Installation Guide
Power Monitoring
Series 4100 Modbus
TM
2
CONTROL POWER
AC
5 VA max.; 90V min.;
UL Maximums: 600 V
L-L
(347 V
L-N
); CE Maximum: 300 V
L-N
DC*
3 W max.; UL and CE: 125 to 300 VDC
Ride Through Time
100 msec at 120 VAC
OUTPUT
Alarm Contacts
N.C., static output (30VAC/ DC, 100mA max. @ 25°C,
derate 0.56mA per °C above 25°C)
Real Energy Pulse Contacts
N.O., static output (30 VAC/ DC, 100 mA max. @ 25°C,
derate 0.56 mA per °C above 25°C)
RS-485 Port
2-wire, 1200 to 38400 baud, Modbus RTU
MECHANICAL CHARACTERISTICS
Weight
0.62 lb (0.28 kg)
IP Degree of Protection
(IEC 60529)
IP40 front display; IP20 Meter
Display Characteristics
Back-lit blue LCD
Terminal Block Screw Torque
0.37 to 0.44 ft-lb (0.5 to 0.6 N·m)
Terminal Block Wire Size
24 to 14 AWG (0.2 to 2.1 mm
2
)
Rail
T35 (35mm) DIN Rail per EN50022
OPERATING CONDITIONS
Operating Temperature Range
-30° to 70°C ( -22° to 158°F)
Storage Temperature Range
-40° to 85°C ( -40° to 185°F)
Humidity Range
<95% RH noncondensing
Altitude of Operation
3000 m
COMPLIANCE INFORMATION
US and Canada
CAT III, Pollution degree 2;
for distribution systems up to 347V
L-N
/ 600VAC
L-L
CE
CAT III, Pollution degree 2;
for distribution systems up to 300V
L-N
Dielectric Withstand
Per UL 508, EN61010
Conducted and Radiated
Emissions
FCC part 15 Class B, EN55011/EN61000 Class B (residential and light
industrial)
Conducted and Radiated
Immunity
EN61000 Class A (heavy industrial)
US and Canada (cULus)
UL508 (open type device)/CSA 22.2 No. 14- 05
Europe (CE)
EN61010-1
Specifications (cont.)
SunSpec Alliance
Interoperability
Specification
Compliance
* External DC current limiting is required, see fuse recommendations.
This meter implements the draft SunSpec 1.0 common elements starting at base 1 address 40001, and the proposed SunSpec 1.1
meter model at 40070 (these addresses are not in Modicon notation).
The SunSpec Alliance logo is a trademark or registered trademark of the SunSpec Alliance.