Chapter 8. MK PROGRAMMING
8 - 3
8
.2 Application Programming
8.2.1 Programming for Controlling Inverter Speed with 5-step Analog Output Voltage
1) System Configuration
2) Initial Settings
(1) Enabled channel : channel 0
(2) Data input type specification :channel 0(-192
~
16191)
(3) Output condition of D/A conversion module when the CPU is stopping : minimum value output of the range.
(4) Offset : 0 V Gain :5 V
3) Descriptions of the Program
(1) P0000 turning On leads to the initial setting of D/A conversion
(2) P0001 turning On leads to output of "0"(0 V) on channel 0.
(3) P0002 turning On leads to output of "4000"(2.5 V) on channel 0
(4) P0003 turning On leads to output of "8000"(5 V) on channel 0.
(5) P0004 turning On leads to output of "12000"(7.5 V) on channel 0.
(6) P0005 turning On leads to output of "16000"(10 V) on channel 0.
(P0000)
(P0001)
(P0002)
(P0003)
(P0004)
(P0005)
Initial
GM3-
PA2A
K7P-
30AS
G3I-
D22A
G3F-
DA4V
K7S-
PA2A