Installation
16
Collective / Continuous Installation for roof top use
Space required for collective installation and continuous installation: When installing several
units, leave space between each block as shown below considering passage for air and people.
1. One row of stand alone installation
2. Rows of collective installation (2 or more)
• L should be smaller than H
L
300 or
more
3000 or
more
H
600 or
more
1500 or
more
100 or
more
L ≤ H
[Unit:mm]
100 or
more
2000 or
more
200 or
more
1000 or
more
[Unit:mm]
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction
hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average snow-
fall) if it is installed at the area with much snowfall.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the
width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.