Indoor unit

R410A

6CIM0-01B (Replaces 6CIM0-01A)

Summary of Contents for 6CIM0-01B

Page 1: ...Indoor unit R410A 6CIM0 01B Replaces 6CIM0 01A ...

Page 2: ... house which gives us an edge to LG to make better and latest technology products with best quality in optimized time systems are equipped with inverter technology and R410A refrigerant which is perfect solution to vari ous installation locations This Engineering product data book incorporates information about the product itself and installation designing for system The comprehensive study of thi...

Page 3: ...General information 1 Model line up 2 Nomenclature 3 Appearance Indoor unit ...

Page 4: ...s Chassis Wall mounted Ceiling cassette SB SC SB SC TR TQ AMNW09GDBL0 LMN096HVT AMNW12GDBL0 LMN126HVT AMNW18GDCL0 LMN186HVT AMNW09GDBR0 LMAN096HVT AMNW12GDBR0 LMAN126HVT AMNW09GB1A0 LMDN095HV AMNW12GB1A0 LMDN125HV AMNW12GTRA0 LMCN125HV AMNW18GDCR0 LMAN186HVT AMNW18GTQA0 LMCN185HV AMNW18GB2A0 LMDN185HV B1 B2 Low static pressure Slim Ceiling concealed duct ...

Page 5: ...Model type W DC Inverter heat pump Ex 9 000 Btu h Class 09 18 000 Btu h Class 18 Cooling heating capacity Electrical rating G 208 230V 1Ø 60Hz Chassis name Indoor unit type D Wall Mounted ART COOL Mirror T Ceiling cassette B Ceiling concealed duct Function A Basic L Plasma Wall mounted C Plasma ceiling cassette ART COOL Mirror type front panel color R Mirror 2 Nomenclature ...

Page 6: ... AMNW18GTQA0 LMCN185HV AMNW09GDBR0 LMAN096HVT AMNW12GDBR0 LMAN126HVT AMNW18GDCR0 LMAN186HVT AMNW09GDBL0 LMN096HVT AMNW12GDBL0 LMN126HVT AMNW18GDCL0 LMN186HVT 3 2 Control system standard These controllers will be provided with the respective indoor units Type Simple wired remote controller Wireless remote controller Wireless remote controller Individual controller Applicable model Ceiling concealed...

Page 7: ...1 Wall Mounted 2 ART COOL Mirror 3 Ceiling cassette 4 way 4 Ceiling concealed duct Low static pressure Indoor unit ...

Page 8: ...1 List of functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring Diagrams 6 Capacity Tables 7 Air flow and temperature distributions reference data 8 Sound levels 9 Controller 10 Installation Indoor unit ...

Page 9: ...ungus O Installation Drain pump X E S P control X Electric heater X High ceiling operation X Auto Elevation Grille X Reliability Hot start O Self diagnosis O Soft dry operation O Convenience Auto changeover X Auto cleaning O Auto operation artificial intelligence O Auto Restart O Child lock O Forced operation O Group control X Sleep mode O Timer on off O Timer weekly O Two thermistor control O Ind...

Page 10: ...0 0 22 1 10 0 22 1 14 5 32 0 Heat Exchanger Row x Column x Fins per inch x No 2 x 16 x 23 x 1 2 x 16 x 23 x 1 3 x 18 x 22 x 1 Face Area m2 ft2 0 22 2 37 0 22 2 37 0 29 3 07 Fan Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Air Flow Rate H M L m3 min 7 0 6 5 6 0 9 5 9 0 8 5 16 2 14 2 12 3 H M L ft3 min 247 230 212 335 318 300 572 501 434 Fan Motor Type BLDC BLDC BLDC Output W x No 14 4 x 1 14 4...

Page 11: ...er cable should be connected with the outdoor unit 76 Seongsan dong Changwon City Gyeongnam 641 713 Korea CHASSIS CODE SB WALL MOUNTED AMNW09GDBL0 LMN096HVT AMNW12GDBL0 LMN126HVT Display signal receiver Part Name Front panel Air suction grille Installation plate Knockout hole 5 No 2 4 3 1 Remark Note 285 11 7 32 50 1 31 32 210 8 9 32 45 1 25 32 895 35 1 4 341 13 15 32 323 12 23 32 128 5 1 32 37 1 ...

Page 12: ...n City Gyeongnam 641 713 Korea CHASSIS CODE SC WALL MOUNTED AMNW18GDCL0 LMN186HVT Display signal receiver Part Name Front panel Air suction grille Installation plate Knockout hole 5 No 2 4 3 1 Remark Note Unit mm inch 250 9 27 32 1030 40 9 16 325 12 25 32 210 8 9 32 Ø 70 2 3 4 Ø70 2 3 4 69 2 23 32 56 2 7 32 Right rear piping Left rear piping Installation Plate Measuring Tape Measuring Tape Hanger ...

