7
Installation of Outdoor Unit
Ceiling Suspended Air conditioner
Ceiling Concealed Duct
Ceiling Concealed Duct – Low static
Model
Capacity
Pipe Size
Length A(m)
Elevation B(m)
Additional
Refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
AVUQ18GJLA0
5kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
AVUQ21GJLA0
6kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
AVUQ24GJLA0
7kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AVUQ36GKLA0
10kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AVUQ42GLLA0
12.5kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AVUQ48GLLA0
13.4kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
AVUQ54GLLA0
15.8kW
Ø19.05(3/4) Ø9.52(3/8)
7.5
50
5
30
40
Model
Capacity
Pipe Size
Length A(m)
Elevation B(m)
Additional
Gas
Liquid
Standard
Max.
Standard
Max.
(g/m)
ABUQ18GHLA0
ABUQ18GL2A0
5kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
ABUQ21GHLA0
ABUQ21GL2A0
6kW
Ø12.7(1/2)
Ø6.35(1/4)
7.5
30
5
15
20
ABUQ24GGLA0
ABUQ24GL3A0
7kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ABUQ36GGLA0
10kW
Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ABUQ42GRLA0 12.5kW Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ABUQ48GRLA0 13.4kW Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
40
ABUQ54GRLA0 15.8kW Ø19.05(3/4) Ø9.52(3/8)
7.5
50
5
30
40