WARNING:
Voltage references to the meter should be connected to a circuit breaker in the panel and/or with
appropriate fusing based on the NEC
®
and any local codes that are applicable.
NOTE: 347/600 V
and
480 V
delta services require external PTs to step down the voltages before being wired to
the meter.
Utilize the correct column below for the type of service being monitored. If none of the examples below match the
form of service in the panel, please refer to the full manual for additional types.
Now use the appropriate diagram on the following page for attaching the voltage references depending on the
panel feed.
For 120/208/240 VAC services
Verify that the meter has the appropriately installed
terminal block in place shown here:
A transformer is included with the meter for
powering the device. Make sure the connections
from the secondary side of the transformer and the
plug J2 below are made correctly:
For 277/480 VAC wye services
SECTION 2: VOLTAGE AND METER POWER WIRING REFERENCE
AUXN
Red
Blue
N
A
AUXA
J2
White
Bl
a
ck
Brown
White
AUXN
N
A
AUXA
J2
Yellow
Or
a
nge
WEB
VERSION