type model line up sales region etc applicability of each chassis could be different According to product type model line up sales region etc applicability of each chassis could be different The lower left and the right side piping of Installation Plate According to product type model line up sales region etc applicability of each chassis could be different...

Page 53: ... ྙ ྚ 2 Remove the chassis cover from the unit 3 Pull back the tubing holder 4 Remove pipe port cover and positioning the tubing SV chassis 1 Open the panel of the indoor unit 2 Remove the chassis cover from the unit by loosing 5 screws 3 Pull back the tubing holder 4 Remove pipe port cover and position the piping SV chassis The feature can be changed according to type of model According to product...

Page 54: ...ng housing section Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause overflow from the drain pan through the inside of the unit CAUTION If the drain hose is routed inside the room insulate the hose with an insulation material so that dripping from sweating condensation will not damage furniture or floors The feature can be changed accordin...

Page 55: ...eat the indoor unit on the installation plate 1 Hook the indoor unit onto the upper portion of the installation plate engage the three hooks at the top of the indoor unit with the upper edge of the installation plate Ensure that the hooks areproperly seated on the installation plate by moving it left and right 2 Unlock the tubing holder from the chassis and mount between the chassis and installati...

Page 56: ...left and right 3 Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 4 Finish the assembly by screwing the unit to the installation plate by using two pieces of type C screws And assemble a chassis cover SJ SK chassis Recovery the chassis cover in Original place SV chassis The feature can be changed according to typ...

Page 57: ...le of shutting down the power supply to the entire system must be installed CAUTION After the confirmation of the above conditions prepare the wiring as follows 1 Drill the piping hole with a ø 70mm hole core drill Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side 1 The drain hose should point downward for easy drain flow 2 Do not make drain ...

Page 58: ... communication transmission cable put the 0 75mm2 cable or thinner cable on the clamp and tighten it with a plastic clamp to the other boss of the control panel In case that communication transmission cable is not needed to connect fix the other side of the clamp with a screw strongly WARNING Make sure that the screws of the terminal are fixed tightly The screw which fasten the wiring in the casin...

Page 59: ...ts or dead spots behind doors and in corners Hot or cold air from ducts Radiant heat from sun or appliances Concealed pipes and chimneys Uncontrolled areas such as an outside wall behind the remote controller This remote controller is equipped with a seven segment LED display For proper display of the remote controller LED s the remote controller should be installed properly The standard height is...

Page 60: ...Wall Mounted Unit 2 MULTI SINGLE Indoor unit 1 List of Functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring diagrams 6 Air flow and temperature distribution 7 Sound levels 8 Installation ...

Page 61: ...eration artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O 7hr Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Humidity Control X Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP O Note 1 O Applied X Not applied Accessory model name Installed at...

Page 62: ...RYCB300 O PDRYCB500 Dry Contact For Modbus X Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 X Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m X 2 Remo Control Wire PZCW...

Page 63: ... operation artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O 7hr Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Humidity Control X Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP O Note 1 O Applied X Not applied Accessory model name Installed...

Page 64: ...RYCB300 O PDRYCB500 Dry Contact For Modbus X Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 X Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m X 2 Remo Control Wire PZCW...

Page 65: ...peration artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O 7hr Timer on off O Timer weekly X Two thermistor control X Auto Elevation Grille X Special Functions Wi Fi X Humidity Control X Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP X Note 1 O Applied X Not applied Accessory model name Installed a...

Page 66: ...RYCB300 X PDRYCB500 Dry Contact For Modbus X Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 X Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m X 2 Remo Control Wire PZCW...

Page 67: ...29 Sound Power Level Max dB A 56 56 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm 21 5 16 0 21 5 16 0 Safety Devices Fuse Fuse Thermal Preotector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may b...

Page 68: ...2 7 1 2 Drain O D I D mm 21 5 16 0 Safety Devices Fuse Thermal Preotector for Fan Motor Connections Method Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should b...

Page 69: ...33 27 40 35 27 Sound Power Level Max dB A 57 57 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm 21 5 16 0 21 5 16 0 Safety Devices Fuse Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some specifica...

Page 70: ... 7 1 2 Drain O D I D mm 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be ...

Page 71: ...33 27 40 35 27 Sound Power Level Max dB A 57 57 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm 21 5 16 0 21 5 16 0 Safety Devices Fuse Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 4C x 1 0 18 Note 1 Due to our policy of innovation some specifica...

Page 72: ...12 7 1 2 Drain O D I D mm 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Power and Communication Cable included Earth No x mm2 AWG 4C x 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should b...

Page 73: ...14 MULTI SINGLE Indoor unit Wall Mounted Unit 2 3 Dimensions Deluxe SJ Chassis S3NW09JL1ZA DC09RQ NSJ S3NM12JL1ZA DC12RQ NSJ ...

Page 74: ...3 Dimensions 15 MULTI SINGLE Indoor unit Wall Mounted Unit 2 Standard Plus Standard SJ Chassis S3NM09JA2FA PC09SQ NSJ S3NM12JA2FA PC12SQ NSJ S3NM09JA3BA SC09EQ NSJ S3NM12JA3BA SC12EQ NSJ ...

Page 75: ...MULTI SINGLE Indoor unit 3 Dimensions 16 Wall Mounted Unit 2 Deluxe Standard Plus Standard SK Chassis S3NM18KL1ZA DC18RQ NSK S3NM18KL2FA PC18SQ NSK S3NM18KL3BA SC18EQ NSK ...

Page 76: ... for evaporator middle temperature CN TH3 Th4 Thermistor for evaporator outlet temperature CN TH2 Model Gas Liquid S3NM09JL1ZA DC09RQ NSJ S3NM12JL1ZA DC12RQ NSJ S3NM09JA2FA PC09SQ NSJ S3NM12JA2FA PC12SQ NSJ S3NM09JA3BA SC09EQ NSJ S3NM12JA3BA SC12EQ NSJ Ø9 52 3 8 Ø6 35 1 4 S3NM18KL1ZA DC18RQ NSK S3NM18KL2FA PC18SQ NSK S3NM18KL3BA SC18EQ NSK Ø12 7 1 2 Heat exchanger Gas pipe connection port flare co...

Page 77: ...18 MULTI SINGLE Indoor unit Wall Mounted Unit 2 5 Wiring Diagrams Deluxe Models S3NM09JL1ZA DC09RQ NSJ S3NM12JL1ZA DC12RQ NSJ S3NM18KL1ZA DC18RQ NSK P No 5401448325 Rev ...

Page 78: ...ring Diagrams 19 MULTI SINGLE Indoor unit Wall Mounted Unit 2 Standard plus Models S3NM09JA2FA PC09SQ NSJ S3NM12JA2FA PC12SQ NSJ S3NM18KL2FA PC18SQ NSK P No 5401363101 Rev OPTION Field Wiring Factory Wiring ...

Page 79: ...MULTI SINGLE Indoor unit 5 Wiring Diagrams 20 Wall Mounted Unit 2 Standard Models S3NM09JA3BA SC09EQ NSJ S3NM12JA3BA SC12EQ NSJ S3NM18KL3BA SC18EQ NSK P No 5401291937 Rev ...

Page 80: ... 0ȋ Fan speed Power Air speed 0 3m s Range 11 0m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power Side View Air velocity m s Temperature C Discharge angle 35 28 1 0 2 0 1 5 26 24 22 20 m 2 1 0 2 1 0 10 8 6 4 2 0 10 8 6 4 2 0 0 5 0 3 2 7 m m 2 7 m Air Velocity m s 0 5 1 0 2 0 0 3 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 Air Velocity m s 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 2 0 1 0 1 0 0...

Page 81: ...peed 0 3m s Range 13 2m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 1 5 2 0 1 0 2 1 0 10 8 6 4 2 0 m 0 3 0 5 2 7 m 2 1 0 10 8 6 4 2 0 2 7 m m 26 28 30 32 24 Side View Air velocity m s Temperature C Discharge angle 55 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 3 0 5 1 0 1 0 2 0 0 5 0 5 0 3 0 3 Air Velocity m s Air Velocity m s Top View Disch...