Page 13: ...Refrigerant pipe connection port diameters Unit mm inch Notes Description is expressed based on Cooling mode Model Gas Liquid AMNW09GDBL0 LMN096HVT AMNW12GDBL0 LMN126HVT Ø9 52 3 8 Ø6 35 1 4 AMNW18GDCL0 LMN186HVT Ø12 7 1 2 Ø6 35 1 4 Description PCB Connector Thermistor for Indoor Air Temperature CN_TH1 Thermistor for Evaporator Inlet Temperature Thermistor for Evaporator Outlet Temperature CN_TH2 T...

Page 14: ...5 Wiring diagrams Models AMNW09GDBL0 LMN096HVT AMNW12GDBL0 LMN126HVT Models AMNW18GDCL0 LMN186HVT 6 _ Wall mounted Indoor Units Indoor unit ...

Page 15: ... 00 6 69 8 40 6 84 9 10 6 98 9 60 7 12 11 60 10 35 12 30 10 66 13 00 11 02 13 50 11 27 14 50 10 72 15 20 10 22 11 20 9 60 11 90 9 83 12 60 10 10 13 10 10 30 14 00 10 00 14 70 9 73 10 50 8 63 11 20 8 74 12 00 8 90 12 50 9 00 13 40 9 02 14 10 9 09 10 30 8 72 11 00 8 75 11 70 8 79 12 00 8 90 13 10 9 03 13 80 9 10 9 80 8 51 10 50 8 60 11 20 8 73 11 70 8 82 12 70 9 32 13 40 9 67 9 50 8 63 10 30 8 86 11...

Page 16: ...0 9 10 9 5 9 7 2 8 3 9 3 10 4 10 8 10 8 5 8 7 2 8 2 9 2 10 3 10 7 10 8 5 5 6 9 8 0 9 0 10 0 10 5 10 5 8 0 9 8 11 3 12 6 14 0 14 6 14 6 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 8 9 6 11 1 12 4 13 8 14 4 14 4 7 7 9 5 11 0 12 3 13 7 14 3 14 3 7 4 9 2 10 6 12 0 13 4 13 9 14 0 12 0 14 8 16 9 18 9 20 9 21 9 22 0 11 9 14 6 16 7 18 8 20 8 21 8 21 8 11 8 14 6 16 7 18 7 20 7 21 7 ...

Page 17: ...ity ft s Temperature F 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 70 75 81 86 91 3 3 6 6 4 9 1 6 Air velocity ft s Temperature F Discharge angle 40 Discharge angle 50 3 3 6 6 4 9 1 6 Air velocity ft s Temperature F 70 75 81 86 91 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0f...

Page 18: ...t 7ft 3ft 0ft 26ft 23ft 20ft 16ft 13ft 10ft 7ft 3ft 0ft 64 68 72 75 3 3 1 6 8 2 4 9 Temperature F Air velocity ft s 9ft 7ft 3ft 0ft 26ft 23ft 20ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 26ft 23ft 20ft 16ft 13ft 10ft 7ft 3ft 0ft Discharge angle 40 Discharge angle 50 7 Air flow and temperature distributions reference data 10 _ Wall mounted Indoor Units Indoor unit ...

Page 19: ...0 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level 0dB 20μPa Octave Band CenterFrequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level 0dB 20μPa Octave Band CenterFrequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 ...

Page 20: ...de Cooling operation A Auto operation or auto changeover C Dehumidifying oper ation D Heating operation B Air circu lation E h N Jet cooling heating button Warms up or cools down the indoor temperature within a short period of time i j H I Air flow direction button Adjusts the air flow direction vertically or horizontally k S Temperature display button Displays the room temperature Press key and h...

Page 21: ...shall be performed by authorized personnel only Installation work must be performed in accordance with the national wiring standards by authorized personal only Vinyl tape Wide Apply after carrying out a drainage test To carry out the drainage test remove the air filters and pour water into the heat exchanger Saddle Installation plate Sleeve Bushing Sleeve Putty Gum Type Sealant Bend the pipe as c...

Page 22: ...SB Chassis 133 5 1 4 95 3 3 4 Installation plate Left rear piping Right rear piping Ø70 Ø2 3 4 Ø70 Ø2 3 4 Unit mm inch 2 Installation plate dimensions 14 _ Wall mounted 10 Installation Indoor Units Indoor unit ...

Page 23: ...allation Plate Measuring Tape Measuring Tape Hanger Place a level on raised tab Unit Outline 207 8 5 32 105 4 1 8 Unit mm inch 460 18 1 8 570 22 7 16 Use only those accessories Standard or optional which have designated specilications CAUTION 10 Installation Wall mounted _ 15 Indoor Units Indoor unit ...

Page 24: ...terline It is also important to use caution concerning the location of the installation plate Routing of the wiring to power outlets is through the walls typically Drilling the hole through the wall for piping connections must be done safely 10 4 Before piping work Good case Press on the upper side of clamp and unfold the tubing to downward slowly More than 200 7 7 8 More than 100 3 15 16 More tha...

Page 25: ...tion of the instal lation plate engage the three hooks at the top of the indoor unit with the upper edge of the installation plate Ensure that the hooks are properly seated on the instal lation plate by moving it left and right Unlock the tubing holder from the chassis and mount between the chassis and installation plate in order to separate the bottom side of the indoor unit from the wall Chassis...

Page 26: ... unit Align the center of the pipes and sufficiently tighten the flare nut by hand Tighten the flare nut with a wrench When needed to extend the drain hose of indoor unit assembly the drain pipe as shown on the drawing Connecting pipe Connecting cable Tape Drain hose Spanner fixed Connection pipe Flare nut Torque wrench Vinyl tape narrow Adhesive Drain pipe Indoor unit drain hose Drain hose Connec...

Page 27: ...original positon Ensure that the hooks are properly seated on the instal lation plate by moving it left and right Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound Finish the assembly by screwing the unit to the installa tion plate by using two pieces of type C screws And assemble a chassis cover Plastic bands Ins...

Page 28: ... piping The drain hose should point downward for easy drain flow Do not make drain piping like the following Drain pan Drain hose Leakage checking Connecting area drain hose Leakage checking Downward slope Do not raise Accumulated drain water Tip of drain hose dipped in water Air Waving Water leakage Water leakage Ditch Less than 50mm gap Water leakage 20 _ Wall mounted 10 Installation Indoor Unit...

Page 29: ... 1 List of functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring Diagrams 6 Capacity Tables 7 Air flow and temperature distributions reference data 8 Sound levels 9 Controller 10 Installation Indoor unit ...

Page 30: ...Grille Reliability Hot start Self diagnosis Soft dry operation Convenience Auto changeover Auto cleaning Auto operation artificial intelligence Auto Restart Child lock Forced operation Group control Sleep mode Timer on off Timer weekly Two thermistor control Individual controller Wired remote controller Deluxe wired remote controller Simple wired remote controller Simple Wired remote controller fo...

Page 31: ...32 Net Weight Body kg lbs 11 0 24 3 11 0 24 3 15 5 34 2 Heat Exchanger Row x Column x Fins per inch x No 2 x 16 x 23 x 1 2 x 16 x 23 x 1 3 x 18 x 22 x 1 Face Area m2 ft2 0 22 2 37 0 22 2 37 0 29 3 07 Fan Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Air Flow Rate H M L m3 min 7 0 6 5 6 0 9 5 9 0 8 5 16 2 14 2 12 3 H M L ft3 min 247 230 212 335 318 300 572 501 434 Fan Motor Type BLDC BLDC BLDC ...

Page 32: ...ole 5 No 2 4 3 1 Remark Note 1 Unit should be installed in compliance with the installation manual in the product box 2 Unit shall be grounded in accordance with the local regulations or applicable national codes 3 The Unit is powered from the outdoor unit Therefore power cable should be connected with the outdoor unit 307 12 3 32 895 35 1 4 205 8 1 16 190 7 15 32 289 11 3 8 675 26 9 16 327 12 7 8...

Page 33: ...ordance with the local regulations or applicable national codes 3 The Unit is powered from the outdoor unit Therefore power cable should be connected with the outdoor unit Ø70 2 3 4 Ø70 2 3 4 69 2 23 3 2 56 2 7 3 2 46 1 13 1 6 Right rear piping Left rear piping Installation Plate Measuring Tape Measuring Tape Hanger Place a level on raised tab Unit Outline 207 8 5 32 105 4 1 8 460 18 1 8 570 22 7 ...

Page 34: ...Evaporator Outlet Temperature Heat Exchanger Cross Flow Fan M n Refrigerant pipe connection port diameters Unit mm inch Notes Description is expressed based on Cooling mode Model Gas Liquid AMNW09GDBR0 LMAN096HVT AMNW12GDBR0 LMAN126HVT Ø9 52 3 8 Ø6 35 1 4 AMNW18GDCR0 LMAN186HVT Ø12 7 1 2 Ø6 35 1 4 Description PCB Connector Thermistor for Indoor Air Temperature CN_TH1 Thermistor for Evaporator Inle...

Page 35: ...Models AMNW09GDBR0 LMAN096HVT AMNW12GDBR0 LMAN126HVT Models AMNW18GDCR0 LMAN186HVT 5 Wiring diagrams 6 _ ART COOL Mirror Indoor Units Indoor unit ...

Page 36: ...8 20 6 42 8 60 6 53 9 30 6 79 9 80 6 97 7 00 6 30 7 50 6 47 8 00 6 69 8 40 6 84 9 10 6 98 9 60 7 12 11 60 10 35 12 30 10 66 13 00 11 02 13 50 11 27 14 50 10 72 15 20 10 22 11 20 9 60 11 90 9 83 12 60 10 10 13 10 10 30 14 00 10 00 14 70 9 73 10 50 8 63 11 20 8 74 12 00 8 90 12 50 9 00 13 40 9 02 14 10 9 09 10 30 8 72 11 00 8 75 11 70 8 79 12 00 8 90 13 10 9 03 13 80 9 10 9 80 8 51 10 50 8 60 11 20 ...

