background image

20

To mount the battery pack on a wall, take the following steps :
1.  Mark the location on the wall for the holes.
2.  Drill holes for fasteners in the wall.
3.  Drive the fasteners through the mounting bracket into the holes.

Area 1

Area 3

Area 2

Area 4

At least 250mm

Ex)

• 

Recommended diameter :  

10mm(0.4") Min.

• 

Recommended length :  

70mm(2.8") Min.

• 

Recommended material :  

Stainless steel (8.8T)

• 

Minimum fastener count :  

4(Area1) / 2(Area2) / 4(Area3) / 2(Area4)

- Vertically

• 

Minimum fastener clearance : At least 

250mm(10")   

ex. Between Area 1’s last fastener  and 

Installation

Summary of Contents for RESU10H StorEdge

Page 1: ...INSTALLATION MANUAL 10H ...

Page 2: ...on However this manual is subject to change without prior notice In addition the illustrations in this manual are meant only to help explain system configuration concepts and installation instructions Please note the image shown is for illustration purposes only Rev 1_Nov 2016 ...

Page 3: ...e 13 2 3 Warehouse storage instructions 13 2 3 1 Packaging specification 13 2 3 2 Handling 14 3 Installation 15 3 1 Mechanical requirements 15 3 1 1 Unboxing the package 15 3 1 2 Items in the package 17 3 1 3 Installation locations 17 3 1 4 Clearance 18 3 1 5 Tools safety gears required 18 3 1 6 Mounting bracket 19 3 1 7 Appearance and dimension 21 3 1 8 System clearance 21 3 1 9 Installing the ba...

Page 4: ...ystem 30 5 2 Shutting off the system 30 5 3 Emergency procedure 31 5 3 1 Fire 31 5 3 2 Damaged or smoking batteries 31 6 Troubleshooting 32 6 1 Troubleshooting 32 7 Uninstallation Return 33 7 1 Return replacement instructions 33 7 1 1 Uninstallation from the wall 33 7 1 2 Contact information 35 Contents ...

Page 5: ... reach of children Read the instruction manual before starting installation and operation Heavy weight may cause serious injury to the back Do not dispose of the product with household wastes Recyclable Disconnect the equipment before carrying out maintenance or repair Observe precautions for handling electrostatic discharge sensitive devices ...

Page 6: ...evice The electronics inside the Battery Pack are vulnerable to electrostatic discharge Be sure to be grounded before handling the Battery Pack Read the label with Warning Symbols and Precautions which is visibly under to the Battery Cover see Section 1 3 1 2 2 Battery handling guide Do not expose battery to temperature over 50 Do not damage the unit in such ways as dropping deforming impacting cu...

Page 7: ...w over the battery pack or submerge battery pack in liquids Do not expose or place near water sources like downspouts or sprinklers If the battery pack is installed in the garage then ensure the product is above the height of the vehicle bumper Ensure proper care is taken to keep off any foreign object on top of the battery pack The RESU battery pack has been certified IP55 and can be installed in...

Page 8: ... with accidents On land Place damaged battery into a segregated place and call local fire department or service engineer In water Stay out of the water and don t touch anything if any part of the battery inverter or wiring is submarged Do not use submerged battery again and contact the service engineer Fire fighting instructions If fire occurs when charging batteries if it is safe to do so shut off t...

Page 9: ...9 Safety 1 3 Warning label Warning labels and other relevant labels are attached to the inside of the battery pack 1 2 3 1 Warning label 2 Product label 3 Traceability label ...

Page 10: ...aller who has all of the following skills and experience Knowledge of the functional principles and operation of on grid and off grid backup systems Knowledge of the dangers and risks associated with installing and using electrical devices and acceptable mitigation methods Knowledge of the installation of electrical devices Knowledge of and adherence to this guide and all safety precautions and be...

Page 11: ...troduction 2 1 Technical data 2 1 1 Dimensions and weight RESU10H P N EVESPBO0100A0 Width 744 mm 29 3 Height 907 mm 35 7 Depth 206 mm 8 1 Weight 1 99 8 kg 220 lbs 1 A battery pack s weight varies slightly 907 744 206 ...

Page 12: ...Connector User interface LEDs for Normal and Fault operation Operating Conditions Installation Location Indoor Outdoor Wall Mounted Operating Temperature 14 to 113 F 10 to 45 C Operating Temperature Recommended 59 to 86 F 15 to 30 C Storage Temperature 22 to 131 F 30 to 55 C Humidity 5 to 95 Altitude Max 6 562ft 2 000m Cooling Strategy Natural Convection Safety Cell UL1642 Battery Pack UL1973 CE R...

Page 13: ...e Polarity Inrush Current Ground Fault Over Temp Battery inside between Li Ion battery and DC DC converter Internal Short Circuit Over Voltage Over Current Over Temp Under Voltage Flexible installation Indoor or Outdoor 2 3 Warehouse storage instructions 2 3 1 Packaging specification Category Contents Size LxWxH mm 1 120 44 1 100 43 450 17 7 Outer Size Qty Box ea 1 1ea 2 layers Packaging Materials...

Page 14: ...ouct Store the product on a flat surface There must be no flammable or explosive materials nearby The temperature and humidity should be maintained at a constant level There should be minimal dust and dirt in the area Do not store this product in a place exposed to direct sunlight Store this product out of reach of children and animals Product Introduction ...

Page 15: ...stallation 3 1 Mechanical requirements 3 1 1 Unboxing the package 1 Lift the cover upwards to remove it 2 Pull out other items Take them out and check if any item is missing See Package items on section 3 1 2 ...

Page 16: ...ning pad 4 Remove the side cover 5 Pull out the battery pack using handles and stand it up Lift handles are sold optionally for this product Installation CAUTION According to regional regulations several people may be required for moving equipment ...

Page 17: ...e and humidity should be maintained at a constant level There should be minimal dust and dirt in the area Battery pack must be installed on walls that are upright and can support 330lbs 150kg Do not install this product in a place exposed to the direct sunlight and rain snow falls Install this product out of reach of children and animals CAUTION If the ambient temperature is outside the operating ...

Page 18: ...and bottom of the product is shown in the figure for the proper ventilation and installer convenience 3 1 5 Tools safety gears required Tools The following tools are required to install the battery pack Precision screwdriver M6 Torque wrench Inclinometer Drill Min Diameter 10mm 0 4 Pencil or Marker Installation ...

Page 19: ...t When installing the battery pack on a wall make sure that the wall is capable of supporting the weight of the battery pack Min 150kg CAUTION Make sure that the battery pack is at all times exposed to the ambient air The battery pack is cooled by natural convection If the battery pack is entirely or partially covered or shielded it may cause the battery pack to stop operating Installation ...

Page 20: ...teners through the mounting bracket into the holes Area 1 Area 3 Area 2 Area 4 At least 250mm Ex Recommended diameter 10mm 0 4 Min Recommended length 70mm 2 8 Min Recommended material Stainless steel 8 8T Minimum fastener count 4 Area1 2 Area2 4 Area3 2 Area4 Vertically Minimum fastener clearance At least 250mm 10 ex Between Area 1 s last fastener and Installation ...

Page 21: ... the battery pack Pack appearance and dimension 907mm 35 7 206mm 8 1 744mm 29 2 Color and Material Front Rear Cover Silver or Gold Aluminum Top Bottom LED Cover Black Plastic 3 1 8 System clearance Battery requires adequate clearance for installation cabling and airflow Minimum clearance in the system configuration is as follows 300mm 12 300mm 12 Inverter 600mm 24 Floor Floor Installation ...

Page 22: ... the rear marked position of both left and right sides Top Bottom 2 Mount the wall bracket to a wall Tighten the screws ensuring that they are horizontally driven into the wall Must be installed with recommended clearances 720mm 29 on the edge of the wall bracket as shown in the figure 3 Mount the battery pack to a wall bracket s U shape clip using the support by lift handles Remove the lift handl...

Page 23: ...o a torque of 5 N m using the M6 torque wrench 5 Press the two buttons and pull the two latches marked position on the rear side of the wiring box cover hinged door Wiring box cover 6 Open the wiring box cover about 2 10 degrees and pull to remove it CAUTION The wiring box cover is heavy approx 1 6kg 3 5lb If dropped it may cause injury Installation ...

