INSTALLATION OF UNIT
35
ENGLISH
Display
Title
Cause of Error
Outdoor unit related error
3
2
1
Master Inverter Compressor High
Discharge Temperature
System is turned off by Master Inverter Compressor
High Discharge Temperature
2
Slave Inverter Compressor High Discharge
Temperature (For 20/23/25RT Only)
System is turned off by Slave Inverter Compressor High
Discharge Temperature
3
3
1
Master Constant Speed Compressor1
High Discharge Temperature
System is turned off by Master Constant Speed
Compressor1 High Discharge Temperature
2
Slave Constant Speed Compressor1 High
Discharge Temperature (For 20/23/25RT Only)
System is turned off by Slave Constant Speed
Compressor1 High Discharge Temperature
3
4
1
High Pressure of Master
System is turned off by excessive increase of high pres-
sure of Master
2
High Pressure of Slave (For 20/23/25RT
Only)
System is turned off by excessive increase of high pres-
sure of Slave
3
5
1
Low Pressure of Master
System is turned off by excessive decrease of low pres-
sure of Master
2
Low Pressure of Slave (For 20/23/25RT
Only)
System is turned off by excessive decrease of low pres-
sure of Slave
3
6
1
Master low compression ratio.
5 minutes after the compressor operation, the compression
ratio is less than 1,8 or continuous operation for 3 minutes
in condition less than differential pressure 400kPa.
2
Slave low compression ratio. (For
20/23/25RT Only)
5 minutes after the compressor operation, the compression
ratio is less than 1,8 or continuous operation for 3 minutes
in condition less than differential pressure 400kPa.
4
0
1
Master Inverter Compressor CT Sensor
Fault
Master Inverter Compressor CT Sensor open or short
2
Slave Inverter Compressor CT Sensor
Fault (For 20/23/25RT Only)
Slave Inverter Compressor CT Sensor open or short
4
1
1
Master Inverter Compressor Discharge
Temperature Sensor Fault
Master Inverter Compressor Discharge Temperature
Sensor open or short
2
Slave Inverter Compressor Discharge
Temperature Sensor Fault (For 20/23/25RT Only)
Slave Inverter Compressor Discharge Temperature
Sensor open or short
4
2
1
Master Low Pressure Sensor Fault
Master Low Pressure Sensor open or short
2
Slave Low Pressure Sensor Fault (For
20/23/25RT Only)
Slave Low Pressure Sensor open or short
4
3
1
Master High Pressure Sensor Fault
Master High Pressure Sensor open or short
2
Slave High Pressure Sensor Fault (For
20/23/25RT Only)
Slave High Pressure Sensor open or short
4
4
1
Master Air Temperature Sensor Fault
Master Air Temperature Sensor open or short
2
Slave Air Temperature Sensor Fault (For
20/23/25RT Only)
Slave Air Temperature Sensor open or short
4
6
1
Master Suction Temperature Sensor
Fault
Master Suction Temperature Sensor open or short
2
Slave Suction Temperature Sensor Fault
(For 20/23/25RT Only)
Slave Suction Temperature Sensor open or short
4
7
1
Master Constant Speed Compressor1
Discharge Temperature Sensor Fault
Master Constant Speed Compressor1 Discharge
Temperature Sensor open or short
2
Slave Constant Speed Compressor1
Discharge Temperature Sensor Fault
(For 20/23/25RT Only)
Slave Constant Speed Compressor1 Discharge
Temperature Sensor open or short