Page 82: ...er Center Vertical Vane 0ȋ Fan speed Power Air speed 0 3m s Range 11 5m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7m m 0 5 1 0 2 0 1 5 0 3 2 1 0 10 8 6 4 2 0 2 7 m m 26 24 22 28 20 Side View Air velocity m s Temperature C Discharge angle 35 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 2 0 1 0 1 0 0 3 0 3 0 5 0 5 Air Velocity m s Air Velocity m s Top View Dischar...

Page 83: ...eed 0 3m s Range 13 5m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 Y_ ZW Y Y ZY Side View Air velocity m s Temperature C Discharge angle 55 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 5 0 3 2 0 2 0 1 0 1 0 0 5 0 3 0 5 0 3 Air Velocity m s Air Velocity m s Top View Disc...

Page 84: ...tical Vane 0ȋ Fan speed Power Air speed 0 3m s Range 12 9m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 2 1 0 10 8 6 4 2 0 2 7 m m 26 24 22 28 Side View Air velocity m s Temperature C Discharge angle 25 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 3 0 5 2 0 2 0 1 0 1 0 0 3 0 3 0 5 0 5 0 3 Air Ve...

Page 85: ...eed 0 3m s Range 20 0m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 2 0 1 5 0 3 0 5 1 0 28 30 32 26 Side View Air velocity m s Temperature C Discharge angle 45 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 0 3 0 5 1 0 2 0 2 0 1 0 1 0 0 5 0 3 0 5 0 3 Air Velocity m s Air Velocity m s Top View Dis...

Page 86: ... air guide Room target temperature setting etc 6 Sound level will vary depending on a range of factors such as the construction acoustic absorption coefficient of particular room in which the equipment in installed Model Deluxe 50Hz 220 240V Sound pressure Levels dB A H M L S3NM09JL1ZA DC09RQ NSJ 36 32 27 S3NM12JL1ZA DC12RQ NSJ 38 34 29 S3NM18KL1ZA DC18RQ NSK 44 38 35 Model Standard plus 50Hz 220 ...

Page 87: ...C 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 6...

Page 88: ...y depending on a range of factors such as the construction acoustic absorption coefficient of particular room in which the equipment in installed Reference acoustic intensity 0dB 10E 6μW m2 Model Deluxe Sound power Levels dB A H S3NM09JL1ZA DC09RQ NSJ 56 S3NM12JL1ZA DC12RQ NSJ 56 S3NM18KL1ZA DC18RQ NSK 60 Model Standard plus Sound power Levels dB A H S3NM09JA2FA PC09SQ NSJ 57 S3NM12JA2FA PC12SQ NS...

Page 89: ... NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 2...

Page 90: ... should be solid enough to protect it from the vibration The place where the unit is not affected by an electrical noise The place where noise prevention is taken into consideration The place where the maintenance space for product is sufficient There should not be any heat source or steam near the unit Please read the instruction sheets completely before installing the product When the power cord...

Page 91: ... must be done safely According to product type model line up sales region etc applicability of each chassis could be different According to product type model line up sales region etc applicability of each chassis could be different The lower left and the right side piping of Installation Plate According to product type model line up sales region etc applicability of each chassis could be differen...

Page 92: ...r ྙ ྚ 2 Remove the chassis cover from the unit 3 Pull back the tubing holder 4 Remove pipe port cover and positioning the tubing SV chassis 1 Open the panel of the indoor unit 2 Remove the chassis cover from the unit by loosing 5 screws 3 Pull back the tubing holder 4 Remove pipe port cover and position the piping SV chassis The feature can be changed according to type of model According to produc...

Page 93: ...ing housing section Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause overflow from the drain pan through the inside of the unit CAUTION If the drain hose is routed inside the room insulate the hose with an insulation material so that dripping from sweating condensation will not damage furniture or floors The feature can be changed accordi...

Page 94: ...Seat the indoor unit on the installation plate 1 Hook the indoor unit onto the upper portion of the installation plate engage the three hooks at the top of the indoor unit with the upper edge of the installation plate Ensure that the hooks areproperly seated on the installation plate by moving it left and right 2 Unlock the tubing holder from the chassis and mount between the chassis and installat...

Page 95: ... left and right 3 Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 4 Finish the assembly by screwing the unit to the installation plate by using two pieces of type C screws And assemble a chassis cover SJ SK chassis Recovery the chassis cover in Original place SV chassis The feature can be changed according to ty...

Page 96: ...ble of shutting down the power supply to the entire system must be installed CAUTION After the confirmation of the above conditions prepare the wiring as follows 1 Drill the piping hole with a ø 70mm hole core drill Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side 1 The drain hose should point downward for easy drain flow 2 Do not make drain...

Page 97: ...f communication transmission cable put the 0 75mm2 cable or thinner cable on the clamp and tighten it with a plastic clamp to the other boss of the control panel In case that communication transmission cable is not needed to connect fix the other side of the clamp with a screw strongly WARNING Make sure that the screws of the terminal are fixed tightly The screw which fasten the wiring in the casi...

Page 98: ...fts or dead spots behind doors and in corners Hot or cold air from ducts Radiant heat from sun or appliances Concealed pipes and chimneys Uncontrolled areas such as an outside wall behind the remote controller This remote controller is equipped with a seven segment LED display For proper display of the remote controller LED s the remote controller should be installed properly The standard height i...

Page 99: ...ART COOL Mirror MULTI SINGLE Indoor unit 1 List of Functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring diagrams 6 Air flow and temperature distribution 7 Sound levels 8 Installation ...

Page 100: ...leaning O Auto operation artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O 7hr Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Humidity Control X Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP O Note 1 O Applied X Not applied Accessory model ...

Page 101: ...tact For Setback O PDRYCB300 O PDRYCB500 Dry Contact For Modbus X Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 X Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m X 2 R...

Page 102: ...x dB A 57 57 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 9 52 3 8 Ø 9 52 3 8 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No mm AWG 4C 1 0 18 4C 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2...

Page 103: ... 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Power and Communication Cable included Earth No mm AWG 4C 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be considered for electrical wo...

Page 104: ...d Power Level Max dB A 59 65 Piping Connections Liquid mm inch Ø 6 35 1 4 Ø 6 35 1 4 Gas mm inch Ø 12 7 1 2 Ø 12 7 1 2 Drain O D I D mm Ø 21 5 16 0 Ø 21 5 16 0 Safety Devices Fuse Thermal Protector for Fan Motor Connections Method Flared Flared Power and Communication Cable included Earth No mm AWG 4C 1 0 18 4C 1 0 18 Note 1 Due to our policy of innovation some specifications may be changed withou...

Page 105: ...7 MULTI SINGLE Indoor unit ART COOL Mirror 3 Dimensions ARTCOOL Mirror SJ Chassis AMNW07GSJR0 AM07BP NSJ USNW09GJRZ0 AM09BP NSJ USNW12GJRZ0 AM12BP NSJ ...

Page 106: ...MULTI SINGLE Indoor unit 3 Dimensions 8 ART COOL Mirror ARTCOOL Mirror SK Chassis USNW18GKRZ0 AM18BP NSK AMNW24GSKR0 AM24BP NSK ...

Page 107: ...h2 Thermistor for evaporator inlet temperature Th3 Thermistor for evaporator middle temperature CN TH3 Th4 Thermistor for evaporator outlet temperature CN TH2 Model Gas Liquid AMNW07GSJR0 AM07BP NSJ USNW09GJRZ0 AM09BP NSJ USNW12GJRZ0 AM12BP NSJ Ø9 52 3 8 Ø6 35 1 4 USNW18GKRZ0 AM18BP NSK AMNW24GSKR0 AM24BP NSK Ø12 7 1 2 Heat exchanger Gas pipe connection port flare connection Liquid pipe connection...

