Ceiling cassette 4-way
_
7
6. Capacity Tables
Indoor Units
Indoor unit
n
Cooling Capacity
Notes:
1. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25ft
Level difference : 0ft
2. TC : Total Capacity(kBtu/h)
SHC: Sensible Heat Capacity(kBtu/h)
Cooling Capacity
Unit Size
(kBtu/h(kW))
Outdoor
air temp.
°F DB
Indoor Air Temp. °F DB/ °F WB
68.0 / 57.2
71.6 / 60.8
77.0 / 64.4
80.6 / 66.2
86.0 / 71.6
89.6 / 75.2
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
68.0
77.0
89.6
95.0
104.0
109.4
114.8
68.0
77.0
89.6
95.0
104.0
109.4
114.8
11.60 10.26 12.30 10.58 13.00 10.95 13.50 11.23 14.50 10.66 15.20 10.14
11.20 9.51 11.90 9.74 12.60 10.02
13.10 10.23 14.00 9.90 14.70 9.63
10.50 8.51 11.20 8.62 12.00 8.79 12.50 8.89 13.40 8.90 14.10 8.98
10.30 8.60 11.00 8.63 11.70 8.67 12.00 8.90 13.10 8.92 13.80 8.99
9.80 8.37 10.50 8.49 11.20 8.61 11.70 8.97 12.70 9.21 13.40 9.24
9.50 8.52 10.30 8.74 11.00 8.94 11.50 9.30 12.40 9.42 13.10 9.74
9.30 8.74 10.00 9.03 10.70 9.35 11.20 9.66 12.10 9.77 12.80
10.04
17.40 15.67 18.50 16.16 19.60 16.73 20.30 17.14 21.70 16.28 22.80 15.49
16.80 14.52 17.80 14.88 18.90 15.30 19.60 15.62 21.00 15.13 22.10 14.71
15.70 13.00 16.90 13.17 18.00 13.43 18.70 13.58 20.10 13.60 21.20 13.71
15.30 13.13 16.40 13.18 17.60 13.24 18.00 13.76 19.70 13.62 20.80 13.73
14.70 12.96 15.80 13.13 16.80 13.32 17.60 14.04 19.00 14.07 20.10 14.11
14.30 13.18 15.40 13.52 16.40 13.82 17.20 14.53 18.50 14.39 19.70 14.88
13.90 13.52 15.00 13.62 16.00 14.45 16.80 14.92 18.20 14.92 19.20 15.33
12
(3.52)
18
(5.28)