NOTE: To be installed per all appropriate codes per your jurisdiction.
NOTE:  For indoor use only.
1.   Determine from where repeater will get power, choices are:

•   Dedicated power supply (Use Leviton #A0015-000 or equivalent). Power 

supply must be a Listed Class 2 power supply or Listed ITE power supply 

marked LPS.

•     Any  LumaCAN

TM

 network Port (requires existing LumaCAN

TM 

power supply 

with enough capacity to power repeater).

2.    Determine mounting location:

•    6-Port should be mounted in a 19" EIA rack mount enclosure, or may be 

used in a desktop configuration.

•    2-Port may be surface mounted or installed into a field box.

3.   Determine where LumaCAN

TM

 networks will be terminated:

NOTE: Each end of the network must be terminated. Any mid-point device 

must not be terminated. Any other configuration and the network will not 

work reliably.  
•     2-Port: Both ports are internally terminated and this can not be changed.
•    6-Port: Ports B-F are internally terminated and this can not be changed. 

Port A has a termination switch and should be terminated when end-of-run.

4.   Network/Power Wiring:

•   All wiring is Class 2.
•   When architecting the low voltage power system, refer to the "LumaCAN 

power considerations white paper" (available at Leviton.com) which 

identifies best practices and things to avoid. Additionally, ensure that there 

is never multiple power-supplies powering the same segment.

•   Do not connect to Ethernet networks. Although LumaCAN

TM

 uses RJ-45 

connectors, it is not Ethernet and may cause damage to Ethernet systems.

5.    Review system requirements from Leviton provided documents or as deduced 

from field requirements.

INSTALLATION PRE-REQUISITES

1.   Set Jumper positions.

•   Refer to diagrams within this document for function.

2.   Install device in the enclosure. 

•    6-Port rack mount: The device will require one "long" and one "short" 

rack mount ear. 

NOTE: two devices also may be installed side by side by removing the 

top cover, screwing the two devices together using the (2) provided holes, 

reinstalling cover, then using only the short rack mounting ears.
•    6-Port desktop: Install provided rubber feet.
•    2-Port: Device may be installed as required by field conditions and allowed 

by the authority having jurisdiction. Device is commonly installed "free air", 

or in a steel box of appropriate size provided by the contractor.

3.   Connect LumaCAN

TM

 wires.

•   Reference LumaCAN

TM

 wiring details for more information.

4.   Connect power wires.

INSTALLATION

Page 7

Summary of Contents for LumaCAN NPRPT-002

Page 1: ...0 405 5320 LESTechSupport Leviton com Para asistencia T cnica 1 800 959 6004 LESTechSupport Leviton com DI 000 NPRPT 20B LumaCANTM Repeaters 2 Port 6 Port R p teurs LumaCANMC 2 et 6 ports Repetidores...

Page 2: ......

Page 3: ...uits 19 20 tapes pr alables l installation 21 Installation 21 Cavaliers de configuration 22 23 C blage et terminaisons LumaCANMC 24 25 Topologies LumaCANMC 25 26 Mises jour logicielles 27 Diagnostic a...

Page 4: ...12 24Vdc 40 80mA Input Voltage 6 Port 12 24Vdc 85 170mA LumaCANTM segment Topology Daisy Chain Max Length 1600 Wire Type Cat 6 or better Max devices 110 Maximum Network with repeaters Length 10 000 3...

Page 5: ...es per Segment Max 250 Devices per Network Max Longest Run 10 000 Max Segment Length Between Repeaters 1 600 T Sapphire Touch Screen T Termination Switch LumaCANRepeater NPRPT 002 USB PowerIn 24VDC LE...

Page 6: ...aCANTM Repeater Switch Sector Net Sector Net Power Supply Bus Controller GreenMAX Cabinet Max 110 Devices per Segment Max 250 Devices per Network Sapphire Touch Screen T Termination Switch T LumaCANTM...

Page 7: ...nMAX Cabinet GreenMAX Cabinet LumaCAN TM LumaCAN TM Repeater LumaCAN TM Repeater LumaCAN TM Repeater LumaCAN TM Repeater Power Supply Bus Controller T Termination T T T T T T T T T T T T T T T T T T T...

Page 8: ...ON Heartbeat Blinks periodically Off is indication of internal processor failure TX Transmit One provided per port blinks when transmitting data out that port Normal operation is periodic blinking whe...

Page 9: ...t Status Indicators 4 Mounting holes for adjacent unit when mounted side by side 5 Cover removal screws Typical of 4 6 Power Input Connectors 7 LumaCANTM Ports 8 USB OTG Port Used for software updates...

