Leuze electronic DMU318 W Series Manual Download Page 7

Leuze electronic GmbH + Co. KG

In der Braike 1 D-73277 Owen 

DMU318-400.W…-M12 - 01

DMU318-1600.W…-M12 - 01

Device functions – analog output

In measurement operation, the 

blue LED

 displays the behavior of analog output 

Analog OUT

Analog output Analog OUT

Note!

When setting the analog output (teach) via the teach button, one 

rising characteristic curve

 is always taught; with 

2-point teach, independent of the selected object distances near/far. The characteristic output curve can be inverted, 
however.

Adjusting the analog output via the teach button

On delivery, the characteristic output curve of the sensor is set as a rising characteristic curve with spread over the entire scanning range: 
4 … 20mA or 0 … 10V corresponds to an object distance of 50 … 400mm or 150 … 1600mm, respectively.

The analog output can be set by means of 1-point teach or 2-point teach. 

Note!

When setting the analog output (teach) via the teach input, one 

rising characteristic curve

 is always taught; with 2-point 

teach, independent of the selected object distances near/far. The characteristic output curve can be inverted, however.

Selecting the output that is to be taught: OUT1 or Analog OUT

1.

Press the 

teach button

 for 

≥ 2s

 to 

activate

 

teach mode

. The 

yellow LED (OUT 1) flashes

 at 1Hz. 

While in this state, 

output OUT 1

 can be taught.

2.

To teach 

output Analog OUT

briefly 

 press the 

teach button

 again. The 

blue LED (Analog OUT)

 now flashes at 1Hz. 

While in this state, 

output Analog OUT

 can be taught.

3.

Briefly press the teach button again to toggle between outputs 

OUT 1

 and 

Analog OUT

 in this state. The flashing LED indicates 

which output is ready for teaching: 

yellow LED flashing = OUT 1 ready for teaching

blue LED flashing = Analog OUT ready for teaching.

Rising characteristic curve

Falling characteristic curve

Dea

d zone

Sensor

Error

Approx.

11V

Approx.

21mA

Start point

 

0V

4mA

Object distance

Remote error

Object outside of 
the measurement range

Error

Approx.

3.8mA

End point

 

10V

20mA

Measurement range

Close error

:

Object outside of

the measurement range

Object within measurement range

Blue LED 

ON

Dea

d zone

Sensor

Object distance

Error

Approx.

11V

Approx.

21mA

Error

Approx.

3.8mA

Remote error

Object outside of 
the measurement range

Close error

:

Object outside of

the measurement range

Start point

 

10V

20mA

End point

 

0V

4mA

Measurement range

Object within measurement range

Blue LED 

ON

DMU318…W

90° angled ultrasonic sensors with analog and switching output

Summary of Contents for DMU318 W Series

Page 1: ...PN NO NC function reversible NEW Both outputs can easily be taught using a button NEW Stable plastic design NEW Temperature compensated scanning range 50 400mm 150 1600mm 10 30 V DC 4 20mA 0 10V Acces...

Page 2: ...utton 12s Indicators Yellow LED OUT2 object detected Blue LED Analog OUT object detected Yellow green or blue green LED flashing Teach in teaching error Green LED Object within the scanning range Mech...

Page 3: ...contact preset C Analog output 4 20mA V Analog output 0 10V Pin assignment of connector pin 5 gray cable wire Sync MUX K Synchronization multiplex input Connection technology M12 M12 connector 5 pin...

Page 4: ...rmally closed Close Far Far Close Dead zone Sensor OUT1 active Yellow LED ON Green LED OFF OUT1 not active Yellow LED OFF Green LED ON Distance Hysteresis Switching point Scanning range OUT1 not activ...

Page 5: ...th 2 point window teach as a function of the switching function 1 Place object at desired switching distance 1 First place object at desired switching distance for switching point 1 2 To adjust the ou...

Page 6: ...output is changed to the opposite state toggled First activate the previously described teach mode for output OUT 1 Changeover of the switching function 1 To change the switching function of output O...

Page 7: ...that is to be taught OUT1 or Analog OUT 1 Press the teach button for 2s to activate teach mode The yellow LED OUT 1 flashes at 1Hz While in this state output OUT 1 can be taught 2 To teach output Ana...

Page 8: ...ning range of 400mm 90mm scanning range of 1600mm 310mm 2 To adjust analog output Analog OUT press the teach button for 2 7s until the blue and green LEDs flash simultaneously at 3Hz 3 Release the but...

Page 9: ...of the same type are wired together in a network according to the following diagram The devices work in synchronous operation with a simultaneous transmission pulse The response time of the individual...

Page 10: ...factory setting 1 switching point at 400mm or 1600mm rising characteristic curve with spread over the entire scanning range Resetting to factory settings 1 When switching on the supply voltage during...

Reviews: