1. Installation Places
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat
radiation from the condenser is not restricted.
• Ensure that the spaces indicated by arrows
around front, back and side of the unit.
• Do not place animals and plants in the path of
the warm air.
• Take the air conditioner weight into account and
select a place where noise and vibration are min-
imum.
• Select a place so that the warm air and noise
from the air conditioner do not disturb neighbors.
More than
300mm
Fence or
obstacles
More than 700mm
More than 600mm
More than
More than
300mm
300mm
More than
300mm
Sunroof
Installation of Outdoor Unit
Installation of Outdoor Unit
2. Piping length and the elevation
6
Air Conditioner
Unit : mm
FREE JOINT SINGLE OUTDOOR
Ceiling Cassette
Model
Capacity
Pipe Size
Length A(m)
Elevation B(m)
Additional
Refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
AUUQ18GH1
5kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
AUUQ21GH1
6kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
AUUQ24GH1
7kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AUUQ36GH1
10kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AUUQ42GH1
12.5kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AUUQ48GH1
13.4kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AUUQ54GH1
15.8kW
Ø19.05(3/4) Ø9.52(3/8)
7.5
50
5
30
40
Model
Capacity
Pipe Size
Length A(m)
Elevation B(m)
Additional
Refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
ATUQ18GPLE3
5kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
ATUQ21GPLE3
6kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
ATUQ24GNLE3
7kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ATUQ36GMLE3
10kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ATUQ42GMLE3 12.5kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ATUQ48GMLE3 13.4kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ATUQ54GMLE3 15.8kW
Ø19.05(3/4) Ø9.52(3/8)
7.5
50
5
30
40