background image

DI-000-A8810-00A

Energy Management Hub

 

and 3-Phase Meter

EMX Data Acquisition System

Cat. No. A8810-41M/41R

Installation Guide

Summary of Contents for A8810-41M

Page 1: ...DI 000 A8810 00A Energy Management Hub and 3 Phase Meter EMX Data Acquisition System Cat No A8810 41M 41R Installation Guide...

Page 2: ......

Page 3: ...TABLE OF CONTENTS Warnings 1 Cautions 1 1 Getting Started 2 2 Site Location and Providing Power 4 3 Internal Component Configuration and Operation 7 4 Final Steps 11 5 Standard Statements 15...

Page 4: ...es See NFPA 70E in the USA or applicable local codes Product may use multiple voltage power sources Be sure all sources of power have been disconnected before servicing Do not depend on this product f...

Page 5: ...e included with the panel Enclosure Mounting Tabs Short Ethernet Patch Cable Ethernet Cable 7 Calibration Certificates Operating Manuals Engineering Drawings and Wiring Diagrams are located on the ins...

Page 6: ...round input terminals Power Meter Series 4100 Bi Directional 4DUMR split core or Rogowski coil versions Energy Monitoring Hub A8810 Power Supply Phoenix Contact Step PS 277AC 24DC 3 5A Separate 3 Phas...

Page 7: ...s for any necessary power current transformer and communications lines in the bottom of the enclosure 2 1 3 1 To maintain the warranty and integrity of the panel all holes punch outs for conduit and w...

Page 8: ...power inputs for meter reference voltage and panel power to allow the hub and meter to remain powered if the circuits being monitored need to be off 2 3 Connecting Current Transformers 2 3 1 CT input...

Page 9: ...X1 X2 C Black White Black X2 X1 X2 White Black X1 X2 L3 L2 L1 N X1 White A B C N X1 X2 A X1 X2 B X1 X2 C Black White Black X2 X1 X2 White Black X1 X2 L3 Diagram 1 1 Phase Line to Neutral 2 Wire System...

Page 10: ...el Number STEP PS 277AC 24DC 3 5 2904945 3 2 2 Nominal Input Voltage Range 100 VAC 277 VAC 3 2 3 Nominal Output Voltage 24 VDC 3 2 4 Nominal Output Current 3 5A 3 3 Leviton 4DUMR Power Meter Descripti...

Page 11: ...een 3 3 2 2 Press to go to the ADDR screen and through the address digits Use or to select the Modbus address default is 001 Leave at 001 unless otherwise instructed 3 2 2 3 Press to accept the value...

Page 12: ...ze in amps default is 100 3 3 3 7 Press to accept the value and go back to the S CT screen 3 3 4 To Enter the service type to be monitored 3 3 4 1 Navigate to the S SYS Set System Setup screen 3 3 4 2...

Page 13: ...1 Terminals and Port Diagram USB Port 3 INTERNAL COMPONENT CONFIGURATION AND OPERATION Power Terminal Menu and Select Buttons RS485 Modbus RTU Port Ethernet Port 3 4 2 LED Description Alive Blinks onc...

Page 14: ...g 3 5 1 2 To confirm you have established connection to the device do a ping to the IP address shown in the DAS s LCD display If no packets were lost the connection is working and you are ready to pro...

Page 15: ...RATION 3 5 1 6 Enter the desired admin user password in both boxes and click the Apply button 3 5 1 7 A Thank You message will be displayed confirming that the password was successfully set Click on t...

Page 16: ...p Check Allow Remote Access Click Apply 3 5 1 9 Once Remote Access Successfully Connects you will receive the message R Access Online Record Serial Number Pin 3 5 1 10 Call provider and provide Serial...

Page 17: ...s is 192 168 40 50 3 6 7 Scroll through the menu options and select Previous Menu to return to the home menu options This change will require a reboot 3 6 8 Click Select button to execute the reboot 3...

Page 18: ...rminated to local code Bottom knockouts are appropriately sealed and weatherproofed RS485 communication is terminated properly to terminal Power Supply Light DC OK is Green Meter LCD is on and cycling...

Page 19: ...e trademarks of their respective owners such use is not meant to imply affiliation sponsorship or endorsement Modbus is a U S registered trademark of Schneider Electric USA Inc Belden is a trademark o...