Chapter 2. SPECIFICATIONS
2 - 7
2.5 Input/Output Conversion Characteristics
I/O characteristics are displayed as a slant of the line connecting offset value and gain value in converting an
digital signal from the external PLC into an analog signal(voltage or current).
The I/O conversion characteristics of the D/A conversion module are shown.
2.5.1 Offset/ Gain Value
1) Offset and gain value is as follows
a) Offset value
Data format of -8192
~
8191: When digital input value is -8000, offset value is analog output value.
Data format of -192
~
16191: When digital input value is 0, offset value is analog output value.
b) Gain value
Data format of -8192
~
8191: When digital input value is 0, offset value is analog output value.
Data format of -192
~
16191: When digital input value is 8000, offset value is analog output value.
2) Factory set value of offset and gain value is like table 2.4.
Module name
Analog input range
Offset value
Gain value
G3F-DA4I
DC 4
~
20 mA
DC 4 mA
DC 12 mA
G3F-DA4V
-10
~
10 VDC
-10 VDC
0 VDC
G3F-DA1A
-10
~
10 VDC
-10 VDC
0 VDC
[Table 2.4] Factory set value of offset and gain
3) Offset and gain value can be selected per channel on test mode.
2.5.2 Example for I/O Conversion Characteristic.
Input/ output conversion characteristic example is shown on Fig 2.1
[Fig 2.1] Input/ output conversion characteristic example
Summary of Contents for G3F-DA4I
Page 42: ...Chapter 5 GM PROGRAMMING 5 5 6 I O Variables on Program ...
Page 44: ...Chapter 5 GM PROGRAMMING 5 7 4 Program INI_STAT ...
Page 45: ...Chapter 5 GM PROGRAMMING 5 8 5 I O Variables on Program ...
Page 47: ...Chapter 5 GM PROGRAMMING 5 10 4 Program ...
Page 48: ...Chapter 5 GM PROGRAMMING 5 11 5 I O Variables on Program ...
Page 74: ...Chapter 10 G3F PA1A G3F PA2A POWER SUPPLY MODULE 10 3 10 4 Dimensions ...
Page 75: ...Chapter 11 DIMENSIONS 11 1 Chapter 11 DIMENSIONS 11 1 G3F DA4V G3F DA4I Dimensions ...
Page 76: ...Chapter 11 DIMENSIONS 11 2 11 2 G4F DA1A Dimensions ...