Page 24: ...the bottom side and assemble the conduit plug In the case outdoor it must be sealed to comply IP55 ex gasket sealing foam silicon etc where the battery pack installation is outdoor 9 Connection Power Communication cables according to the labels marked CAUTION If you lose or break a protection cover that violates NEC Regulation Installation ...

Page 25: ...e AWG Max length Pinning At first connect the ground wire to terminal 2 Then make connections to the other terminals one after another except terminal 6 Leave terminal 6 unconnected For the specifications of the terminal block see section 3 2 1 Spring Terminal blocks 12 Connecting the battery pack to the inverter Refer to the installation instructions for the inverter to connect the power cable an...

Page 26: ...26 13 Reattach the transparent protection cover and tighten with the screw Marked position Close the wiring box cover Reattach battery over the two latchets on the rear Installation ...

Page 27: ...10m 35ft Cable type 4 10 10 12AWG DC 600V insulated Pinning Phoenix contact PCB terminal block SPT 5 3 V 7 5 ZB P N 1719325 GND 2 Communication terminal block Max cable length 10m 35ft Cable type 0 2 1 5 18 22AWG Pinning Phoenix contact PCB terminal block SPT 2 5 6 V 5 0 P N 1991134 12V AUX GND AUX BAT Enable CAN High CAN Low Reserve Installation ...

Page 28: ...e to connector sequence 1 To remove one of the wires from its terminal insert a small screwdriver into the rectangular hall above the terminal 2 Apply slight pressure to the screwdriver and at the same time pull out the wire Installation ...

Page 29: ...9 4 Commissioning 4 1 LED status 4 1 1 LED indicators The LED indicators on the front of the battery pack show its operational state as follows LED status Action Power on Idle Charging Discharging Fault ...

Page 30: ...main battery pack See if the battery pack is successfully initialized The power on indicator on the front should turn on in green 3 Turn on the inverter 5 2 Shutting off the system To shut down the battery pack take the following steps 1 Turn off the inverter 2 Turn off the battery pack by moving the circuit breaker switch to the OFF position 3 Make sure that every indicator on the battery pack is...

Page 31: ...he following countermeasures 1 If it is safe to do so disconnect the battery pack circuit breaker 2 If the battery pack is not on fire yet extinguish the fire before the battery pack catches fire 3 If the battery pack is on fire do not try to extinguish but evacuate people immediately CAUTION When the battery pack is burning it leaks poisonous gases 5 3 2 Damaged or smoking batteries Damaged or sm...

Page 32: ...what caused the warning The possible warning messages are as follows Battery over voltage Battery under voltage Battery over temperature Battery under temperature Battery discharge over current Battery charge over current BMS internal communication Battery cell voltage imbalance The abnormal state is cleared when the battery pack recovers normal operation personnel Installer or LG Chem NOTE For a ...

Page 33: ...witch OFF the Inverter before starting the uninstallation of the battery pack 2 Press the two buttons and pull the two latches marked position on the rear 3 Open the wiring box cover about 2 10 degrees and pull to remove it 4 Loosen the screw marked position and remove the transparent protection cover ...

Page 34: ...connect the power cable from the terminal block Disconnect the positive terminal first and next the negative terminal and finally ground terminal 8 Assemble transparent protection cover Close the wiring box cover and lock the ratchet 9 Loosen the two hex socket screws using a socket wrench to detach the battery pack from the wall using lift handles Uninstallation Return CAUTION According to region...

Page 35: ... Oksan myeon Heungdeok gu Cheongju si Chungcheongbuk do South Korea Telephone 82 43 219 2695 Email Soongkyu lgchem com US Address 1064 Chicago Rd Troy MI 48083 USA Telephone 1 248 808 0016 Email CSNorthAmericaESS lgchem com Europe Address Otto Volger Str 7C 65843 Sulzbach Taunus Germany Telephone 49 162 297 0918 Email aburkert lgchem com Australia Address 3 6 Pelle St Mitchell ACT 291 Telephone 61...

Page 36: ... 2016 LG Chem LG Twin Towers 128 Yeoui daero Yeongdeungpo gu Seoul Korea 07336 TEL 82 2 3773 1114 FAX 82 2 3773 7005 http www lgesspartner com http www lgchem com Keep this manual for later use ...

Reviews: