6. External Static Pressure & Air Flow
21
MULTI/SINGLE
Indoor unit
Ceiling concealed duct - Middle static pressure
ZBNW42GM2A0 [UM42R N20]
ZBNW48GM3A0 [UM48R N30], ZBNW60GM3A0 [UM60R N30]
Note
The above table shows the correlation between the air rates and E.S.P.
Setting value
Static Pressure (mmAq(Pa))
5(49)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
Air Flow Rate [m³/min]
90
22.2
95
25.1
22.3
100
28.0
25.4
105
30.9
28.5
23.3
110
33.8
31.6
26.8
115
36.7
34.8
30.3
24.4
120
39.7
37.9
33.8
28.3
23.5
125
42.6
41.0
37.3
32.2
27.5
130
44.1
40.8
36.1
31.6
26.1
135
44.3
40.0
35.6
30.4
28.0
140
43.9
39.7
34.6
32.4
145
43.7
38.9
36.8
150
43.1
41.2
155
45.6
Setting value
Static Pressure (mmAq(Pa))
5(49)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
Air Flow Rate [m³/min]
70
25.1
75
29.5
26.1
80
34.0
30.8
25.9
85
38.4
35.4
30.6
23.2
90
42.9
40.1
35.2
28.1
21.0
95
47.3
44.8
39.9
33.1
26.3
19.5
100
51.8
49.4
44.6
38.0
31.7
25.2
22.6
105
56.2
54.1
49.2
43.0
37.1
31.0
28.5
110
58.8
53.9
47.9
42.4
36.7
34.4
115
58.6
52.9
47.8
42.5
40.3
120
57.8
53.1
48.2
46.1
121
54.2
49.4
47.3