Page 108: ...10 MULTI SINGLE Indoor unit ART COOL Mirror 5 Wiring Diagrams Models AMNW07GSJR0 AM07BP NSJ AMNW24GSKR0 AM24BP NSK Models USNW09GJRZ0 AM09BP NSJ USNW12GJRZ0 AM12BP NSJ USNW18GKRZ0 AM18BP NSK ...

Page 109: ...tical Vane 0ȋ Fan speed Power Air speed 0 3m s Range 11 5m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7m m 0 5 1 0 2 0 1 5 0 3 2 1 0 10 8 6 4 2 0 2 7 m m 26 24 22 28 20 Side View Air velocity m s Temperature C Discharge angle 35 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 2 0 1 0 1 0 0 3 0 3 0 5 0 5 Air Velocity m s Air Velocity m s Top View Discharge angle 35 1...

Page 110: ...d 0 3m s Range 13 5m Vertical Louver Left Right Vertical Vane 55ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 Y_ ZW Y Y ZY Side View Air velocity m s Temperature C Discharge angle 55 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 5 0 3 2 0 2 0 1 0 1 0 0 5 0 3 0 5 0 3 Air Velocity m s Air Velocity m s Top View Discha...

Page 111: ...ower Air speed 0 3m s Range 12 9m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 2 1 0 10 8 6 4 2 0 2 7 m m 26 24 22 28 Side View Air velocity m s Temperature C Discharge angle 25 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 3 0 5 2 0 2 0 1 0 1 0 0 3 0 3 0 5 0 5 0 3 Air Velocity m s Air Velocity m...

Page 112: ...d 0 3m s Range 20 0m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 2 0 1 5 0 3 0 5 1 0 28 30 32 26 Side View Air velocity m s Temperature C Discharge angle 45 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 0 3 0 5 1 0 2 0 2 0 1 0 1 0 0 5 0 3 0 5 0 3 Air Velocity m s Air Velocity m s Top View Disch...

Page 113: ... Power Air speed 0 3m s Range 15 0m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 1 0 2 0 1 5 0 3 0 5 26 24 22 28 Side View Air velocity m s Temperature C Discharge angle 25 m 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 1 0 2 0 0 3 0 5 2 0 2 0 1 0 1 0 0 5 0 5 0 3 0 3 Air Velocity m s Air Velocity m s...

Page 114: ...ed 0 3m s Range 20 0m Vertical Louver Left Right Vertical Vane 50ȋ Fan speed Power 2 1 0 10 8 6 4 2 0 2 7 m m 2 1 0 10 8 6 4 2 0 2 7 m m 2 0 0 3 0 5 1 0 1 5 ZW ZY Y_ Y Side View Air velocity m s Temperature C Discharge angle 45 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 10 8 6 4 2 0 m 5 5 4 4 3 3 2 2 1 1 0 2 0 0 3 0 5 1 0 2 0 2 0 1 0 1 0 0 5 0 5 0 3 0 3 Air Velocity m s Air Velocity m s Top View Dischar...

Page 115: ...NW09GJRZ0 AM09BP NSJ 36 33 27 USNW12GJRZ0 AM12BP NSJ 40 35 27 USNW18GKRZ0 AM18BP NSK 44 38 35 AMNW24GSKR0 AM24BP NSK 46 41 36 AMNW07GSJR0 AM07BP NSJ USNW09GJRZ0 AM09BP NSJ USNW12GJRZ0 AM12BP NSJ 0 8m 1m Microphone 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55...

Page 116: ...evel dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle...

Page 117: ...Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low High Middle Ǹ Low 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 High Middle Ǹ Low High Middle Ǹ Low 10 20 ...

Page 118: ...hould be solid enough to protect it from the vibration The place where the unit is not affected by an electrical noise The place where noise prevention is taken into consideration The place where the maintenance space for product is sufficient There should not be any heat source or steam near the unit Please read the instruction sheets completely before installing the product When the power cord i...

Page 119: ...done safely According to product type model line up sales region etc applicability of each chassis could be different According to product type model line up sales region etc applicability of each chassis could be different The lower left and the right side piping of Installation Plate According to product type model line up sales region etc applicability of each chassis could be different SJ Chas...

Page 120: ...ྙ ྚ 2 Remove the chassis cover from the unit 3 Pull back the tubing holder 4 Remove pipe port cover and positioning the tubing SV chassis 1 Open the panel of the indoor unit 2 Remove the chassis cover from the unit by loosing 5 screws 3 Pull back the tubing holder 4 Remove pipe port cover and position the piping SV chassis The feature can be changed according to type of model According to product ...

Page 121: ...g housing section Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause overflow from the drain pan through the inside of the unit CAUTION If the drain hose is routed inside the room insulate the hose with an insulation material so that dripping from sweating condensation will not damage furniture or floors The feature can be changed according...

Page 122: ...at the indoor unit on the installation plate 1 Hook the indoor unit onto the upper portion of the installation plate engage the three hooks at the top of the indoor unit with the upper edge of the installation plate Ensure that the hooks areproperly seated on the installation plate by moving it left and right 2 Unlock the tubing holder from the chassis and mount between the chassis and installatio...

Page 123: ...eft and right 3 Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound 4 Finish the assembly by screwing the unit to the installation plate by using two pieces of type C screws And assemble a chassis cover SJ SK chassis Recovery the chassis cover in Original place SV chassis The feature can be changed according to type...

Page 124: ...e of shutting down the power supply to the entire system must be installed CAUTION After the confirmation of the above conditions prepare the wiring as follows 1 Drill the piping hole with a ø 70mm hole core drill Drill the piping hole at either the right or the left with the holes slightly slanted to the outdoor side 1 The drain hose should point downward for easy drain flow 2 Do not make drain p...

Page 125: ...communication transmission cable put the 0 75mm2 cable or thinner cable on the clamp and tighten it with a plastic clamp to the other boss of the control panel In case that communication transmission cable is not needed to connect fix the other side of the clamp with a screw strongly WARNING Make sure that the screws of the terminal are fixed tightly The screw which fasten the wiring in the casing...

Page 126: ...s or dead spots behind doors and in corners Hot or cold air from ducts Radiant heat from sun or appliances Concealed pipes and chimneys Uncontrolled areas such as an outside wall behind the remote controller This remote controller is equipped with a seven segment LED display For proper display of the remote controller LED s the remote controller should be installed properly The standard height is ...

Page 127: ...ng Mounted cassette 4 way MULTI SINGLE Indoor unit 1 List of Functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring diagrams 6 Air flow and temperature distribution 7 Sound levels 8 Installation ...

Page 128: ...o operation artificial intelligence O O Multi Only Auto Restart O O Child lock O O Forced operation O O Group control O O Sleep mode O O Timer on off O O Timer weekly O O Two thermistor control O O Auto Elevation Grille X X Special Functions Wi Fi X O Accessory Humidity Control X X Human Detecting Control X X Comes with product Wireless Remote Controller X X Wired Remote Controller O O Network Sol...

Page 129: ...MA0 X Category Product Remark ZTNW09GRLA0 CT09R NR0 ZTNW12GRLA0 CT12R NR0 Wireless Remote Controller PQWRHQ0FDB Heat Pump O Wired Remote Controller Simple PQRCVCL0Q W Simple O PQRCHCA0Q W for Hotel O Standard PREMTB001 Standard White O PREMTBB01 Standard Black O PREMTB100 New Standard White O Premium PREMTA000 A B Premium O Dry contact Simple Contact PDRYCB000 Simple Dry Contact O Communication ty...

Page 130: ...lti Only O Multi Only Auto Restart O O Child lock O O Forced operation O O Group control O O Sleep mode O O Timer on off O O Timer weekly O O Two thermistor control O O Auto Elevation Grille X PTEGM0 Special Functions Wi Fi O Accessory O Accessory Humidity Control X O Single Only Human Detecting Control X O Accessory Comes with product Wireless Remote Controller X X Wired Remote Controller O O Net...

