INSTALLATION OF UNIT
3
9
ENGLISH
Starting the Unit
(If unit is equipped with electric heater.)
Check to ensure all grilles and registers are
open and all unit access doors are closed
before start-up.
Turn on unit main power supply.
Press the E/Heater operation button on the
Remote controller.
Set the temperature approximately 5˚C above
room temperature.
Verify that the unit airflow rate is adjusted
according to information provided in
"Determining Evaporator Fan Adjustment" sec-
tion of this manual.
To start the unit in the cooling mode, close
unit disconnect switch and set the operating
mode to COOL and move the cooling set
point approximately 5˚C below room tempera-
ture. The condenser fan motor, compressor
and evaporator fan motor should operate auto-
matically. There will be a delay of up to 3 min-
utes before the unit will start in the cooling
mode.
After the unit has operated in the cooling
mode for a short period of time, install pres-
sure gauges on the gauge ports of the suction
line valves.
Check the suction pressures and compare
them to the normal operating pressures about
from 700~1000kPa
With the compressor operating, check the line
voltage at the unit. The voltage should be
within the range shown on the unit name-
plate. If low voltage is encountered, check the
size and length of the supply line from the
main disconnect to the unit. The line may be
undersized for the length of the run.
Heating Mode
Cooling Mode
Operating Pressures
Voltage
NOTE
!
• Always route refrigerant hoses through
the port hole provided and have com-
pressor access panel in place.
NOTE
!
• Do not use pressures to determine the
unit refrigerant charge. The correct
charge is shown on the unit nameplate.
To charge the system accurately, use
superheat charging or weigh the charge.
WARNING
•Bodily injury can result from high volt-
age electrical components. If operating
checks must be performed with the unit
operating, it is the technician's responsi-
bility to recognize these hazards and
proceed safely. Failure to do so could
result in severe personal injury or death
due to electrical shock or contact with
moving parts.
!