Page 37: ...4 10 9 10 9 5 9 7 3 8 4 9 4 10 4 10 9 10 9 5 9 7 2 8 3 9 3 10 4 10 8 10 8 5 8 7 2 8 2 9 2 10 3 10 7 10 8 5 5 6 9 8 0 9 0 10 0 10 5 10 5 8 0 9 8 11 3 12 6 14 0 14 6 14 6 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 8 9 6 11 1 12 4 13 8 14 4 14 4 7 7 9 5 11 0 12 3 13 7 14 3 14 3 7 4 9 2 10 6 12 0 13 4 13 9 14 0 12 0 14 8 16 9 18 9 20 9 21 9 22 0 11 9 14 6 16 7 18 8 20 8 21 8 2...

Page 38: ...ing Heating 72 68 75 64 3 3 4 9 1 6 Air velocity ft s Temperature F 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 16ft 13ft 10ft 7ft 3ft 0ft 70 75 81 86 91 3 3 6 6 4 9 1 6 Air velocity ft s Temperature F Discharge angle 40 Discharge angle 50 3 3 6 6 4 9 1 6 Air velocity ft s Temperature F 70 75 81 86...

Page 39: ...ature F 91 86 81 75 70 Air velocity ft s 9ft 7ft 3ft 0ft 26ft 23ft 20ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 26ft 23ft 20ft 16ft 13ft 10ft 7ft 3ft 0ft 64 68 72 75 3 3 1 6 8 2 4 9 Temperature F Air velocity ft s 9ft 7ft 3ft 0ft 26ft 23ft 20ft 16ft 13ft 10ft 7ft 3ft 0ft 9ft 7ft 3ft 0ft 26ft 23ft 20ft 16ft 13ft 10ft 7ft 3ft 0ft Discharge angle 40 Discharge angle 50 ...

Page 40: ... 33 39 37 30 36 33 27 31 28 Octave Band Center Frequency Hz Sound Pressure Level dB re 20uPa Octave Band Center Frequency Hz Sound Pressure Level dB re 20uPa Octave Band Center Frequency Hz Sound Pressure Level dB re 20uPa 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60...

Page 41: ...e Cooling operation A Auto operation or auto changeover C Dehumidifying oper ation D Heating operation B Air circu lation E h N Jet cooling heating button Warms up or cools down the indoor temperature within a short period of time i j H I Air flow direction button Adjusts the air flow direction vertically or horizontally k S Temperature display button Displays the room temperature Press key and ho...

Page 42: ... read the instruction sheets completely before installing the product When the power cord is damaged replacement work shall be performed by authorized personnel only Installation work must be performed in accordance with the national wiring standards by authorized personal only Vinyl tape Wide Apply after carrying out a drainage test To carry out the drainage test remove the air filters and pour w...

Page 43: ... Chassis 133 5 1 4 95 3 3 4 Installation plate Left rear piping Right rear piping Ø70 Ø2 3 4 Ø70 Ø2 3 4 Unit mm inch 2 Installation plate dimensions Indoor Units 14 _ ART COOL Mirror 10 Installation Indoor unit ...

Page 44: ...llation Plate Measuring Tape Measuring Tape Hanger Place a level on raised tab Unit Outline 207 8 5 32 105 4 1 8 Unit mm inch 460 18 1 8 570 22 7 16 Use only those accessories Standard or optional which have designated specilications CAUTION Indoor Units 10 Installation ART COOL Mirror _ 15 Indoor unit ...

Page 45: ...line using Horizontal meter Measure the wall and mark the centerline It is also important to use caution concerning the location of the installation plate Routing of the wiring to power outlets is through the walls typically Drilling the hole through the wall for piping connections must be done safely 10 4 Before piping work Good case Press on the upper side of clamp and unfold the tubing to downw...

Page 46: ...plate Ensure that the hooks are properly seated on the instal lation plate by moving it left and right Unlock the tubing holder from the chassis and mount between the chassis and installation plate in order to separate the bottom side of the indoor unit from the wall Piping Insert the connecting cable through the bottom side of indoor unit and connect the cable You can see detail contents in Conne...

Page 47: ...he unit Foamed polyethylene or equivalent is recommended Left side piping Right side piping 2 Connecting the installation pipe and drain hose to the indoor unit Align the center of the pipes and sufficiently tighten the flare nut by hand Tighten the flare nut with a wrench When needed to extend the drain hose of indoor unit assembly the drain pipe as shown on the drawing Connecting pipe Tape Drain...

Page 48: ...riginal positon Ensure that the hooks are properly seated on the instal lation plate by moving it left and right Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots clicking sound Finish the assembly by screwing the unit to the installa tion plate by using two pieces of type C screws And assemble a chassis cover Plastic bands Insu...