Page 131: ...MA0 X Category Product Remark ZTNW24GPLA0 CT24R NP0 Wireless Remote Controller PQWRHQ0FDB Heat Pump O Wired Remote Controller Simple PQRCVCL0Q W Simple O PQRCHCA0Q W for Hotel O Standard PREMTB001 Standard White O PREMTBB01 Standard Black O PREMTB100 New Standard White O Premium PREMTA000 A B Premium O Dry contact Simple Contact PDRYCB000 Simple Dry Contact O Communication type PDRYCB400 2 Points ...

Page 132: ...al intelligence X Auto Restart O Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille PTEGM0 Special Functions Wi Fi O Accessory Humidity Control O Human Detecting Control O Accessory Comes with product Wireless Remote Controller X Wired Remote Controller O Network Solution LGAP O Note 1 O Applied X Not applied Ac...

Page 133: ...YCB300 O PDRYCB500 Dry Contact For Modbus O Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 O Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m O 2 Remo Control Wire PZCWR...

Page 134: ...er and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Decoration Panel Model Name PT QCHW0 PT QCHW0 Color Morning Fog Morning Fog Dimensions W x H x D mm 620 34 620 620 34 620 Net Weight kg 3 0 3 0 Shipping Weight kg 4 1 4 1 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and na...

Page 135: ...2 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Decoration Panel Model Name PT QCHW0 PT QCHW0 Color Morning Fog Morning Fog Dimensions W x H x D mm 620 34 620 620 34 620 Net Weight kg 3 0 3 0 Shipping Weight kg 4 1 4 1 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local a...

Page 136: ...able included Earth No x mm 4C x 0 75 4C x 0 75 Decoration Panel Model Name PT QCHW0 PT MCHW0 Color Morning Fog Morning Fog Dimensions W x H x D mm 620 34 620 950 35 950 Net Weight kg 3 0 6 3 Shipping Weight kg 4 1 8 3 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electr...

Page 137: ...62 64 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Decoration Panel Model Name PT MCHW0 PT MCHW0 Color Morning Fog Morning Fog Dimensions W x H x D mm 950 35 950 950 35 950 Net Weight kg 6 3 6 3 Shipping Weight kg 8 3 8 3 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable loc...

Page 138: ... 64 66 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Decoration Panel Model Name PT MCHW0 PT MCHW0 Color Morning Fog Morning Fog Dimensions W x H x D mm 950 35 950 950 35 950 Net Weight kg 6 3 6 3 Shipping Weight kg 8 3 8 3 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable lo...

Page 139: ...13 MULTI SINGLE Indoor unit Ceiling Mounted cassette 4 way 3 Dimensions ZMNW05GTRA0 MT06R NR0 ZMNW07GTRA0 MT08R NR0 ZTNW09GRLA0 CT09R NR0 ZTNW12GRLA0 CT12R NR0 ...

Page 140: ...MULTI SINGLE Indoor unit 3 Dimensions 14 Ceiling Mounted cassette 4 way ZTNW18GQLA0 CT18R NQ0 ...

Page 141: ...3 Dimensions 15 MULTI SINGLE Indoor unit Ceiling Mounted cassette 4 way ZTNW24GPLA0 CT24R NP0 ...

Page 142: ...MULTI SINGLE Indoor unit 3 Dimensions 16 Ceiling Mounted cassette 4 way ZTNW36GMLA0 UT36R NM0 ZTNW42GMLA0 UT42R NM0 ZTNW48GMLA0 UT48R NM0 ZTNW60GMLA0 UT60R NM0 Chassis code TM ...

Page 143: ...tlet temperature CN_PIPE OUT Humid Sensor CN_HUMID Model Gas Liquid ZMNW05GTRA0 MT06R NR0 ZMNW07GTRA0 MT08R NR0 ZTNW09GRLA0 CT09R NR0 ZTNW12GRLA0 CT12R NR0 Ø9 52 Ø6 35 ZTNW18GQLA0 CT18R NQ0 Ø12 7 ZTNW24GPLA0 CT24R NP0 Ø15 88 Ø 12 7 Ø9 52 Ø 6 35 ZTNW36GMLA0 UT36R NM0 ZTNW42GMLA0 UT42R NM0 ZTNW48GMLA0 UT48R NM0 ZTNW60GMLA0 UT60R NM0 Ø15 88 Ø9 52 Heat exchanger Gas pipe connection port flare connecti...

Page 144: ...18 MULTI SINGLE Indoor unit Ceiling Mounted cassette 4 way 5 Wiring Diagrams Models ZMNW05GTRA0 MT06R NR0 ZMNW07GTRA0 MT08R NR0 Model ZTNW09GRLA0 CT09R NR0 ZTNW12GRLA0 CT12R NR0 ZTNW18GQLA0 CT18R NQ0 ...

Page 145: ...5 Wiring Diagrams 19 MULTI SINGLE Indoor unit Unit mm Ceiling Mounted cassette 4 way Model ZTNW24GPLA0 CT24R NP0 ZTNW36GMLA0 UT36R NM0 ZTNW42GMLA0 UT42R NM0 ZTNW48GMLA0 UT48R NM0 ZTNW60GMLA0 UT60R NM0 ...

Page 146: ...6 34 ZTNW36GMLA0 UT36R NM0 46 43 40 ZTNW42GMLA0 UT42R NM0 47 44 41 ZTNW48GMLA0 UT48R NM0 47 44 41 ZTNW60GMLA0 UT60R NM0 47 44 41 ZMNW05GTRA0 MT06R NR0 ZMNW07GTRA0 MT08R NR0 ZTNW09GRLA0 CT09R NR0 ZTNW12GRLA0 CT12R NR0 ZTNW18GQLA0 CT18R NQ0 1 5m Ceiling Measuring place Anechoic chamber Octave Band Sound Pressure Level dB re 20Pa Octave Band Center Frequency Hz 10 20 30 40 50 60 70 80 63 125 250 500 ...

Page 147: ... NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Low 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 400...

Page 148: ...UT42R NM0 64 ZTNW48GMLA0 UT48R NM0 64 ZTNW60GMLA0 UT60R NM0 66 ZMNW05GTRA0 MT06R NR0 ZMNW07GTRA0 MT08R NR0 ZTNW09GRLA0 CT09R NR0 ZTNW12GRLA0 CT12R NR0 ZTNW18GQLA0 CT18R NQ0 PWL 0dB 10E 6μPa Octave Band Center Frequency Hz 63 125 250 500 1000 2000 4000 8000 20 30 40 50 60 70 80 90 100 NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 80 NR 85 NR 90 PWL 0dB 10E 6μPa Octave Band Center F...

Page 149: ...NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 Cooling 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 Cooling 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW ...

Page 150: ...Heating Discharge angle 50 Air velocity m s 2 7m 2m 1m 0m 2 5m 1 5m 0m 1 5m 2 5m 0 5 0 5 0 5 1 0 5 0 5 0 5 1 Temperature C 2 7m 2m 1m 0m 2 5m 1 5m 0m 1 5m 2 5m 34 26 22 24 22 34 26 22 24 22 2 7m 2m 1m 0m 2m 1m 0m 1m 2m 2 5m 2 5m Discharge angle 40 Air velocity m s Temperature C Cooling 2 7m 2m 1m 0m 2m 1m 0m 1m 2m 2 5m 2 5m 0 5 1 0 1 0 0 5 0 25 0 25 0 25 0 5 0 25 18 18 19 19 20 20 2 7m 2m 1m 0m 2m...

Page 151: ...Discharge angle 50 Air velocity m s Temperature C Heating 0 25 0 25 0 5 0 5 1 0 1 0 2 7m 2m 1m 0m 2m 1m 0m 1m 2m 2 5m 2 5m 22 24 26 26 30 32 34 34 36 36 38 38 2 7m 2m 1m 0m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 2 7m 2m 1m 0m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m Discharge angle 40 Air velocity m s Temperature C Cooling 0 25 0 25 0 5 0 5 1 0 1 5 1 0 1 5 23 23 22 22 21 21 20 20 Discharge angle 50 Air velocity...

Page 152: ... 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 2 7m 2m 1m 0m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 0 25 0 25 0 5 1 0 1 5 1 5 1 0 0 5 32 32 33 33 34 34 27 28 29 30 28 29 30 Discharge angle 40 Air velocity m s Temperature C Cooling 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 0 5 0 5 0 25 0 25 1 0 1 0 1 5 1 5 2 0 2 5 2 5 3 0 3 0 2 0 22 22 21 21 20 20 Discharge an...

Page 153: ...m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 0 25 0 25 0 5 0 5 1 0 1 0 1 5 1 5 2 0 2 0 2 5 2 5 31 31 30 30 33 33 34 34 35 35 32 32 29 29 Discharge angle 40 Air velocity m s Temperature C Cooling 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 0 5 1 0 1 0 1 5 1 5 2 0 2 0 2 5 2 5 3 0 3 0 0 5 0 25 0 25 23 23 2...

Page 154: ...0m 1m 2m 3m 4m 5m 5m 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 0 5 0 5 1 0 1 0 1 5 1 5 2 0 2 0 2 5 3 0 3 0 3 5 3 5 2 5 1 0 0 25 0 25 22 22 21 21 20 20 19 19 18 18 Discharge angle 50 Air velocity m s Temperature C Heating 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 3 2m 2m 1m 0m 3m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m 5m 0 25 0 25 0 5 1 0 5 1 0 1 5 1 2 0 2 0 2 5 2 5 3 0 3 0 0 5 31 31 32 33 3...

Page 155: ...tion hole of the ceiling should be larger than the indoor unit The selection of the servicing inspection hole should be approved by the customer There should not be any heat source or steam near the unit Avoid the following installation location 1 Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated These may cause heat exchange efficiency reduction ...

Page 156: ...ew protective kit should be equipped or use additional insulation to the indoor unit body Dew Protective kit is sold separately Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least TQ TR Chassis According to product type model line up sales region etc applicability of each chassis could be different Use the ventilation fan for smoke collecting hood with su...

Page 157: ...the down floor directions 4 The gate or exit of the building is protected by dual door system to minimize inflow of outdoor air TP Chassis According to product type model line up sales region etc applicability of each chassis could be different TM TN Chassis According to product type model line up sales region etc applicability of each chassis could be different Ceiling Ceiling Board Ceiling Board...

Page 158: ...ermeasure method Indoor unit Insulate the unit body with some insulation like glass wool at least 10 mm in thickness Refrigerant piping Increase the piping insulation thickness with thickness above 20 mm Others Inside the ceiling near th air tight seal places To escape of the humidity inside false ceiling In case of places having the temperature and humidity of the surrounding water sources sea ri...

Page 159: ...position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose 4 Drill the hole for anchor bolt on the wall or ceiling Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling Mount the suspension bolts to the set anchor firmly Secure the installation plates onto the suspension bolts adjust level roug...

Page 160: ...10 a Set anchor Old building New building b Plate washer c Spring washer d Nut e Suspension bolts Set screw of paper model 4 pieces Paper model for installation Ceiling board 150mm Ceiling board Ceiling Keep the length of the bolt from the bracket to 40mm Open the ceiling board along the outer edge of the paper model Air Conditioner body Keep the length of 15 18mm between the air conditioner botto...

Page 161: ...circuit breaker switch between power source and the unit Confirm the Specification of power source Confirm that electrical capacity is sufficient Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate Confirm that the cable thickness is as specified in the power sources specification Particularly note the relation between cable length ...

Page 162: ...filtration of foreign particle from outside Otherwise a short circuit may occur inside the electric parts box When clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps Also when wiring make sure the cover on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box co...

Page 163: ... 1 1 4 inch Piping material Use the Polyvinyl chloride pipe 25 mm 1 inch pipe fittings The decoration panel has its installation direction Before installing the decoration panel always remove the paper template Good case Bad case Fit the insulator this part and be careful for cool air leakage Decorative panel Air conditioner unit Ceiling board Good example Cool air leakage no good Decorative panel...

Page 164: ... insulation material Use the following procedure to test the drain pump operation 1 Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end 2 Feed water to the flexible drain hose and check the piping for leakage 3 Be sure to check the drain pump for normal operating and noise when electrical wiring is complete 4 When the test is complete connect the f...

Page 165: ...e down from the combination should be as large as possible The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum Face the vent pipe opening facing downward to keep foreign matter from penetrating the system Face piping downward Vent pipe Face the vent pipe opening facing downward to keep foreign matter from penetrating the system ...

Page 166: ...ncealed duct Middle static pressure MULTI SINGLE Indoor unit 1 List of Functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring diagrams 6 External static pressure Air flow 7 Sound levels 8 Installation ...

Page 167: ...geover O Auto cleaning X Auto operation artificial intelligence X Auto Restart O Child lock O Forced operation X Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Accessory Humidity Control X Comes with product Wireless Remote Controller X Wired Remote Controller O Network Solution LGAP O Note 1 O Applied X Not app...

Page 168: ...nected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 O Zone controller ABZCA O Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m O 2 Remo Control Wire PZCWRC2 0 25m O Extension Wire PZCWRC1 10m O Wi Fi Controller PWFMDD200 O Note 1...

Page 169: ...A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 O Zone controller ABZCA O Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m O 2 Remo Control Wire PZCWRC2 0 25m O Extension Wire PZCWRC1 10m O Wi Fi Controller PWFMDD200 O ...

Page 170: ...2 0 25 0 Sound Pressure Level Cooling H M L dB A 34 32 30 35 34 32 Sound Power Level Cooling Max dB A 59 60 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be c...

Page 171: ... 8 Drain Pipe O D I D mm Ø 32 25 Ø 32 25 Sound Pressure Level Cooling H M L dB A 36 34 33 38 36 34 Sound Power Level Cooling Max dB A 60 62 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric cha...

Page 172: ...Drain Pipe O D I D mm Ø 32 25 Ø 32 25 Sound Pressure Level Cooling H M L dB A 40 38 36 42 40 38 Sound Power Level Cooling Max dB A 65 66 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric charac...

Page 173: ...8 MULTI SINGLE Indoor unit Ceiling concealed duct Middle static pressure 3 Dimensions ZBNW18GM1A0 CM18R N10 ZBNW24GM1A0 CM24R N10 Supplied with product ...

Page 174: ...3 Dimensions 9 MULTI SINGLE Indoor unit Ceiling concealed duct Middle static pressure ZBNW36GM2A0 UM36R N20 ZBNW42GM2A0 UM42R N20 ...

Page 175: ...MULTI SINGLE Indoor unit 3 Dimensions 10 Ceiling concealed duct Middle static pressure ZBNW48GM3A0 UM48R N30 ZBNW60GM3A0 UM60R N30 ...

Page 176: ...istor for suction air temperature CN ROOM Thermistor for evaporator inlet temperature CN PIPE IN Thermistor for evaporator outlet temperature CN PIPE OUT Model Gas Liquid ZBNW18GM1A0 CM18R N10 Ø12 7 Ø6 35 ZBNW24GM1A0 CM24R N10 Ø15 88 Ø9 52 Ø12 7 Ø6 35 Sirocco Fan Heat exchanger Gas pipe connection port flare connection Liquid pipe connection port flare connection Cooling Heating M Thermistor for s...

Page 177: ...ure CN ROOM Thermistor for evaporator inlet temperature CN PIPE IN Thermistor for evaporator outlet temperature CN PIPE OUT Model Gas Liquid ZBNW36GM2A0 UM36R N20 ZBNW42GM2A0 UM42R N20 ZBNW48GM3A0 UM48R N30 ZBNW60GM3A0 UM60R N30 Ø15 88 Ø9 52 Sirocco Fan Heat exchanger Gas pipe connection port flare connection Liquid pipe connection port flare connection Cooling Heating M Thermistor for suction air...

Page 178: ...13 MULTI SINGLE Indoor unit Ceiling concealed duct Middle static pressure 5 Wiring Diagrams Model ZBNW18GM1A0 CM18R N10 ZBNW24GM1A0 CM24R N10 ...

Page 179: ...MULTI SINGLE Indoor unit 5 Wiring Diagrams 14 Ceiling concealed duct Middle static pressure Model ZBNW36GM2A0 UM36R N20 ZBNW42GM2A0 UM42R N20 ...

Page 180: ...5 Wiring Diagrams 15 MULTI SINGLE Indoor unit Ceiling concealed duct Middle static pressure Model ZBNW48GM3A0 UM48R N30 ZBNW60GM3A0 UM60R N30 ...

Page 181: ...mode by using button it indicates as the picture below 2 Select ESP fan step by pressing button 01 very low 02 low 03 medium 04 high 05 very high 3 Move to ESP value setting by pressing button It is 000 when delivering from the warehouse 4 Press button to setup ESP value It is possible to setup ESP value from 1 to 255 and 1 is the smallest and 255 is the biggest 5 If pressing button long for 3 sec...

Page 182: ...eously for more than 3 seconds the system will be entered into the installer setting mode After entering into the installer setting mode select the static pressure step setting code value by pressing the button Static pressure step setting code value 32 1 Select the desired setting value with the temperature up s down t button 2 When pressing button currently established static pressure value will...

Page 183: ...118 120 124 124 124 HIGH 32 0 101 105 109 112 115 119 123 126 128 128 128 Model Step CMM Static Pressure mmAq Pa 5 49 6 59 7 69 8 78 9 88 10 98 11 108 12 118 13 127 14 137 15 147 Setting Value 32 01 32 02 32 03 32 04 32 05 32 06 32 07 32 08 32 09 32 10 32 11 ZBNW42GM2A0 UM42R N20 LOW 28 0 100 103 106 110 114 118 121 125 128 133 136 MID 33 0 108 111 114 118 122 125 128 131 134 138 141 HIGH 38 0 117...

Page 184: ...e air flow rate varies 3 Factory Set External Static Pressure each Model If it is zero static pressure please set value below Maximum value Model Factory set E S P mmAq Pa ZBNW18GM1A0 CM18R N10 6 59 ZBNW24GM1A0 CM24R N10 ZBNW36GM2A0 UM36R N20 ZBNW42GM2A0 UM42R N20 ZBNW48GM3A0 UM48R N30 ZBNW60GM3A0 UM60R N30 Model Maximum value ZBNW18GM1A0 CM18R N10 115 ZBNW24GM1A0 CM24R N10 ZBNW36GM2A0 UM36R N20 1...

Page 185: ...17 5 15 0 12 0 95 19 0 16 7 13 7 10 7 100 20 6 18 5 15 5 12 5 105 22 1 20 3 17 3 14 3 11 1 110 23 7 22 1 19 0 16 1 13 1 10 0 115 23 8 20 8 17 9 15 1 12 2 120 22 6 19 7 17 1 14 3 11 3 125 21 5 19 1 16 5 13 6 11 9 130 23 3 21 2 18 7 15 8 14 3 135 23 2 20 8 18 0 16 7 140 23 0 20 3 19 1 145 22 5 21 5 150 23 8 Setting value Static Pressure mmAq Pa 4 39 6 59 8 78 10 98 12 118 14 137 15 147 Air Flow Rate...

Page 186: ...6 26 8 115 36 7 34 8 30 3 24 4 120 39 7 37 9 33 8 28 3 23 5 125 42 6 41 0 37 3 32 2 27 5 130 44 1 40 8 36 1 31 6 26 1 135 44 3 40 0 35 6 30 4 28 0 140 43 9 39 7 34 6 32 4 145 43 7 38 9 36 8 150 43 1 41 2 155 45 6 Setting value Static Pressure mmAq Pa 5 49 6 59 8 78 10 98 12 118 14 137 15 147 Air Flow Rate m min 70 25 1 75 29 5 26 1 80 34 0 30 8 25 9 85 38 4 35 4 30 6 23 2 90 42 9 40 1 35 2 28 1 21...

Page 187: ...he following installation location 1 Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated These may cause heat exchange efficiency reduction or water drops drain pump mal function In these cases take the following actions Make sure that ventilation fan is enough to cover all noxious gases from this place Ensure enough distance from the cooking room t...

Page 188: ...ld separately Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least Inspection Hole Standard Distance between false ceiling actual ceiling Number of in spection hole Remarks More than 100cm 1 Sufficient space in the ceiling for servicing 20cm to 100cm 2 Insufficient space Difficult for servicing Less than 20cm Hole size should be more than the size of IDU M...

Page 189: ...and washer onto the suspension bolts for locking the suspension bolts on the ceiling Mount the suspension bolts to the set anchor firmly Secure the installation plates onto the suspension bolts adjust level roughly using nuts washers and spring washers 5 In case of ducted type unit apply a joint canvas between the unit and duct to absorb unnecessary vibration The following parts are local purchasi...

Page 190: ...ding to product type model line up sales region etc applicability of each chassis could be different Chassis name Dimension mm A B C D E F G H I J M1 933 4 971 6 619 2 700 30 270 15 2 858 201 4 900 M2 1 283 4 1 321 6 619 2 689 6 30 270 15 2 1 208 201 4 1 250 M3 1 283 4 1 321 6 619 2 689 6 30 360 15 2 1 208 291 4 1 250 C E G D F I A J B H Drain hole ...

Page 191: ...stance This air conditioner has been tested according to the KS Conditions and confirmed If it is operated for a long time in high humid atmosphere dew point temperature more than 23 C 73 F water drops are liable to fall In this case add heat insulation material according to the following procedure CAUTION Make sure to insulate any field piping all the way to the piping connection inside the unit ...

Page 192: ...t to exert force on the drain port on the indoor unit The outside diameter of the drain connection on the indoor unit is 32 mm 1 1 4 inch Piping material Use the Polyvinyl chloride pipe 25 mm 1 inch pipe fittings Possible drain head height is upto 700 mm 27 6 19 inch So the drain head should be installed below 700 mm 27 6 19 inch Be sure to install heat insulation on the drain piping Heat insulati...

Page 193: ...in connection on the indoor unit and drain piping fittings should be referenced from Specifications of each models Piping material Use the Polyvinyl chloride pipe Be sure to install heat insulation on the drain piping Heat insulation material Polyethylene foam with thickness more than 8 mm 5 16 inch U trap is not required for low static model in which the external static pressure is below 50 pa 5m...

Page 194: ...ater on the evaporator 3 Check the drainage Ensure that water flows through drain hose of indoor unit without any leakage Use the following procedure to test the drain pump operation 1 Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end 2 Feed water to the flexible drain hose and check the piping for leakage 3 Be sure to check the drain pump for no...

Page 195: ...The pipe down from the combination should be as large as possible The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum Face the vent pipe opening facing downward to keep foreign matter from penetrating the system Face piping downward Vent pipe Face the vent pipe opening facing downward to keep foreign matter from penetrating the system ...

Page 196: ...ce which is wet or moist Water or moist may cause short circuit The following troubles would be caused by voltage drop down Vibration of a magnetic switch damage on the contact point there of fuse breaking disturbance to the normal function of a overload protection device Proper starting power is not given to the compressor 7 5 2 Wiring connection Connect the wires to the terminals on the control ...

Page 197: ...ges Pass wiring through the wiring through holes to prevent damage to them Make sure the remote controller wiring the wiring between the units and other electrical wiring do not pass through the same locations outside of the unit separating them properly otherwise electrical noise external static could cause product malfunction 7 5 4 Wired Remote Controller Installation Since the room temperature ...

Page 198: ...oncealed duct Low static pressure MULTI SINGLE Indoor unit 1 List of Functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring diagrams 6 External static pressure Air flow 7 Sound levels 8 Installation ...

Page 199: ...Auto operation artificial intelligence O Multi only Auto Restart O Child lock O Forced operation X Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Accessory Humidity Control X Comes with product Wireless Remote Controller X Wired Remote Controller O Network Solution LGAP O Note 1 O Applied X Not applied Accessory...

Page 200: ...ected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 O Zone controller ABZCA O Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m O 2 Remo Control Wire PZCWRC2 0 25m O Extension Wire PZCWRC1 10m O Wi Fi Controller PWFMDD200 O Note 1 ...

Page 201: ...ndoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 O Zone controller ABZCA O Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3 0 25m O 2 Remo Control Wire PZCWRC2 0 25m O Extension Wire PZCWRC1 10m O Wi Fi Controller PWFMDD200 O Note 1 O Possible X Imp...

Page 202: ...m Ø 32 0 25 0 Ø 32 0 25 0 Sound Pressure Level Cooling H M L dB A 31 28 27 31 28 27 Sound Power Level Cooling Max dB A 55 55 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics ch...

Page 203: ...5 0 Sound Pressure Level Cooling H M L dB A 36 34 31 39 35 32 Sound Power Level Cooling Max dB A 54 58 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be consid...

Page 204: ...lations or applicable national codes 774 A B C L1 L2 L3 700 733 660 974 900 933 860 1 174 1 100 1 133 1 060 unit mm Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Power supply connection 5 Air discharge 6 Air suction Number Descripition unit mm Unit size 5k 7k 9k 12k 18k 6 35 Unit size 21k 24k 9 52 Unit size 5k 7k 9k 12k 18k 12 7 Unit size 21k 24k 15 88 20 D 5 6 2 1 ...

Page 205: ...n PCB Connector Inlet Air Temperature Thermistor CN ROOM Evaporator In Temperature Thermistor CN PIPE IN Evaporator Out Temperature Thermistor CN PIPE OUT Model Gas mm Liquid mm ZBNW09GL2A0 CL09R N20 Ø9 52 Ø6 35 ZBNW12GL2A0 CL12R N20 Ø9 52 ZBNW18GL2A0 CL18R N20 Ø12 7 Indoor Unit Cooling Heating Evaporator Out Temperature Thermistor Evaporator In Temperature Thermistor M M Sirocco Fan Inlet Air Tem...

Page 206: ... units should be connected Description PCB Connector Inlet Air Temperature Thermistor CN ROOM Evaporator In Temperature Thermistor CN PIPE IN Evaporator Out Temperature Thermistor CN PIPE OUT Model Gas mm Liquid mm ZBNW24GL3A0 CL24R N30 Ø15 88 Ø9 52 Ø 12 7 1 2 Ø 6 35 1 4 Indoor Unit Cooling Heating Evaporator Out Temperature Thermistor Evaporator In Temperature Thermistor M M Sirocco Fan Inlet Air...

Page 207: ...10 MULTI SINGLE Indoor unit Ceiling concealed duct Low static pressure 5 Wiring Diagrams Models ZBNW09GL2A0 CL09R N20 ZBNW12GL2A0 CL12R N20 ZBNW18GL2A0 CL18R N20 Model ZBNW24GL3A0 CL24R N30 ...

Page 208: ...ow 02 low 03 medium 04 high 05 very high 3 Move to ESP value setting by pressing button It is 000 when delivering from the warehouse 4 Press button to setup ESP value It is possible to setup ESP value from 1 to 255 and 1 is the smallest and 255 is the biggest 5 If pressing button long for 3 seconds it enters into remote controller setter setup mode If pressing once shortly it enters into user setu...

Page 209: ... 73 12 09 11 22 10 14 8 83 7 30 115 13 69 13 05 12 18 11 09 9 78 8 25 120 14 67 14 02 13 16 12 07 10 76 9 23 125 15 66 15 01 14 15 13 06 11 75 10 22 130 16 67 16 02 15 16 14 07 12 76 11 23 135 16 18 15 10 13 79 12 26 140 16 14 14 83 13 30 145 15 89 14 36 Setting Value Static Pressure mmAq Pa 0 0 1 10 2 20 3 30 4 40 5 50 Air Flow Rate m min 85 10 19 90 12 18 10 71 11 09 95 13 81 12 34 12 19 100 15 ...

Page 210: ... of the servicing inspection hole should be approved by the customer There should not be any heat source or steam near the unit Avoid the following installation location 1 Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated These may cause heat exchange efficiency reduction or water drops drain pump mal function In these cases take the following act...

Page 211: ...or the humidity rise above RH 80 the dew protective kit should be equipped or use additional insulation to the indoor unit body Dew Protective kit is sold separately Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least Chassis code A mm B mm L1 800 800 L2 800 1 000 L3 800 1 200 Use the ventilation fan for smoke collecting hood with sufficient capacity Cook...

Page 212: ...d washer onto the suspension bolts for locking the suspension bolts on the ceiling Mount the suspension bolts to the set anchor firmly Secure the installation plates onto the suspension bolts adjust level roughly using nuts washers and spring washers 5 In case of ducted type unit apply a joint canvas between the unit and duct to absorb unnecessary vibration The following parts are local purchasing...

Page 213: ...it breaker switch between power source and the unit Confirm the Specification of power source Confirm that electrical capacity is sufficient Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate Confirm that the cable thickness is as specified in the power sources specification Particularly note the relation between cable length and t...

Page 214: ... the infiltration of foreign particle from outside Otherwise a short circuit may occur inside the electric parts box When clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps Also when wiring make sure the cover on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts...

Page 215: ...0 mm 27 6 19 inch So the drain head should be installed below 700 mm 27 6 19 inch Be sure to install heat insulation on the drain piping Heat insulation material Polyethylene foam with thickness more than 8 mm 5 16 inch Maintenance drain port Upward routing not allowed Pipe clamp Indoor unit According to type of indoor unit external appearance could be different 1 50 1 100 slope Hanger distance Ha...

Page 216: ...n connection on the indoor unit and drain piping fittings should be referenced from Specifications of each models Piping material Use the Polyvinyl chloride pipe Be sure to install heat insulation on the drain piping Heat insulation material Polyethylene foam with thickness more than 8 mm 5 16 inch U trap is not required for low static model in which the external static pressure is below 50 pa 5mm...

Page 217: ...ter on the evaporator 3 Check the drainage Ensure that water flows through drain hose of indoor unit without any leakage Use the following procedure to test the drain pump operation 1 Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end 2 Feed water to the flexible drain hose and check the piping for leakage 3 Be sure to check the drain pump for nor...

Page 218: ...he pipe down from the combination should be as large as possible The pipe work should be kept as short as possible and the number of indoor units per group kept to a minimum Face the vent pipe opening facing downward to keep foreign matter from penetrating the system Face piping downward Vent pipe Face the vent pipe opening facing downward to keep foreign matter from penetrating the system ...

Page 219: ...eiling Suspended Unit MULTI SINGLE Indoor unit 1 List of Functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring diagrams 6 Air flow and temperature distribution 7 Sound levels 8 Installation ...

Page 220: ...o cleaning X Auto operation artificial intelligence X Auto Restart O Child lock O Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O Auto Elevation Grille X Special Functions Wi Fi O Accessory Humidity Control O Comes with product Wireless Remote Controller O Wired Remote Controller X Network Solution LGAP O Note 1 O Applied X Not applied Accesso...

Page 221: ...ints Dry Contact For Setback O PDRYCB300 O PDRYCB500 Dry Contact For Modbus O Gateway IDU PI485 PHNFP14A0 Connected with the Indoor Units X PSNFP14A0 Connected with the Indoor Units X ETC Remote temperature sensor PQRSTA0 O Zone controller ABZCA X Electronic thermostat AQETC X CTI Communication transfer interface PKFC0 X COဌSensor PES C0RV0 For ERV ERV DX Indoor units X Group control wire PZCWRCG3...

Page 222: ... 0 Ø 21 5 16 0 Sound Pressure Level Cooling H M L dB A 42 40 39 46 45 43 Sound Power Level Cooling Max dB A 55 61 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter shoul...

Page 223: ...Level Cooling H M L dB A 46 43 40 46 43 40 Sound Power Level Cooling Max dB A 63 63 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be considered for electrical...

Page 224: ...Level Cooling H M L dB A 48 44 40 48 44 40 Sound Power Level Cooling Max dB A 63 63 Power and Communication Cable included Earth No x mm 4C x 0 75 4C x 0 75 Note 1 Due to our policy of innovation some specifications may be changed without notification 2 Wiring cable size must comply with the applicable local and national code And Electric characteristics chapter should be considered for electrical...

Page 225: ...7 MULTI SINGLE Indoor unit Ceiling Suspended Unit 3 Dimensions ZVNW18GM1A0 UV18R N10 ZVNW24GM1A0 UV24R N10 Chassis code VM1 ...

Page 226: ...3 Dimensions 8 MULTI SINGLE Indoor unit Ceiling Suspended Unit ZVNW36GM2A0 UV36R N20 ZVNW42GM2A0 UV42R N20 ZVNW48GM2A0 UV48R N20 ZVNW60GM2A0 UV60R N20 Chassis code VM2 ...

Page 227: ...e CN ROOM Thermistor for evaporator inlet temperature CN PIPE IN Thermistor for evaporator outlet temperature CN PIPE OUT Humid sensor CN_HUMID Model Gas Liquid ZVNW18GM1A0 UV18R N10 Ø12 7 Ø6 35 ZVNW24GM1A0 UV24R N10 Ø15 88 Ø9 52 Ø12 7 Ø6 35 Heat exchanger Gas pipe connection port flare connection Liquid pipe connection port flare connection Cooling Thermistor for suction air temperature Thermisto...

Page 228: ...nlet temperature CN PIPE IN Thermistor for evaporator outlet temperature CN PIPE OUT Humid sensor CN_HUMID Model Gas Liquid ZVNW36GM2A0 UV36R N20 ZVNW42GM2A0 UV42R N20 ZVNW48GM2A0 UV48R N20 ZVNW60GM2A0 UV60R N20 Ø15 88 Ø9 52 Heat exchanger Gas pipe connection port flare connection Liquid pipe connection port flare connection Cooling Capillary Tube Strainer Cross Flow Fan M Heating Thermistor for e...

Page 229: ...MULTI SINGLE Indoor unit Ceiling Suspended Unit 5 Wiring Diagrams Models ZVNW18GM1A0 UV18R N10 ZVNW24GM1A0 UV24R N10 ZVNW36GM2A0 UV36R N20 ZVNW42GM2A0 UV42R N20 ZVNW48GM2A0 UV48R N20 ZVNW60GM2A0 UV60R N20 ...

Page 230: ...M1A0 UV24R N10 ZVNW36GM2A0 UV36R N20 ZVNW42GM2A0 UV42R N20 1m Microphone 1m 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Low 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 50...

Page 231: ...ZVNW60GM2A0 UV60R N20 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB 20μPa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold High Middle Ǹ Low ...

Page 232: ...1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR 90 Cooling 10 20 30 40 50 60 70 80 90 100 125 250 500 1000 2000 4000 8000 Sound Power Level 0dB 10E 6μW m 2 Octave Band Center Frequency Hz NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 75 NR 25 NR 20 NR 80 NR 85 NR ...

Page 233: ...city m s Temperature C Heating 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 0 5 1 0 1 5 1 0 0 5 0 25 0 25 25 26 27 36 32 35 33 34 28 30 29 31 Discharge angle 0 Air velocity m s Temperature C Cooling 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 1 5 2 0 1 0 0 5 0 25 22 22 23 19 18 17 20 21 Discharge...

Page 234: ...Air velocity m s Temperature C Heating 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 0 5 1 0 2 0 2 5 1 5 0 25 29 30 33 34 31 32 Discharge angle 0 Air velocity m s Temperature C Cooling 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 1 5 2 5 1 0 2 0 0 5 0 25 20 19 18 17 21 16 22 Discharge angle 40 Air ...

Page 235: ... 40 Air velocity m s Temperature C Heating 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 0 25 0 5 2 0 2 5 1 0 1 5 29 34 33 32 30 31 Discharge angle 0 Air velocity m s Temperature C Cooling 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 2 7m 2m 1m 0m 1m 2m 3m 4m 5m 6m 7m 8m 9m 0m 10m 0 25 0 5 3 0 2 5 1 0 2 0 1 5 21 16 17 18 19 20 Discharge angle 40...

Page 236: ...t is sufficient The servicing inspection hole of the ceiling should be larger than the indoor unit The selection of the servicing inspection hole should be approved by the customer There should not be any heat source or steam near the unit Avoid the following installation location 1 Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated These may cause...

Page 237: ...high frequency generators CAUTION If the temperature rise above 30 or the humidity rise above RH 80 the dew protective kit should be equipped or use additional insulation to the indoor unit body Dew Protective kit is sold separately Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least Use the ventilation fan for smoke collecting hood with sufficient capaci...

Page 238: ...nd piping hole 3 Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose 4 Drill the hole for anchor bolt on the wall or ceiling Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling Mount the suspension bolts to the set anchor firmly Secure the installation plates onto the suspen...

Page 239: ... washer M10 CAUTION Tighten the nut and bolt to prevent the unit from falling Chassis Bolt lactions Unit mm A B VM1 1 018 355 VM2 1 418 355 Flat washer for M10 accessory Flat washer for M10 accessory Hanging bolt W3 8 or M10 Nut W3 8 or M10 Nut W3 8 or M10 Spring washer M10 a Set anchor Old building New building b Plate washer c Spring washer d Nut e Suspension bolts z G i h u j h G z z z z G t U ...

Page 240: ...from side panel and paper bracket from side cover 4 Knock out the pipe hole from the left side cover with nipper plier 5 Remove the rubber stopple in the desired drain direction Important It is recommended to select the left side for drain to have common hole in the side cover along with pipe and wiring Knock hole on right side cover only if right side is selected for water drain CAUTION Hold the ...

Page 241: ...r Declination CAUTION Installation with declination of the indoor unit is very important for the drain of air conditioner Minimum thickness of the insulation for the connecting pipe shall be 10mm If the Installation Plates are fixed to horizontal line the indoor unit after installing will be declined to the bottomside Front of view The unit must be horizontal or inclined at angle The inclination s...

Page 242: ...connection on the indoor unit and drain piping fittings should be referenced from Specifications of each models Piping material Use the Polyvinyl chloride pipe Be sure to install heat insulation on the drain piping Heat insulation material Polyethylene foam with thickness more than 8 mm 5 16 inch U trap is not required for low static model in which the external static pressure is below 50 pa 5mm A...

Page 243: ...ould point downward for easy drain flow Do not make drain piping like the following Be sure to execute heat insulation on the drain piping The feature can be changed according to type of model k G i Downward slope Do not raise Water leakage Accumulated drain water Air Waving Water leakage Tip of drain hose dipped in water Water leakage Ditch Less than 50mm gap ...

Page 244: ... source Confirm that electrical capacity is sufficient Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate Confirm that the cable thickness is as specified in the power sources specification Particularly note the relation between cable length and thickness Do not install the leakage breaker in a place which is wet or moist Water or ...

Page 245: ...ration of foreign particle from outside Otherwise a short circuit may occur inside the electric parts box When clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps Also when wiring make sure the cover on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box cover ...

Page 246: ... Electronics Inc All Rights Reserved Printed in Korea February 2018 The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system The specifications designs and information in this brochure are subject to change without notice ...

Reviews: