Installation Guide
Power Monitoring
Series 4100 Modbus
TM
15
B
a
c
k
To
S
E
TU
P
UI for Setup
From:
To Setup p. 2
“SPASS”
Back
S COM
RS-485
Output
ADDR
--------
001
BAUD
--------
38400
19200
9600
4800
2400
1200
PAR
--------
nOnE
EvEn
Odd
Next
Set Communications Parameters:
ADDR - Modbus Address:
1
– 247.
+
increments the selected (blinking) digit.
-
selects the digit to the left.
BAUD - Baud Rate:
1200
– 38400 Baud
PAR - Parity:
Odd, Even, None
+
or
–
to step through the options.
SETUP > PASWD
Back
Current
Transformer
S CT
CT V
--------
1.0
.33
CT SZ
--------
100
Next
Set Current Transducer:
CT V
- CT Input Voltage: + or
–
to Select 1.0 or .33V.
CT SZ -
CT Size: in Amps. Maximum is 32000 Amps.
Back
S SYS
SYSTM
--------
3L-1n
3L
2L-1n
Set
System Configuration:
SYSTM: +
or
–
to step through the following System Type options:
System Reg 130 CTs Description
3L-1n
40
3
Wye Three Phase: A, B, & C with Neutral (Default).
3L
31
3
Delta Three Phase: A, B & C; no Neutral
System
Type
2L
1L-1n
Next
2L-1n
12
2
Single Split Phase: A & B with Neutral
2L
11
1
Single Phase: A & B; no Neutral
1L-1n
10
1
Single Phase: A to Neutral
Back
S PT
RATIO
--------
001.00
Set Potential Transfomer Ratio:
RATIO
–
Potential transformer step down is RATIO:1. Default is 1:1
(No PT installed). See Install for wiring diagrams. This value must be
set before the System Voltage (if used).
Potential
Transformer
Back
S
V
Sytem
Next
V LL
--------
00600
Set System Voltage:
V LL
–
The nominal Line to Line Voltage for the system. This is used
by the meter to calculate the theoretical maximum system power, and
as the reference voltage for setting the Phase Loss threshold.
Maximum is 32000 Volts. For system type 1+N (10), this is a Line to
Neutral Voltage, indicated by
“V LN”. Note: the meter will reject settings
Voltage
Next
that are not within the meter
’s operating range when divided by the PT
ratio.
Back
Sytem
S PWR
MX KW
--------
103.92
System Power:
MX KW
–
The theoretical Maximum System Power is calculated by the
meter from the System Voltage, CT size, and System Type. Power
Factor is assumed to be unity. The value of System Power is used to
determine which combinations of pulse weight and duration are valid
and will keep up with the maximum power the meter will see. This value
Voltage
Next
is read only.
To Setup p. 2
“SPLOS”
Note:
Bold
is the Default.
In meter kits, Input Voltage and CT Amperage are
factory preset to appropriate settings. Do not modify
.