Page 49: ...iping The drain hose should point downward for easy drain flow Do not make drain piping like the following Drain pan Drain hose Leakage checking Connecting area drain hose Leakage checking Downward slope Do not raise Accumulated drain water Tip of drain hose dipped in water Air Waving Water leakage Water leakage Ditch Less than 50mm gap Water leakage Indoor Units 20 _ ART COOL Mirror 10 Installati...

Page 50: ... way 1 List of functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring Diagrams 6 Capacity Tables 7 Air flow and temperature distributions reference data 8 Sound levels 9 Controller 10 Installation Indoor unit ...

Page 51: ... Forced operation O Group control O Sleep mode O Timer on off O Timer weekly O Two thermistor control O Wired remote controller PQRCVSL0 PQRCVSL0QW Deluxe wired remote controller X Individual control Simple wired remote controller PQRCVCL0Q PQRCVCL0QW Simple Wired remote controller for hotel use X Wireless remote controller O General central controller Non LGAP X Network Network Solution LGAP O fu...

Page 52: ...ht Body kg lbs 14 0 30 9 15 0 33 1 Heat Exchanger Row x Column x Fins per inch x No 2 x 8 x 18 x 1 2 x 10 x 18 x 1 Face Area m2 ft2 0 22 2 40 0 28 3 00 Fan Type Turbo Fan Turbo Fan Air Flow Rate H M L m3 min 9 5 8 0 7 0 13 0 12 0 11 0 H M L ft3 min 335 283 247 459 424 388 Fan Motor Type BLDC BLDC Output W x No 43 x 1 43 x 1 Running Current A 0 25 0 25 Sound Pressure Level H M L dB A 38 35 32 38 37...

Page 53: ...1 32 Air outlet hole 700 27 9 16 378 6 14 29 32 380 14 31 32 Air outlet hole 172 6 25 32 378 6 14 29 32 4 R 2 0 4 R 2 5 3 2 22 7 8 570 22 7 16 570 22 7 16 517 20 11 32 517 20 11 32 461 18 5 32 523 20 19 32 214 8 7 16 53 2 3 32 142 5 5 5 8 30 1 3 16 19 3 4 84 5 3 5 16 59 5 2 11 32 570 22 7 16 35 1 11 32 4 3 2 1 6 5 Unit mm inch 7 Note 1 Unit should be installed in compliance with the installation m...

Page 54: ...e with the installation manual in the product box 2 Unit shall be grounded in accordance with the local regulations or applicable national codes 3 The Unit is powered from the outdoor unit Therefore power cable should be connected with the outdoor unit 700 27 9 16 473 18 5 8 55 2 5 32 380 14 31 32 Air outlet hole 700 27 9 16 378 6 14 29 32 380 14 31 32 Air outlet hole 172 6 25 32 378 6 14 29 32 4 ...

Page 55: ...ndoor Air Temperature Thermistor for Evaporator Outlet Temperature n Refrigerant pipe connection port diameters Model Gas Liquid AMNW12GTRA0 LMCN125HV Ø9 52 3 8 Ø6 35 1 4 AMNW18GTQA0 LMCN185HV Ø12 7 1 2 Ø6 35 1 4 Unit mm inch Notes Description is expressed based on Cooling mode Description PCB Connector Thermistor for Indoor Air Temperature CN_ROOM Thermistor for Evaporator Inlet Temperature CN_PI...

Page 56: ...5 Wiring diagrams 6 _ Ceiling cassette 4 way Indoor Units Indoor unit Models AMNW12GTRA0 LMCN125HV AMNW18GTQA0 LMCN185HV ...

Page 57: ... 90 14 70 9 63 10 50 8 51 11 20 8 62 12 00 8 79 12 50 8 89 13 40 8 90 14 10 8 98 10 30 8 60 11 00 8 63 11 70 8 67 12 00 8 90 13 10 8 92 13 80 8 99 9 80 8 37 10 50 8 49 11 20 8 61 11 70 8 97 12 70 9 21 13 40 9 24 9 50 8 52 10 30 8 74 11 00 8 94 11 50 9 30 12 40 9 42 13 10 9 74 9 30 8 74 10 00 9 03 10 70 9 35 11 20 9 66 12 10 9 77 12 80 10 04 17 40 15 67 18 50 16 16 19 60 16 73 20 30 17 14 21 70 16 ...

Page 58: ...14 23 32 43 50 59 TC TC TC TC TC TC TC 60 8 64 4 68 0 70 0 71 6 75 2 60 8 64 4 68 0 70 0 71 6 75 2 8 0 9 8 11 3 12 6 14 0 14 6 14 6 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 8 9 6 11 1 12 4 13 8 14 4 14 4 7 7 9 5 11 0 12 3 13 7 14 3 14 3 7 4 9 2 10 6 12 0 13 4 13 9 14 0 12 0 14 8 16 9 18 9 20 9 21 9 22 0 11 9 14 6 16 7 18 8 20 8 21 8 21 8 11 8 14 6 16 7 18 7 20 7 21 7 21 ...

Page 59: ...t 10ft 7ft 7ft 3ft 0ft 3ft 13ft 9ft 7ft 3ft 0ft 13ft 10ft 10ft 7ft 7ft 3ft 0ft 3ft 13ft Temperature ßF 6 6 64 64 68 68 72 72 75 75 6 6 4 9 4 9 3 3 3 3 1 6 1 6 Discharge angle 40 Discharge angle 50 Model AMNW12GTRA0 LMCN125HV Cooling Heating Discharge angle 40 Air velocity ft s Temperature F 9ft 7ft 3ft 0ft 5ft 5ft 8ft 8ft 0ft 6 6 6 6 4 9 4 9 3 3 3 3 1 6 1 6 9ft 7ft 3ft 0ft 5ft 5ft 8ft 8ft 0ft 64 6...

Page 60: ...are assumed to be standard 4 9ft Ceiling Octave band center frequency Hz Sound pressure level dB re 20uPa Octave band center frequency Hz Sound pressure level dB re 20uPa M L H Sound Levels dB A Model AMNW12GTRA0 LMCN125HV AMNW18GTQA0 LMCN185HV 38 38 35 37 32 34 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate ...

Page 61: ...rt Clean CLEAR ALL Button Used to clear all timer ROOM TEMPERATURE SETTING Button Used to select the room temperature ON OFF Button Used to turn on off the unit INDOOR FAN SPEED SELECTION Button Used to select fan speed in four steps low medium high and chaos UP DOWN AIRFLOW Button Used to stop or start louver movement and set the desired up down airflow direction LEFT RIGHT AIRFLOW Button Optiona...

Page 62: ...llation Owner s manual Installation manual 10 1 Accessories Check whether the following accessories are included with your unit 1 Standard accessories Please read the instruction sheets completely before installing the product When the power cord is damaged replacement work shall be performed by authorized personnel only Installation work must be performed in accordance with the national wiring st...

Page 63: ... conditioner Plan to install the circulator The air discharge port is made to give more airflow to the down wood directions The gate or exit of the building is protected by dual door system 2 In case the floor or surfaces of the place to be air conditioned is in direct contact with the outdoor air The floor of the heating room indirect contact with the storeroom garage or the outside air receives ...

Page 64: ...nsulate the unit body with some insulation like glass wool at least 13 32 inch in thickness Refrigerant piping Increase the piping insulation thickness with thickness above 13 16 inch Others Inside the ceiling near th air tight seal places To escape of the humidity inside false ceiling 4 In case of multiple indoor cassette units recommended 10 Installation 14 _ Ceiling cassette 4 way Indoor Units ...

Page 65: ...he indoor unit is easier 1 Install the indoor unit Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut and washer from the upper and lower sides of the hanger bracket NOTE Ceiling cassette 4 way _ 15 10 Installation Indoor Units Indoor unit Ceiling Anchor Long nut or turn buckle Suspension bolt False ceiling TQ TR Chassis Unit mm inch 585 660 23 1 16 26 Ceili...

Page 66: ...rip Remove the washer fixing plate used for preventing the washer from falling and tighten the upper nut 5 Remove the paper pattern for installation 3 For existing ceilings Adjust the height and position of the unit Perform steps 3 and 4 in 5 1 For new ceilings 10 6 Connecting pipes to the indoor unit 1 Refrigerant piping work please refer REFRIGERANT PIPING WORK 2 Piping insulation Perform heat i...

Page 67: ... hose connection use the clip Accessory Flexible drain hose Properly install decoration panel because any slit or gab between unit and decoration panel will result cool air leakage which may responsible for water driblling CAUTION Air conditioner unit Decoration panel Fit the insulation this part and be careful for cool air leakage False ceiling False ceiling Decoration panel Air Cool air leakage ...

Page 68: ...ws and tighten all screws completely 5 Fit the corner covers Hook clip Hook 6 Open two screws of control panel cover 7 Connect one display connector and two vane control connectors of front panel to indoor unit PCB The position marking on PCB is as Display connector CN DISP Vane control connector CN VANE 1 2 8 Close the cover for control box 9 Fit the link on the panel as shown in picture The link...

Page 69: ...en clamping the wires be sure no pressure is applied to the wire connections by using the included clamping material to make appropriate clamps Also when wiring make sure the cover on the electric parts box fits snugly by arranging the wires neatly and attaching the electric parts box cover firmly When attaching the electric parts box cover make sure no wires get caught in the edges Pass wiring th...

Page 70: ...ned too hard screws might be damaged 3 Do not connect wires of different gauge to the same grounding terminal Loose connection may deteriorate protection 4 At the unit keep proper separation between trans missio and power supply wiring The equipment may malfunction if subjected to electrical external noise 5 Never connect power supply wiring to the terminal block for remote controller wiring A mis...

Page 71: ...led duct Low static pressure 1 List of functions 2 Specifications 3 Dimensions 4 Piping diagrams 5 Wiring Diagrams 6 Capacity Tables 7 External pressure setting 8 Sound levels 9 Controller 10 Installation Indoor unit ...

Page 72: ...ce Forced operation X Group control O Sleep mode X Timer on off X Timer weekly X Two thermistor control O Wired remote controller PQRCVSL0 PQRCVSL0QW Deluxe wired remote controller X Individual control Simple wired remote controller O Simple Wired remote controller for hotel use X Wireless remote controller PQWRHDF0 General central controller Non LGAP X Network Network Solution LGAP O function Dry...

Page 73: ...32 x 22 5 8 Net Weight Body kg lbs 20 5 45 2 20 5 45 2 26 5 58 4 Heat Exchanger Row x Column x Fins per inch x No 2 x 12 x 21 x 1 2 x 12 x 21 x 1 2 x 11 x 21 x 1 Face Area m2 ft2 0 16 1 68 0 16 1 68 0 21 2 31 Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Air Flow Rate H M L m3 min 8 5 7 5 6 5 9 5 8 5 7 5 15 0 13 5 11 5 H M L ft3 min 300 265 229 335 300 265 530 477 406 External Static Pressure mmAq ...

Page 74: ...r supply connection Note 1 Unit should be installed in compliance with the installation manual in the product box 2 Unit shall be grounded in accordance with the local regulations or applicable national codes 3 The Unit is powered from the outdoor unit Therefore power cable should be connected with the outdoor unit 903 35 9 16 820 32 9 32 728 28 21 32 856 33 11 16 795 31 5 16 165 6 1 2 235 9 1 4 1...

Page 75: ...connection Note 1 Unit should be installed in compliance with the installation manual in the product box 2 Unit shall be grounded in accordance with the local regulations or applicable national codes 3 The Unit is powered from the outdoor unit Therefore power cable should be connected with the outdoor unit 2 3 4 5 6 1 1100 43 5 16 190 7 15 32 1180 46 15 32 1072 42 7 32 1131 44 17 32 20 25 32 575 2...

Page 76: ...e Thermistor for Evaporator Outlet Temperature Sirocco Fan M M n Refrigerant pipe connection port diameters Model Gas Liquid AMNW09GB1A0 LMDN095HV ø9 52 3 8 ø6 35 1 4 AMNW12GB1A0 LMDN125HV Unit mm inch Notes Description is expressed based on Cooling mode Description PCB Connector Thermistor for Indoor Air Temperature CN_ROOM Thermistor for Evaporator Inlet Temperature CN_PIPE IN Thermistor for Eva...

Page 77: ... Indoor Air Temperature Thermistor for Evaporator Outlet Temperature Sirocco Fan M M n Refrigerant pipe connection port diameters Model Gas Liquid AMNW18GB2A0 LMDN185HV ø12 7 1 2 ø6 35 1 4 Unit mm inch Notes Description is expressed based on Cooling mode Description PCB Connector Thermistor for Indoor Air Temperature CN_ROOM Thermistor for Evaporator Inlet Temperature CN_PIPE IN Thermistor for Eva...

Page 78: ...Ceiling concealed duct low static pressure _ 7 5 Wiring diagrams Indoor Units Indoor unit Models AMNW09GB1A0 LMDN095HV AMNW12GB1A0 LMDN125HV AMNW18GB2A0 LMDN185HV ...

Page 79: ...1 8 26 7 53 8 48 7 75 9 20 7 99 9 90 8 22 7 33 7 25 7 64 7 44 7 96 7 62 8 18 7 88 8 90 8 08 9 60 8 39 12 19 10 54 12 45 10 60 12 85 10 69 13 24 10 78 13 73 10 88 14 93 11 09 11 89 10 32 12 32 10 38 12 85 10 51 13 13 10 64 14 00 10 80 15 20 11 09 11 89 9 96 12 32 10 10 12 99 10 32 13 27 10 44 14 27 10 60 15 60 11 01 10 96 9 50 11 52 9 72 11 73 9 89 12 00 10 05 13 20 10 25 14 80 10 61 10 31 9 25 10 ...

Page 80: ...8 64 4 68 0 70 0 71 6 75 2 6 0 7 4 8 5 9 5 10 5 10 9 11 0 6 0 7 3 8 4 9 4 10 4 10 9 10 9 5 9 7 3 8 4 9 4 10 4 10 9 10 9 5 9 7 2 8 3 9 3 10 4 10 8 10 8 5 8 7 2 8 2 9 2 10 3 10 7 10 8 5 5 6 9 8 0 9 0 10 0 10 5 10 5 8 0 9 8 11 3 12 6 14 0 14 6 14 6 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 9 9 7 11 2 12 5 13 9 14 5 14 5 7 8 9 6 11 1 12 4 13 8 14 4 14 4 7 7 9 5 11 0 12 3 13 7 14 3 14 3 7 4 9 2 10 6 12 0 13 4...

Page 81: ...person should be respon sible for the results In this case free service cannot be provided CAUTION TEMP FAN SPEED OPER MODE Function Code Value If you want to set installer setting mode Press the Temperature up button and the oper mode button same time for five seconds 1 When you enter the setting mode Initially Function code is displayed on the LCD screen 2 No Function Code Value 1 Test Run 01 01...

Page 82: ...ior to the shift TEMP FAN SPEED OPER MODE When pressing the button and button simultaneously for more than 3 seconds the system will be entered into the installer setting mode After entering into the installer setting mode select the E S P code value by pressing the button E S P code value 03 1 Select the desired air flow rate with the button Whenever pressing the button SLo Lo Med Hi Po will be i...

Page 83: ...0V According to the fluctuation of voltage air flow rate varies Static pressure mmAq in Aq Setting value 0 0 0 1 0 04 2 0 08 3 0 12 4 0 16 Model name Step Hi Mid Lo 8 5 CMM 300CFM 75 84 94 104 114 7 5 CMM 265CFM 69 77 88 99 110 6 5 CMM 230CFM 62 71 83 95 106 9 5 CMM 336CFM 82 90 99 109 118 8 5 CMM 300CFM 75 84 94 104 114 7 5 CMM 265CFM 69 77 88 99 110 15 CMM 530CFM 90 97 105 114 122 13 5 CMM 477CF...

Page 84: ...70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Sound Pressure Level dB re 20Pa Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold Octave Band Sound Pressure Level...

Page 85: ...its Indoor unit 1 Wired remote controller 2 3 4 5 TEMP FAN SPEED OPER MODE 1 1 Operation Display Panel 2 Temperature Control Button 3 Fan Speed Button 4 On Off Button 5 Operation Mode select Button Model name PQRCVCL0QW White Color_Supplied PQRCVCL0Q Black Color_Accessory ...

Page 86: ... Button ON OFF Button OPRATION MODE SELECTION Button WIRELESS REMOTE CONTROLLER RECEIVER Some products don t receive the wireless signals AIR FLOW Button SUBFUNCTION Button FUNCTION SETTING Button VENTILATION Button RESERVATION UP DOWN LEFT RIGHT Button To check the indoor temperature press button ROOM TEMPERATURE Button SETTING CANCEL Button EXIT Button 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 h Some ...

Page 87: ... personnel only Installation work must be performed in accordance with the national wiring standards Air filter Air return Air outlet vents 10 1 Accessories Check the following accessories are included with your unit 1 Standard accessories Name Quantity Shape for gas pipe for liquid pipe Clamp metal 1 EA Insulation for fitting 1 set Other Clamp 8 EA Screws for duct flanges 1 set Owner s manual Con...

Page 88: ... the unit could fall out of place and cause serious injury Where sufficient clearance of maintenance and service can be ensured Where optimum air distribution can be ensured Where nothing blocks the air passage Where condensate can be properly drained Where piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manual of the outdoor unit Keep the i...

Page 89: ... strong enough to bear the equipment s weight Use embedded inserts or anchor bolts with new buildings and hole in anchors with old buildings Low static duct type in case of suction from back side Low static duct type in case of suction from bottom side 10 4 Position of suspension bolt A place where the unit will be leveled and that can sup port the weight of the unit A place where the unit can wit...

Page 90: ...ted according to the KS Conditions and confirmed that there is not any default However if it is operated for a long time in high humid atmosphere dew point temperature more than 73 F water drops are liable to fall In this case add heat insulation material according to the following procedure Heat insulation material Adiabatic glass wool with thick ness 13 32 to 13 16 inch Stick glass wool on all a...

Page 91: ...rse flow in any part 7 32 inch or thicker formed thermal insulation shall always be provided for the drain pipe Correct method U trap is not required for low static model in which the external static pressure is below 50 pa 5mm Aq Lay the drain hose with a downware inclination so water will drain out Wrong method 10 Installation 20 _ Ceiling concealed duct low static pressure Indoor Units Indoor u...

Page 92: ...body to wire the outdoor unit indoor units and the remote controller All wiring must be performed by an authorized electri cian This system consists of multiple indoor units Mark each indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and ID unit are properly matched If wiring and piping between the outdoor unit and an indoor unit are mismatched the system may c...

Page 93: ...ower supply wiring The equipment may malfunction if subjected to electrical external noise 5 Never connect power supply wiring to the terminal block for remote controller wiring A mistake of the sort could damage the entire system 6 Use only specified wire and tightly connect wires to terminals Be careful wires do not place external stress on terminals Keep wiring in neat order and so as not to ob...

Page 94: ...geaircon com All rights reserved December 2012 Printed in Korea The specifications designs and information in this brochure are subject to change without notice The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system ...