4.7.5 Muting restart
Following a muting fault (e.g. muting timeout, failure of the supply voltage), the restart button can be used
to override the muting path even if the protective field is interrupted see chapter 8.6.2 „Muting restart“.
4.7.6 Alternative connection for second muting signal
Particularly in cases in which the second independent muting signal comes, for example, from a control,
it is advantageous to connect this signal to the machine interface (8-pin plug). In operating modes 2, 3, 4
and 6, the second muting signal can alternatively be connected to input MS2 of the 8-pin plug or to input
MS2 of the local interface (5-pin socket).
1
M-EN / TO = high -> muting timeout extension
2
Start of the muting timeout extension
3
End of the additional muting timeout extension
Figure 4.6: Muting timeout extension
1
M-EN / TO = low -> no muting timeout extension
Figure 4.7: No valid signal for timeout extension
MS1
MS2
Muting
max. 10 min
Muting-EN/TO
t
max. 8h
2
3
1
MS1
MS2
Muting
Muting-TO
t
max. 10 min
1
The muting signal from the control must not be applied constantly; rather, it must only be activat
-
ed if muting is required.