Installation
24
Water Quality
Water quality should comply with EN 98/83 EC Directives. Requirement for resolved chemical ingre-
dients is following table. Detailed water quality condition can be found in EN 98/83 EC Directives.
Frost protection
In areas of the country where entering water temperatures drop below 0℃(32℉), the water pipe must
be protected by using an approved antifreeze solution. Consult your Indoor unit supplier for locally ap-
proved solutions in your area. Calculate the approximate volume of water in the system. (Except the In-
door unit.) And add antifreeze solution to the total volume to allow for the water contained in Indoor unit.
Parameter Value
Acrylamide 0.10
μg
/
l
Antimony 5.0
μg
/
l
Arsenic 10
μg
/
l
Benzene 1.0
μg
/
l
Benzo(a)pyrene 0.010
μg
/
l
Boron 1.0
mg
/
l
Bromate 10
μg
/
l
Cadmium 5.0
μg
/
l
Chromium 50
μg
/
l
Copper 2.0
mg
/
l
Cyanide 50
μg
/
l
1.2-dichloroethane 3.0
μg
/
l
Epichlorohydrin 0.10
μg
/
l
Parameter Value
Fluoride 1.5
mg
/
l
Lead 10
μg
/
l
Mercury 1.0
μg
/
l
Nickel 20
μg
/
l
Nitrate 50
mg
/
l
Nitrite 0.50
mg
/
l
Pesticides 0.10
μg
/
l
Pesticides — Total 0.50
μg
/
l
Polycyclic aromatic hydrocarbons 0.10
μg
/
l
Selenium 10
μg
/
l
Tetrachloroethene and Trichloroethene 10
μg
/
l
Trihalomethanes — Total 100
μg
/
l
Vinyl chloride 0.50
μg
/
l
CAUTION
• If the unit is installed at existing hydraulic water loop, it is important to clean hydraulic pipes to remove
sludge and scale.
• Installing sludge strainer in the water loop is very important to prevent performance degrade.
• Chemical treatment to prevent rust should be performed by installer.
CAUTION
1. Use only one of the above antifreeze.
2. If a antifreeze is used, pressure drop and capability degradation of the system can occur.
3. If one of antifreezes is used, corrosion can occur. So please add corrosion inhibitor.
4. Please check the concentration of the antifreeze periodically to keep same concentration.
5. When the antifreeze is used (for installation or operation), take care to ensure that antifreeze
must not be touched.
6. Ensure to respect all laws and norms of your country about Anti-freeze usage.
Type of Antifreeze
Minimum Temperature for Freeze Protection
0℃(32℉)
-5℃(23℉)
-10℃(14℉)
-15℃(5℉)
-20℃(-4℉) -25℃(-13℉)
Ethylene glycol
0%
12%
20%
30%
-
-
Propylene glycol
0%
17%
25%
33%
-
-
Methanol
0%
6%
12%
16%
24%
30%
Summary of Contents for AHNW166T0
Page 73: ......