Product Data 36
YA Chassis
PTAC
6RWU0-06A
2.2 Digital Controls
Simultaneously press this
,
buttons and hold for 3 seconds to enter the setup ready state with the letter
in the display.
The 1st Digit number is changed sequentially from 1 to 6 when the
button is pressed to select desired set-
ting option.
Select the 2nd digit value through the
buttons and set the desired setting value for each option.
Automatically save previous setting value when Option is changed by the
button.
Simultaneously press this
,
buttons and hold for 3 seconds to escape the function. (Display phase tem-
perature during normal escape)
※
Escape automatically when no button is pressed for 3 minutes.
* Not available on all models.
Control Type
1
0
Local/Wifi,LG Exclusive Wired Remote Controller(option)
Default setting
1
Remote
Energy Saver
2
0
Off
Default setting
1
On
Temperature
Display
3
0
Fahrenheit
Default setting
1
Celsius
Cooling
Heating
Temperature Limit
4
0
54°F(12.2°C)~86°F(30.0°C)
54°F(12.2°C)~86°F(30.0°C)
Default setting
1
56°F(13.3°C)~86°F(30.0°C)
54°F(12.2°C)~84°F(28.9°C)
2
58°F(14.4°C)~86°F(30.0°C)
54°F(12.2°C)~82°F(27.8°C)
3
60°F(15.5°C)~86°F(30.0°C)
54°F(12.2°C)~80°F(26.7°C)
4
62°F(16.6°C)~86°F(30.0°C)
54°F(12.2°C)~78°F(25.5°C)
5
64°F(17.7°C)~86°F(30.0°C)
54°F(12.2°C)~76°F(24.4°C)
6
66°F(18.9°C)~86°F(30.0°C)
54°F(12.2°C)~74°F(23.3°C)
7
68°F(20.0°C)~86°F(30.0°C)
54°F(12.2°C)~72°F(22.2°C)
Unit Type
5
0
Electric Heat Pump
Default setting
1
Electric Heater
2
Cooling Only
3
Heat Pump Only
Make Up
Air Mode*
(Option)
6
0
Off
Default setting
1
On