5
MULTI/SINGLE
Indoor unit
Ceiling concealed duct - Low static pressure
2. Specifications
Model Name
Unit
ZBNW09GL2A0
[CL09R N20]
ZBNW12GL2A0
[CL12R N20]
Power Supply
V , Ø , Hz
220-240, 1, 50
220-240, 1, 50
220, 1, 60
220, 1, 60
Casing
-
-
Dimensions
W x H x D
mm
900 × 190 × 700
900 × 190 × 700
Net Weight
kg
24.0
24.0
Shipping Weight
kg
26.0
26.0
Heat Exchanger
Rows x Columns x FPI
2 × 11 × 18
2 × 11 × 18
Face Area
m²
0.17
0.17
Fan Type
Sirocco
Sirocco
Air Flow Rate
H / M / L
m³/min
10.0 / 8.5 / 7.0
10.0 / 8.5 / 7.0
External static pressure High Mode_Factory Set
Pa (mmAq)
24.5 (2.5)
24.5 (2.5)
Fan Motor
Type
BLDC
BLDC
Drive
Internal
Internal
Output
W x No.
19 × 1 + 5 × 1
19 × 1 + 5 × 1
Power Input
H / M / L
W
40 / 32 / 26
40 / 32 / 26
FLA (Full Load Ampere)
A
0.8
0.8
Dehumidification Rate
˜
/h
0.55
1.11
Safety Device
Fuse / Thermal Protector for Fan Motor
Piping Connections
Liquid Side
mm (inch)
Ø 6.35 (1/4)
Ø 6.35 (1/4)
Gas Side
mm (inch)
Ø 9.52 (3/8)
Ø 9.52 (3/8)
Drain Pipe
O.D. / I.D.
mm
Ø 32.0 / 25.0
Ø 32.0 / 25.0
Sound Pressure Level
Cooling
H / M / L
dB(A)
31 / 28 / 27
31 / 28 / 27
Sound Power Level
Cooling
Max.
dB(A)
55
55
Power and Communication Cable (included Earth)
No. x mm²
4C x 0.75
4C x 0.75
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Anechoic chamber. Therefore, these values depend on the ambient conditions and values are normally higher
in actual operation.
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
Summary of Contents for AM07BP NSJ
Page 1: ...Indoor unit R32 Heat Pump 50 60Hz 0CTI5 02A Replaces 0CTI5 01C P No MFL67502513 ...
Page 140: ...MULTI SINGLE Indoor unit 3 Dimensions 14 Ceiling Mounted cassette 4 way ZTNW18GQLA0 CT18R NQ0 ...
Page 141: ...3 Dimensions 15 MULTI SINGLE Indoor unit Ceiling Mounted cassette 4 way ZTNW24GPLA0 CT24R NP0 ...