Page 10: ...the low voltage power system refer to the LumaCAN power considerations white paper available at Leviton com which identifies best practices and things to avoid Additionally ensure that there is never...

Page 11: ...repeater from LumaCANTM port 1 3 4 LumaCANTM 2 will power repeater from LumaCANTM port 2 NOTE If Jumpers 1 2 3 4 are installed repeater will be powered from LumaCANTM ports AND pass power through bet...

Page 12: ...Ports F 3 4 then power is bridged between Port F Port E 2 3 No function default configuration 3 4 Power repeater from power supply on this port Port A jumpers installed on pins 1 2 No function 2 3 No...

Page 13: ...to the network cable hold the plug with the clip down and looking at it from the back to match the Figure 1 2 Insert the terminated Cat 6 plugs in to the ports on the Repeater 3 Terminate all end of l...

Page 14: ...of RJ 45 connectors These two standards are often referenced as TIA 568A and TIA 568B Although either is acceptable so long as it is consistent throughout a project Leviton requires the use of only th...

Page 15: ...ONTINUED Bad Topology STAR GreenMAX Cabinet Sapphire Touch Screen Switch Sapphire Touch Screen Switch GreenMAX Cabinet Sapphire Touch Screen Switch Sapphire Touch Screen Switch LumaCANTM Repeater Good...

Page 16: ...epeater through the terminal program Once properly communicating to the repeater you should have a command prompt as follows You may need to tap Enter CLI 2 Type update followed by Enter as follows CL...

Page 17: ...ll messages Transmit Buffer Full Code Appearance ATBF The first character A is the port from which data was received letter A F The second character T indicates a transmit buffer is full The third cha...

Page 18: ...V c c 85 170 mA Segments LumaCANMC Topologie en cascade Longueur maximale 486 7 m Type de fils cat gorie 6 ou mieux Nombre maximal de dispositifs 110 Dimensions maximales des r seaux dot s de r p teur...

Page 19: ...imum de 250 dispositifs par r seau Parcours maximal de 10 000 pi 3048m Longueur maximale des segments entre r p teurs de 1 600 pi 488m T cran tactile SapphireMD T Terminaison Commande LumaCANRepeater...

Page 20: ...C Commande SectorMD Net SectorMD Net Contr leur de bus bloc d alimentation Armoire GreenMAXMD Maximum de 110 dispositifs par segment Maximum de 250 dispositifs par r seau cran tactile SapphireMD T Ter...

Page 21: ...X MD Armoire GreenMAX MD LumaCAN MC R p teur LumaCAN MC R p teur LumaCAN MC R p teur LumaCAN MC R p teur LumaCAN MC Contr leur de bus bloc d alimentation T Terminaison T T T T T T T T T T T T T T T T...

Page 22: ...aillances du processeur interne T moins Tx transmission Clignotent quand des donn es sont transmises depuis le port correspondant En fonctionnement normal ils clignotent p riodiquement quand des donn...

Page 23: ...r pour les erreurs et RX pour la r ception 4 Trous servant fixer plusieurs unit s c te c te 5 Vis de fixation du couvercle quatre normalement 6 Connecteurs d alimentation 7 Ports LumaCANMC 8 Port USB...

Page 24: ...te Paper livre blanc sur l alimentation des r seaux LumaCANMC lequel d crit les pratiques exemplaires et les pi ges viter Il faut en outre s assurer qu il n y a jamais plus d une source d alimentation...

Page 25: ...p teur depuis le port 1 Position 3 4 LumaCanMC 2 alimentation du r p teur depuis le port 2 REMARQUE si les cavaliers sont install s aux positions 1 2 et 3 4 le r p teur sera aliment depuis les deux p...

Page 26: ...e entre ce dernier et le port E Position 2 3 aucune fonction configuration par d faut Position 3 4 alimentation du r p teur depuis ce port Positionner les cavaliers du port A pour obtenir le fonctionn...

Page 27: ...urs il faut les tenir en mettant la patte vers le bas pour que les broches correspondent l illustration 2 Ins rer les connecteurs dans les ports du r p teur 3 Effectuer des terminaisons tous les dispo...

Page 28: ...normes de configuration On les d signe souvent par les appellations TIA 568A et TIA 568B Bien que les deux soient acceptables condition qu on s en tienne la m me d un bout l autre de l installation Le...

Page 29: ...ie EN TOILE Armoire GreenMAXMD cran tactile SapphireMD Commande cran tactile SapphireMD Commande Armoire GreenMAXMD cran tactile SapphireMD Commande cran tactile SapphireMD Commande R p teur LumaCANMC...

Page 30: ...e tapes 1 Amorcer une connexion avec le r p teur par l interm diaire de l mulateur de terminal Une fois la communication tablie l invite suivante devrait appara tre l cran il pourrait tre n cessaire d...

Page 31: ...ndique le port de la m moire vis e de A F Le quatri me caract re indique le probl me F voulant dire que la m moire est pleine Ce code particulier ATBF signale donc que le port A a re u un message qu i...

Page 32: ...Voltaje de Entrada 6 Entradas 12 24 VCD 85 170mA Segmento LumaCANTM Topolog a Cadena Daisy Longitud m xima 1600 488 m Tipo de cable Categor a 6 o superior N mero m ximo de Productos 110 Red con n mero...

Page 33: ...imo 3 048 m 10 000 Largo de segmento m ximo entre repetidores 488 m 1 600 T Pantalla de toque Sapphire T Terminaci n Interruptor LumaCANRepeater NPRPT 002 USB PowerIn 24VDC LEVITON Repetidor LumaCANTM...

Page 34: ...NTM Interruptor Sector Net Sector Net Control del suministrador de alimentaci n Gabinete GreenMax Pantalla de toque Sapphire T Terminaci n Interruptor T LumaCANTM Gabinete GreenMax T T T LumaCANTM Lum...

Page 35: ...enMax Gabinete GreenMax LumaCAN TM Repetidor LumaCAN TM Repetidor LumaCAN TM Repetidor LumaCAN TM Repetidor LumaCAN TM Control del suministrador de alimentaci n T Terminaci n T T T T T T T T T T T T T...

Page 36: ...que hay falla en el procesador interno TX Transmisi n Una proporcionada por entrada parpadea cuando se est n transmitiendo datos por esa entrada En una operaci n normal parpadea peri dicamente cuando...

Page 37: ...e montaje para unidades adyacentes cuando se monta una al lado de la otra 5 Tornillos removibles de la cubierta normalmente 4 6 Conectores de Alimentaci n de Entrada 7 Entradas LumaCANTM 8 Entradas US...

Page 38: ...de energ a de LumaCANTM como documento blanco LumaCANTM Power Consideration White Paper vea este documento disponible en Leviton com el cual identifica los mejores ejemplos y las cosas para evitar Ade...

Page 39: ...e la entrada 1 LumaCANTM 3 4 2 LumaCANTM Repetir la energ a de la entrada 2 LumaCANTM NOTA Si los puentes 1 2 y 3 4 est n instalados el repetidor se alimentar de las entradas LumaCANTM y pasar n la en...

Page 40: ...entonces el puente se tiende entre la entrada F y E 2 3 No funciona configuraci n de f brica 3 4 Repetidor de energ a del suministrador de energ a en esta entradat Puentes instalados en los pines de l...

Page 41: ...avija con el clip hacia abajo y mir ndola desde atr s para que se vea como en la figura 1 2 Inserte la clavija terminada Cat 6 en la entrada del Repetidor 3 Termine todos los extremos de los productos...

Page 42: ...ecept culo RJ 45 son los siguientes Cuando termine una clavija macho RJ 45 en el cable de red sostenga la clavija con el clip hacia abajo y mirando desde la parte de atr s para que coincida con la fig...

Page 43: ...LLA Gabinete GreenMax Pantalla de Toque Sapphire Interruptor Pantalla de Toque Sapphire Interruptor Gabinete GreenMax Pantalla de Toque Sapphire Interruptor Pantalla de Toque Sapphire Interruptor Repe...

Page 44: ...del programa terminal Una vez que se comunica apropiadamente al repetidor debe tener una l nea de comandos de la siguiente manera Quiz s tenga que presionar Enter CLI 2 Escriba Update actualizaci n s...

Page 45: ...est lleno de mensajes B fer de Transmisi n Completo Aparece C digo ATBF El primer car cter A es la entrada desde donde los datos fueron recibidos A F El segundo car cter T indica que un b fer de tran...

Page 46: ...ould any of the equipment fail during the warranty period but agrees only to repair or replace defective equipment returned to its plant in Tualatin Oregon This Warranty is void on any product that ha...

Page 47: ......

Page 48: ...evice must accept any interference received including interference that may cause undesired operation D CLARATION DE CONFORMIT Ce dispositif est conforme aux exigences de la partie 15 des r glements d...

Reviews: