Chapter 5. GM PROGRAMMING
5 - 1
Chapter 5. GM PROGRAMMING
5.1 Programming for Controlling Inverter Speed with 5 Step Analog Output Voltage
1) System Configuration
2) Initial Settings
(1) Enabled channel : channel 0
(2) Data input type specification :channel 0(-192
~
16191)
(3) Output condition of D/A conversion module when the CPU is stopping : minimum value output of the range.
(4) Offset : 0 V Gain :5 V
3) Descriptions of the Program
(1) %I0.0.0 turning On leads to the initial setting of D/A conversion
(2) %I0.0.1 turning On leads to output of "0"(O V) on channel 0.
(3) %I0.0.2 turning On leads to output of "4000"(2.5 V) on channel 0
(4) %I0.0.3 turning On leads to output of "8000"(5 V) on channel 0.
(5) %I0.0.4 turning On leads to output of "12000"(7.5 V) on channel 0.
(6) %I0.0.5 turning On leads to output of "16000"(10 V) on channel 0.
Summary of Contents for G3F-DA4I
Page 42: ...Chapter 5 GM PROGRAMMING 5 5 6 I O Variables on Program ...
Page 44: ...Chapter 5 GM PROGRAMMING 5 7 4 Program INI_STAT ...
Page 45: ...Chapter 5 GM PROGRAMMING 5 8 5 I O Variables on Program ...
Page 47: ...Chapter 5 GM PROGRAMMING 5 10 4 Program ...
Page 48: ...Chapter 5 GM PROGRAMMING 5 11 5 I O Variables on Program ...
Page 74: ...Chapter 10 G3F PA1A G3F PA2A POWER SUPPLY MODULE 10 3 10 4 Dimensions ...
Page 75: ...Chapter 11 DIMENSIONS 11 1 Chapter 11 DIMENSIONS 11 1 G3F DA4V G3F DA4I Dimensions ...
Page 76: ...Chapter 11 DIMENSIONS 11 2 11 2 G4F DA1A Dimensions ...